Abstract
Grid-forming control is regarded as a promising technology for achieving high levels of renewable energy integration in future power grids. To fulfill this role, grid-forming devices is expected to possess fault ride through capability. This paper focuses on the transient stability of a droop control-based grid-forming inverter that utilizes current reference saturation as a current limiting strategy. The objective of this work is to investigate the fault recovery process of the grid-forming inverter and analyze the criterion for transitioning the inverter out of the current limiting mode. The theoretical analysis in this study is validated through time-domain simulations, which compare the results obtained using the circuit current limiting method and the d-axis priority-based current limiting method. Various operational conditions are considered to comprehensively evaluate the performance of the grid-forming inverter during a three-phase short circuit scenario. The simulation results confirm the effectiveness of the proposed theoretical approach.
Keep this discovery
Explore connections, maps & timelines
Lyu, Xue, Du, Wei, Mohiuddin, Sheik Mohammad, Nandanoori, Sai Pushpak, Elizondo, Marcelo A.. 2024-03-08. Improved Transient Stability Analysis of Multi-loop Droop-Controlled Grid Forming Inverters with Current Reference Limiter. https://www.osti.gov/biblio/2429554
Cite the original work for its findings. Save a collection to share your selection of sources.