DOE OSTI · 1906850
A Current Limiting Control Strategy for Single-Loop Droop-Controlled Grid-Forming Inverters Under Balanced and Unbalanced Faults
Abstract
Existing studies reporting current limiting control strategies for grid-forming inverters primarily focus on grid-forming inverters that use a multi-loop control structure. This study reports a current limiting control for grid-forming inverters that uses a single-loop control structure. The proposed current limiting control was implemented at the pulse width modulation (PWM) control layer to guarantee a rapid response. Once an overcurrent caused by severe faults is detected, the proposed control strategy immediately blocks relevant insulated-gate bipolar transistors (IGBTs) using a hysteresis loop, ensuring that the overcurrent is limited within a few PWM cycles. After the fault is cleared, the inverter seamlessly transfers back to droop control mode to maintain stability. The current limiting control has been tested in a microgrid environment operating in the OPAL-RT platform. Study results show that the control strategy can effectively limit the overcurrent under both balanced and unbalanced faults and can maintain system transient stability after the fault is cleared.
Keep this discovery
Explore connections, maps & timelines
Du, Wei, Nguyen, Quan H., Liu, Yuan, Mohiuddin, Sheik Mohammad. 2022-11-30. A Current Limiting Control Strategy for Single-Loop Droop-Controlled Grid-Forming Inverters Under Balanced and Unbalanced Faults. https://doi.org/10.1109/ecce50734.2022.9947505
Cite the original work for its findings. Save a collection to share your selection of sources.