DOE OSTI · 1891312
Line Faults Classification Using Machine Learning on Three Phase Voltages Extracted from Large Dataset of PMU Measurements
Also available from
Abstract
An end-to-end supervised learning method is developed to classify transmission line faults in a twoyear field-recorded dataset that includes synchronized measurements of three-phase voltages recorded by 38 Phasor Measurement Units (PMU) sparsely located in in the US Western Grid interconnection. Statistical analysis is performed to extract features from this large dataset to train Support Vector Machine (SVM), Random Forest (RF), and eXtreme Gradient Boosting (XGBoost) classifiers initially. The training further leverages a simulated dataset from a synthetic grid with 12 PMUs to increase the number of faults of types infrequently seen in the field-recorded dataset. Training the classification models with the combined dataset resulted in a classification accuracy of 97.7%. This is a significant improvement over 89.7% to 92.5% accuracy obtained by relying on the field-recorded dataset alone.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Otudi, Hussain, Dokic, Tatjana, Mohamed, Taif, Kezunovic, Mladen, Hu, Yi, Obradovic, Zoran. 2022-01-04. Line Faults Classification Using Machine Learning on Three Phase Voltages Extracted from Large Dataset of PMU Measurements. https://doi.org/10.24251/hicss.2022.425. https://searchnasa.com/record/osti%3A1891312/line-faults-classification-using-machine-learning-on-three-phase-voltages-extracted-from-large-datas
Citations retain the original authors and DOI and include this site’s record URL. If this discovery service contributed to your research, you can also cite Search NASA by Indiciae: BibTeX · RIS.