Site Ambient Temperatures and Operating Schedules for EIC - Utility CW Considerations
Abstract
The heat dissipated by the EIC accelerator system and components is ultimately removed by the conventional water-cooling systems that will be ultimately dissipated the waste heat to the atmosphere. An estimated 45 MW of heat will be dissipated to water during full beam operation and that will need to be effectively rejected to the atmosphere. Approximately 50% of the heat is required to be rejected to a low temperature heat sink that cannot be achieved by an evaporative cooling tower during summer. To operate during these summer months, a secondary chilled water refrigeration system will be required that would increase the cost of the cooling water system. Further, operating chiller compressor in the summer months will increase the energy consumption of the machine. This analysis is being prepared to evaluate the impact on operating and capital costs on the cooling system for various summer operating schedules while utilizing the most cost-effective scenario of an evaporative cooling system. The technology selection for the various heat sinks is addressed in a separate write-up and are not expected to change the conclusions of this write-up.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Srinivasan, Ram. 2021-11-01. Site Ambient Temperatures and Operating Schedules for EIC - Utility CW Considerations. https://doi.org/10.2172/1969914