DOE OSTI · 2588553
Laboratory Testing and Performance Characterization of the High Efficiency Dehumidification System (HEDS) Technology
Abstract
The high efficiency dehumidification system (HEDS) is a unique air handling unit (AHU) design with two water coils. Connected in series, these water coils can sensibly reheat the airstream after it is cooled and dehumidified, thereby mitigating (or sometimes eliminating) the need for conventional sensible reheat with additional energy from hot water, electric resistance or steam coils. Another unique design feature is the size of the HEDS primary cooling coil. While typical AHU cooling coils have a 6-row geometry, the HED's cooling coil has a deeper 10-row geometry enabling discharge air dew point temperatures at or below 55 degrees F despite warmer chilled water supply temperatures approaching (sometimes exceeding) 50 degrees F. The ability to meet acceptable discharge air dew points with warmer chilled water supply temperatures improves both operational efficiency and system resilience against chilled water plant operational or control issues. This report summarizes the 59 steady-state test results that form a comprehensive performance map of the HEDS technology including its reheat capability. The breadth of outdoor air conditions and flow rates over which the HEDS technology was tested and characterized encompasses the unit 1) operating as a dedicated outdoor air system or mixed air system and 2) controlled with constant air volume or variable air volume fan control.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Shoukas, Greg [National Renewable Energy Laboratory (NREL), Golden, CO (United States)] (ORCID:0000000172974240), Doebber, Ian [National Renewable Energy Laboratory (NREL), Golden, CO (United States)], Cu, Khanh Nguyen [National Renewable Energy Laboratory (NREL), Golden, CO (United States)], Desai, Jal [National Renewable Energy Laboratory (NREL), Golden, CO (United States)], Salasovich, Jimmy [National Renewable Energy Laboratory (NREL), Golden, CO (United States)]. 2025-09-09. Laboratory Testing and Performance Characterization of the High Efficiency Dehumidification System (HEDS) Technology. https://doi.org/10.2172/2588553
Cite the original work for its findings. Save a collection to share your selection of sources.