Search NASA⌕ Search

SEARCH · Search NASA

Results for “electromagnetic transients”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 181 records · Page 10

DQ Admittance Model Extraction for IBRs via Gaussian Pulse Excitation

While $dq$ admittance models have shown to be very useful for stability analysis, extracting admittance models of inverter-based resources (IBRs) from the electromagnetic transient (EMT) simulation environment using frequency scans takes time. In this letter, a new perturbation method based on Gaussian pulses in combination with the system identification algorithms shows great promise for parametric $dq$ admittance model extraction. We present the $dq$ admittance model extracting method for a type-4 wind turbine. Challenges in implementing Gaussian pulse excitation are also pointed out. In conclusion, the extracted $dq$ admittance model via the new method shows to have a high matching degree with the measurements obtained from frequency scans.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Criteria for Grid-Forming Inverters Transitioning Between Current Limiting Mode and Normal Operation

Here, this letter focuses on the fault recovery analysis of inverters using multi-loop droop based grid-forming control, taking into account different current limiting strategies. A criterion is proposed to determine when the inverter can exit the current limiting mode after fault clearance. The theoretical findings are verified through electromagnetic transient simulations using the direct (d)-axis priority-based current limiting method, circular current limiting method, and virtual impedance method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Unified Model of Current-Limiting Grid-Forming Inverters for Large-Signal Analysis

Grid-forming (GFM) inverters can hardly withstand any overloading. As such, GFM inverters need a current limiter in their control system to avoid hardware damage during overloading or grid disturbances. When the current limiter is engaged for inverter protection, however, it dynamically changes the inverter output impedance, which can significantly affect the system behavior against large disturbances. For example, when the current limiter curtails the output power, the primary controller of the GFM inverter-which generates the voltage and angle reference-is prone to losing synchronization with the grid. This can cause large-signal instability in the network. This paper presents a unified GFM current-limiter model to gain a deeper understanding of the impact of the GFM inverter current limiting on large-signal instability and other system behaviors. The unified model captures several well-known current limiters for GFM inverters, and it reveals their large-signal equivalence characterized by the limiter angle. We use the unified model to present in-depth insights into the driving forces that cause large-signal instability in GFM inverter-driven grids. Further, this paper illustrates that the unified model can be used as a tool for assessing the system-level impacts of various GFM current-limiter designs during grid disturbances. Using numerical, analytical, electromagnetic transient models, and a hardware setup, the validity of the unified model is evaluated.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analytical Models of Frequency and Voltage in Large-Scale All-Inverter Power Systems

Low-order frequency response models for power systems have a decades-long history in optimization and control problems such as unit commitment, economic dispatch, and wide-area control. With a few exceptions, these models are built upon the Newtonian mechanics of synchronous generators, assuming that the frequency dynamics across a system are approximately homogeneous, and assume the dynamics of nodal voltages for most operating conditions are negligible, and thus are not directly computed at all buses. As a result, the use of system frequency models results in the systematic underestimation of frequency minimum nadir and maximum RoCoF, and provides no insight into the reactive power-voltage dynamics. This paper proposes a low-order model of both frequency and voltage response in grid-forming inverter-dominated power systems. The proposed model accounts for spatial-temporal variations in frequency and voltage behavior across a system and as a result, demonstrates the heterogeneity of frequency response in future renewable power systems. Electromagnetic transient (EMT) simulations are used to validate the utility, accuracy, and computational efficiency of these models, setting the basis for them to serve as fast, scalable alternatives to EMT simulation, especially when dealing with very large-scale systems, for both planning and operational studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transmission-and-Distribution Dynamic Co-simulation Framework for Distributed Energy Resource Frequency Response

