Search NASA⌕ Search

DOE OSTI · 2007869

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Also available from

Abstract

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Chang, Heather, Baeckeland, Nathan, Banerjee, Abhishek, Seo, Gab-Su. 2023-08-22. Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition. https://doi.org/10.23919/icpe2023-ecceasia54778.2023.10213932

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Performance Evaluation of a Single-Phase Grid-Forming Inverter Through Hardware Experiments

This study conducts hardware experiments to assess the performance of a commercial single-phase grid-forming (GFM) inverter using a purely hardware-based approach. We adhere to a testing protocol for the GFM inverter and enhance it by exploring the transient performance of GFM inverters across various grid dynamic events. Quantifiable performance metrics are established for each testing scenario to gain insights into the performance of the single-phase GFM inverters. Based on the comprehensive tests, the following observations are summarized: 1) The performance of the single-phase GFM inverter is satisfactory, and it is capable of being the islanding master for residence homes when the main grid is gone. 2) For frequency response, the inverter is able to stay connected but cannot inject the needed active power to support the grid. This may be improved by the manufacturer by using droop control. 3) The GFM inverter exhibits harmful transients in voltage and frequency during islanding operation, which can be enhanced by maintaining the same operating points before and after the breaker is open.

black start↗

Black-Starting Microgrids Using Inverter-Based Distributed Energy Resources

Recent trends in power systems show increasing deployment of inverter-based distributed energy resources (DERs) at the distribution level. Efforts have also been made to use inverter-based DERs for system restoration of critical sections of distribution feeders. In the past few years, there has been active consideration of using local grid-forming (GFM) DERs, which can form their own voltage and frequency, to black-start microgrids instead of waiting for the bulk system for supply restoration. However, using current-limited inverter-based DERs for black-start operations with high inrush currents can pose some technical challenges. This paper presents detailed electromagnetic transient studies on a digital real-time simulator to assess the operational feasibility of using local inverter-based GFM DERs for microgrid black-start operations as a bottom-up approach instead of a top-down approach where the substation is used to restore critical sections of the feeder. The paper presents key modeling details for distribution system components for studying GFM DER-based microgrid black-start operations. The paper presents simulation results comparing different black-start approaches using GFM DERs for two test systems: i) a simple test microgrid and ii) a real-world utility microgrid currently being designed and deployed by Holy Cross Energy in Colorado.