An end-to-end supervised learning method is developed to classify transmission line faults in a twoyear field-recorded dataset that includes synchronized measurements of three-phase voltages recorded by 38 Phasor Measurement Units (PMU) sparsely located in in the US Western Grid interconnection. Statistical analysis is performed to extract features from this large dataset to train Support Vector Machine (SVM), Random Forest (RF), and eXtreme Gradient Boosting (XGBoost) classifiers initially. The training further leverages a simulated dataset from a synthetic grid with 12 PMUs to increase the number of faults of types infrequently seen in the field-recorded dataset. Training the classification models with the combined dataset resulted in a classification accuracy of 97.7%. This is a significant improvement over 89.7% to 92.5% accuracy obtained by relying on the field-recorded dataset alone.