Abstract
This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.