Dielectric Spectroscopy Cable NDE for Unequal Aging Over Different Lengths

Abstract

This Pacific Northwest National Laboratory milestone report assesses the effect of unequal aging over different lengths of cable on dielectric spectroscopy (DS) bulk impedance measurements from the cable end. DS measurements can indicate the remaining useful life of cables; however, most benchmark tests are based on accelerated aging of the entire cable. If only a portion of the cable is exposed to a harsh environment (as is frequently the case), the DS measurement will indicate a significantly less-aged cable than if the entire cable were exposed to a uniform environmental stress. The DS measurement is primarily related to the intrinsic insulation material relative permittivity—typically between 1.5 and 3.0. Insulation aging increases permittivity and, correspondingly, the cable’s overall capacitance measured from the cable end. To judge the health of the overall cable system, operators are primarily interested in the condition of the most severely aged section since that is where a failure is most likely to occur. This can be expressed as the dimensionless relative permittivity of the severely aged section divided by the permittivity of a pristine cable. This relative permittivity is an intrinsic material parameter independent of cable length and can serve as a quantitative indication of the insulation condition. If the relative percentages of cable exposed to a harsh and benign environment are known, the DS measurement of the entire cable length, including both pristine and aged sections, can be compensated to predict the relative permittivity (relative to pristine permittivity) of the most severly aged segment. A test was performed on three 50 ft (16 m) cables with 10%, 50%, and 90% of the cable inside a thermal aging oven. Predictably, the aging effect on the DS response was greatest in the 90% sample, followed by the 50% sample, and then the 10% sample. The more interesting result is the ratio of the aged insulation permittivity to the pristine insulation permittivity. Based on prior work, an end-of-life cable has a value of approximately 1.35. If the relative percentages of pristine and severely aged cable lengths are known, and the total cable-length capacitance of the initial pristine cable and the combined pristine plus aged cable are known, the relative aged permittivity (ratio of aged section permittivity / pristine section permittivity) can be estimated. The relative cable lengths exposed to a harsh environment may be known or estimated based on plant layout drawings or cable reflectometry tests that can locate the oven entry and exit points. The compensation was verified using a lumped-parameter model to predict the aged-segment permittivity e2/e1, where e2 is the aged-segment permittivity and e1 is the pristine-segment permittivity. For all three percentages of aged cable lengths, the ratio was quite similar, as would be expected since all cable segments were exposed to the same aging environment. This ratio of aged permittivity to pristine permittivity can be compared to other damage indicating tests, including elongation at break, to assess cable condition.

Explore related subjects

Keep this discovery

BibTeXRIS

Glass, Samuel W., Elen, Muthu (ORCID:0000000261927091), Fifield, Jacob. 2026-08-28. Dielectric Spectroscopy Cable NDE for Unequal Aging Over Different Lengths. https://doi.org/10.2172/3684099

Cite the original work for its findings. Save a collection to share your selection of sources.

Discover connections

Connections use source metadata and explicit phrase matches, not verified experimental comparisons.

KEEP EXPLORING

Related discoveries

Strategies for Fabricating Molybdenum Structures Using Laser Powder Bed Fusion

Advances in manufacturing techniques are viewed as enabling technologies for development of high performance nuclear fuel forms that couple high uranium density with improvements to key properties such as thermal conductivity unattainable through conventional fabrication routes. Additive manufacturing (AM) enables the fabrication of complex fuel geometries that are difficult or impossible to achieve using conventional manufacturing methods. Melting-based AM processes, such as laser powder bed fusion (LPBF), provide high geometric resolution (>200 µm depending on the feature) across a variety of metal alloys, including those suitable for high-temperature fuel cladding applications, such as Nb, W, and Mo. Molybdenum is particularly attractive due to its high thermal conductivity, low thermal expansion, and excellent mechanical stability at elevated temperatures. However, its high melting temperature and brittle nature at low temperatures pose significant challenges during LPBF processing. Rapid solidification inherent to LPBF induces high residual stresses, often leading to post-solidification cracking, which limits the manufacturability of Mo components via this method.

11 NUCLEAR FUEL CYCLE AND FUEL MATERIALS

Layout and Cabling Considerations for a Large Communications Antenna Array

Layout considerations for a large deep space communications antenna array are discussed. A novel fractal geometry for the antenna layout is described that provides optimal packing of antenna elements, efficient cable routing, and logical division of the array into identical sub-arrays.

R T Logan, Jr.

AC and DC Fault Management for Megawatt Electrified Aircraft Electrical Powertrains Task 3: Lifetime and Reliability of Electrical Insulators

This research project was a collaborative investigation between researchers at the RTX Technology Research Center (RTRC) and the University of Texas at Austin and made a significant contribution to enabling electric aircraft. The transport of electric power between the points of generation and use requires power cables. These cables must be smaller, lighter and provide a more predictable life than power cables used in stationary applications. Consequently, this investigation provided heretofore unavailable information supporting the safety and reliability of smaller lighter power cables for electrified aircraft. In addition, the research identified key additional engineering data needed to support quantitative reliability assessments. Important advances included: • Demonstrated that at least one manufacturer can make a novel, smaller, lighter power cable that is free from serious defects. • Developed and published an appropriate analytical construct to describe the life of this novel cable. This is a necessary step for use in aviation where the understanding of remaining life is critical. • Demonstrated thermal-mechanical aging that suggested 1000+ flights before the thermal-mechanical processes produced defects large enough that the defect growth was accelerated electrically. • Showed that electrical aging took place at two rates. The first possibly lasting weeks to months and the second possibly days to weeks. If robust, this provides a good diagnostic for cable replacement. • Demonstrated that the traditional electrical testing of cable materials using manufactured voids can be misleading due to the size of the voids. Emerging laser drilling technology permitted demonstration that the physics of failure in realistically small voids is different from that in the unrealistically large voids used in earlier research, which is very important for high-quality, high-performance, small aircraft cables. Although this project represents a significant contribution to the specifics of cable aging in the aircraft environment, important additional research remains to be completed, including: • Non-uniform thermal cycling by applying the heat from the center conductor to maximize thermal stress next to the core area where the electric gradient is the strongest. This builds on the uniform thermal cycling that has been completed. • The augmentation of the thermal-mechanical failure rate by electrical processes. Better understanding of these time constants strongly affects the ability to predict life. • Termination design: Terminations provide not only electrical reflection potential, but a location for a series arc fault and an area where ozone can diffuse into the center conductor and negatively affect cable insulation. • The abrasion and ozone resistance of the cable jacket. • Pressure cycling as an accelerant of thermal, mechanical, and/or electrical aging. • Possible methods for online PD detection and offline PD localization

model