Search NASA⌕ Search

DOE OSTI · 2205669

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint

Abstract

This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Wang, Jing, Ganguly, Subhankar (ORCID:0000000333070614), Kroposki, Benjamin. 2023-11-07. Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint. https://www.osti.gov/biblio/2205669

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Small-Signal Stability Support from Dynamically Configurable Grid-Forming/Following Inverters for Distribution Systems

The growth of inverter-based resources (IBRs) in modern power systems can challenge system stability since they do not natively provide inertia, prompting a need to develop new methods to address the potential instabilities. In this paper, a dynamically configurable grid-forming (GFM) and grid-following (GFL) control is proposed, which enables inverters to flexibly transition to support system needs. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small-signal stability margin. In addition, a holistic and detailed small-signal model for a distribution feeder that captures the dynamics from both synchronous generators (SGs) and IBRs is also derived and used to evaluate the effectiveness of the proposed GFM/GFL controls to augment the system small-signal stability margin. Case studies with varying levels of IBRs were implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach.

grid-following control↗

Small-Signal Stability Support from Dynamically Configurable Grid-Forming/Following Inverters for Distribution Systems: Preprint

As the penetration of inverter-based resources (IBRs) continues to increase in modern power systems, system stability is challenged by the insufficient inertia induced by IBRs; hence, there is a need to develop various methods to address the potential instabilities. In this paper, grid-forming (GFM) and grid-following (GFL) controls are implemented for inverters with flexible-mode transitions between them. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small signal stability margin. Further, a holistic and detailed small signal model of the entire system with the dynamics from both synchronous generators (SGs) and IBRs is derived. The effectiveness of the proposed work in adjusting the system small signal stability margin is validated by conducting case studies with varying penetration levels of IBRs. A test system with one SG and five inverters was implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach. Index Terms - grid-following control, grid-forming control, operation mode transition, small-signal stability analysis

grid-following control↗