Utility Experience with Inverter Based Resource Impacts on Transmission Protection

Abstract

High penetration of inverter-based resources (IBR) can adversely affect the transmission protection schemes in the area. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems because the existing system has been designed based on the fault current response of conventional rotating-machine-based generators. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. It includes a broad review of all challenges that system protection has experienced so far with high penetration of IBRs. Key issues have been identified based on a survey of different utility protection engineers. Finally, fault event recordings are shown to demonstrate some actual cases of mis-operations of relays near IBRs.

Explore related subjects

Keep this discovery

BibTeXRIS

Saeed, Ajmal [Pacific Gas and Electric, Oakland, CA (United States)], Jensen, Mike [Pacific Gas and Electric, Oakland, CA (United States)], Zamani, Amin [Quanta Technology, Raleigh, NC (United States)], Reno, Matthew [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)], Bidram, Ali [Univ. of New Mexico, Albuquerque, NM (United States)], Raffield, Taylor I. [Duke Energy, Charlotte, NC (United States)]. 2025-02-01. Utility Experience with Inverter Based Resource Impacts on Transmission Protection. https://doi.org/10.2172/2572378

Cite the original work for its findings. Save a collection to share your selection of sources.

Discover connections

Connections use source metadata and explicit phrase matches, not verified experimental comparisons.

KEEP EXPLORING

Related reports

Utilities Perspective on Protection Challenges with High IBR Penetration

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, we are looking broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the presentation summarizes on gathered data and internal experiences.

24 POWER TRANSMISSION AND DISTRIBUTION

A Sensitivity-driven Wide Area Protection (SWAP) Coordination Tool for High Penetration of Inverter-based Resources (IBR)

Traditionally, power system generation sources have been composed of synchronous generators, of which the fault current behavior is understood with minimal differences between generation size and types due to the physics of their construction. Present protection schemes and modeling methods are based upon these understood characteristics. Most renewable generation is composed of inverter-based resources (IBR), in which fault current is determined by switching control software and hardware limitations, each of which can vary between manufacturers and even between models of the same manufacturer. The resulting fault current is low in magnitude, low in negative-sequence current, unpredictable phase angles, and is a challenge to model. These characteristics also result in a challenge to traditional protection schemes and fault simulation software. To address several of these concerns, the project has the following goals: 1. Improve IBR models: Improve IBR models used in short circuit (SC) programs to accurately capture the response of IBRs at the bulk power system (BPS) level for fault and protection studies. 2. Develop automation tool: Develop an automation tool that allows engineers to identify protection coordination and sensitivity issues by performing SC and protection coordination studies in a high IBR-penetrated grid by applying variations to the IBR models, faults, contingencies, etc. 3. Develop schemes: Develop new protection mitigation solution schemes that complement the existing protection systems to ensure safe operation of the BPS with higher IBR penetration levels. The project team did not achieve this final goal, as the Department of Energy (DOE) stopped the project early due to changes in DOE funding priorities. The termination notice came at the beginning of the final project phase, while the team was identifying and beginning to investigate protection issues. It should be noted that the team discussed a 100% penetration scenario. However, this scenario would require the use of grid-forming IBR models that are not presently available. Since developing these models requires additional effort, the 100% penetration scenario was not pursued during this project. In the future, developing the methodology and models for the 100% scenario could benefit the industry.

14 SOLAR ENERGY

End-To-End Decentralized Transmission Line Protection in IBR-Dominated Weak Grids Using Interpretable Data-Driven Methods

Traditional transmission line protection relies on predictable synchronous-based fault signatures, which frequently fail under the non-standard, current-limited fault characteristics of Inverter-Based Resources (IBRs). This study investigates how to achieve secure, communication-free fault isolation in IBR-dominated weak grids without relying on opaque, computationally heavy "black-box" machine learning algorithms. To address this, we propose a novel, standalone, and inherently interpretable data-driven protection framework. Unlike centralized methods requiring multi-terminal communication, this decentralized approach relies solely on local measurements using a hierarchical linear-kernel Support Vector Machine (SVM). The methodology decomposes the protection task into four sequential stages that mimic traditional protection elements: fault detection and fault direction identification, fault type classification, zone classification, and location estimation. This multi-stage architecture allows for specialized feature engineering at each stage, combining high computational efficiency with logic traceability. The framework's end-to-end performance was validated via C-code and PSCAD/EMTDC co-simulation, utilizing a real-world utility network and an OEM black-box IBR model. The proposed relay achieves 97.2% overall accuracy and provides a reliable trip decision within a 2.5-cycle window. The results confirm 100% accuracy in fundamental fault detection, reliable zone selectivity across low to moderate fault resistances, and robust security against non-fault transients, proving its immediate viability for integration into commercial numerical relays.