Experiments on a vapor compression air conditioner with liquid desiccants for efficient dehumidification

Abstract

Buildings require air conditioning systems that not only cool and dehumidify supply air but also provide sufficient ventilation to ensure indoor air quality and occupant comfort. However, standard recirculation systems-which introduce about a 10 % to 20 % fraction of outdoor air-often fail to deliver air that is precisely cooled and dry, particularly because 80-90 % of the ventilation cooling load is latent. Mixing humid ventilation air with recirculated indoor air increases the energy and costs required to condition the air to comfortable levels. Dedicated outdoor air systems (DOASs) are designed to handle this latent dominated ventilation load and thus need to have efficient humidity removal. Many cooling cycles can perform this task. Here we describe a liquid desiccant DOAS, which combines a vapor compression cycle and a liquid desiccant absorber and desorber pair. We present its performance at 26 operating conditions and a thermodynamic model which can accurately predict the moisture removal efficiency. The model's performance predictions have a mean percentage error of 2.5 % and a coefficient of variation of the root mean square error of 7.5 %. We also compare the performance of this vapor-compression-coupled liquid desiccant system with a standard vapor compression system with the same components but no liquid desiccant. For the 26 conditions tested in this study, this comparison shows that adding liquid desiccants lowers the required evaporator cooling load by 21 %, allows for 25 % lower compressor volumetric capacity, and 25 % lower electricity use. Future work will leverage this model to quantify the reduction in annual electricity use across different climates, including the need for a standard vapor compression system to reheat the air during some of the year.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Woods, Jason [National Renewable Energy Laboratory (NREL), Golden, CO (United States)] (ORCID:0000000276612658), Shoukas, Greg [National Renewable Energy Laboratory (NREL), Golden, CO (United States)] (ORCID:0000000172974240), Lu, Zechao [National Renewable Energy Laboratory (NREL), Golden, CO (United States)] (ORCID:0000000307472820), Kozubal, Eric [National Renewable Energy Laboratory (NREL), Golden, CO (United States)] (ORCID:0000000261953126). 2025-10-28. Experiments on a vapor compression air conditioner with liquid desiccants for efficient dehumidification. https://doi.org/10.1016/j.enconman.2025.120683

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Building the Business Case with JUSTIFI: Quantifying Multiple Benefits in the Automotive Industry

The Michigan State University Industrial Training and Assessment Center (MSU ITAC) conducted a pilot study at an automotive parts manufacturer in Michigan. The study identified energy-productivity enhancements through the application of the JUSTIFI software. Key recommendations included replacing six inefficient rooftop units (RTUs) with a new air rotational unit. By quantifying operational savings for this project, the expected payback period went from 6.6 years to 1.4 years. Additionally, the installation of variable frequency drives (VFDs) on condenser tower motors was suggested. By including all operational benefits, the payback period was reduced from 8.2 years to 1.3 years. This comprehensive analysis aims to bolster the manufacturer's goals of reducing energy while enhancing overall operational efficiency.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A Physics-Informed Reinforcement Learning Framework for Economic-Thermal Co-Optimization of Crypto Mining Data Centers: Preprint

The rapid expansion of cryptocurrency mining has created a new class of high-density data centers characterized by extreme thermal flux and high sensitivity to volatile economic markets. Traditional thermal management strategies, typically reliant on rule-based control, maintain static setpoints that fail to account for fluctuating electricity prices and cryptocurrency values - factors critical to mining profitability. To address this, we present a physics-informed reinforcement learning (PIRL) framework for economic-thermal co-optimization in crypto mining data centers. This framework consists of a proximal policy optimization (PPO) agent, a virtual testbed powered by high-fidelity physics-based models, and an interactive frontend dashboard. The PPO agent is trained using the virtual testbed and strict hardware safety limits. This physics-informed approach allows the agent to learn a stochastic policy that dynamically balances mining revenue against operational costs by co-optimizing HVAC cooling setpoints and IT computational hashrate. The simulation results demonstrate that the integrated framework achieved an 8.62% increase in net operational profit compared to traditional baseline strategies while strictly adhering to safety-critical temperature constraints (coolant supply temperature < 32 degrees C). This work provides a scalable template for the deployment of reinforcement learning in mission critical facilities where economic volatility and physical safety must be managed simultaneously.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Field Validation of a Grid-Interactive Efficient Building Software Solution

The U.S. General Services Administration's (GSA's) Green Proving Ground (GPG) program, in partnership with the National Laboratory of the Rockies (NLR), completed a field study of a Grid-Interactive Efficient Buildings (GEB) software solution. The study focused on a single testbed facility to test the GEB functionality of the software solution, along with other features. The testbed facility - a courthouse - is a common building type in GSA's vast building portfolio, offering potentially impactful findings on a scalable level. The study evaluated Prescriptive Data's technology, Nantum OS, a connected building operating system ("GEB Solution") which aggregates multiple sources of previously siloed building data and combines that data with external sources, such as weather information or utility signals, into a single integrated platform. A GEB Solution is a type of Energy Management Information System (EMIS). EMIS is defined as a system of devices, data services, and software applications that communicates with any building system or third-party data source to aggregate and transform data into new capabilities to aid in the optimization of energy use at the building, campus, or agency level. This specific GEB Solution is an EMIS with ASO, automated system optimization, offering supervisory control of certain aspects of the Building Automation System (BAS). Multiple features were evaluated including, but not limited to, Continuous Demand Management to avoid setting new monthly kilowatt (kW) peaks, energy efficiency for reduction of kilowatt hours (kWh) and natural gas consumption, and automated demand response (ADR) for purposes of lowering demand during a utility called Demand Response (DR) event. The testbed facility was the Foley Federal Building and US Courthouse ("Foley Federal Building") located in Las Vegas, NV. This is a 209,496 sq. ft. building constructed in the 1960s with major renovations in 2004. The facility was a good candidate due to the large prevalence of office and courthouse spaces in the GSA portfolio of buildings. It also has many features which allow integration into and control of the building and a strong facilities team to assist with the study. Quantitative and qualitative performance objectives were developed using GSA's GPG GEB project template along with input from the vendor and building facility staff; these are outlined in Table 1. The quantitative performance objectives focused on continuous demand management, energy efficiency, and automated demand response. The qualitative performance objectives focused on the ease of installation and commissioning as well as the operability of the GEB solution. Other performance metrics that are reported on include carbon reduction, cost effectiveness, and occupant acceptance.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