The rapid deployment of distributed energy resources (DERs) in distribution networks has made it challenging to balance the transmission system and stabilize frequency. DERs have the ability to provide frequency regulation services; however, existing frequency dynamic simulation tools - which were developed mainly for the transmission system - lack the capability to simulate distribution network dynamics with high penetrations of DERs. Although electromagnetic transient simulation tools can simulate distribution network dynamics, the computation efficiency limits their use for large-scale transmission-and-distribution (T&D) co-simulation. This paper presents an efficient open-source T&D dynamic co-simulation framework for DER frequency response based on the HELICS platform and off-the-shelf T&D simulators. The challenge of synchronizing the simulation time between the transmission network and the DERs in the distribution network is solved through the detailed modeling of DERs in frequency dynamic models while DER power flow models are also preserved in the distribution networks, thereby respecting local voltage constraints when dispatching DER power for frequency response. DER frequency response (primary and secondary) is simulated in case studies to validate the proposed framework. Last, the accuracy of the proposed co-simulation model is benchmarked, and a large T&D system simulation (2k transmission and 1M distribution nodes) is presented to demonstrate the efficiency and effectiveness of the overall framework.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid Modeling for Stability Analysis

Here this document is a summary of a report prepared by the IEEE PES Task Force (TF) on Microgrid (MG) Dynamic Modeling, IEEE Power and Energy Society, Tech. Rep. PES-TR106, 2023. In this paper, the major issues and challenges in microgrid modeling for stability analysis are discussed, and a review of state-of-the-art modeling approaches and trends is presented. In the context of the IEEE 1547 standard, the document covers issues associated with component models for MG dynamic studies and simulations, including generator and grid modeling, full and average converter models, unbalanced and balanced system conditions, dynamic and static loads, protection requirements, and detailed and simplified controls considering communications delays, packet losses, and security issues. Considering the future integration of grids and MGs to form broad integrated networks, a discussion is presented of the use of phasor vis-à-vis electromagnetic transient simulation tools for MG dynamic stability studies, as well as modeling scale-up issues and MG equivalent models. Specifically white-, grey-, and black-box models, are presented. This TF paper and companion report constitute a modeling guide for R&D groups working on developments and standards of MGs with a focus on stability issues.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Control Design and EMT Simulation Toward the Restoration of Faulted Wind-Dominant Grids

Present power engineers have been challenged to employ electromagnetic transient (EMT) simulations to study the restoration of wind-dominant grids. This paper addresses this hurdle by developing strategies to: (i) reliably control the dc-link voltage of grid-forming wind turbines with dc-coupled batteries, (ii) tune controllers to stably interconnect wind power plants into a grid under recovery, and (iii) autonomously make restoration decisions if transmission faults occur during restoration. These contributions are assessed via EMT simulations of wind-dominant versions of the WSCC 9-bus grid and a 22-bus power system. Furthermore, this paper is significant to address recommendations by the North American Electric Reliability Corporation.

17 WIND ENERGY↗

GIST (Grid Impedance Scan Tool) [SWR-22-73]

NREL has developed GIST (Grid Impedance Scan Tool) to scan the impedance response of inverter-based resources such as land-based and offshore wind power plants, solar power plants, etc., from their electromagnetic transient simulation models to evaluate their impact on grid stability. GIST can scan impedance response of inverter-based resources from vendor-supplied black-box simulation models without requiring internal proprietary details, enabling detailed stability analysis of power systems with high levels of inverter-based generation.

Shah, Shahil↗

pnnl/pecblocks

ConverterBlocks uses the output of detailed electromagnetic transient (EMT) simulations to produce generalized block diagram models of power electronic systems. The process uses deep learning with customized block architectures. The outputs are reduced-order models that meet specified accuracy requirements, while providing important advantages over the original EMT models: ConverterBlock models have fewer nodes and can take longer time steps, resulting in shorter simulation times ConverterBlock models are continuously differentiable, making them compatible with control design methodsGeneralized block diagram modeling of power electronic converters for grid solar and storage applications.

McDermott, Tom↗

pnnl/DPVPROT

Distributed photovoltaics protection software toolkit The code package includes several important functions for design and analysis of new grid protection schemes, for scenarios of distributed photovoltaic (DPV) generation approaching 100% of the peak feeder load, i.e., high-penetration DPV. Convert distribution feeder models, used by planning engineers, to electromagnetic transient (EMT) models that produce waveforms for advanced relay algorithms. Visualize the results of protection scheme operation. Tools to determine distance relay settings on distribution systems. Tools to predict the performance of time-domain, incremental distance relay algorithms

McDermott, Tom↗

EMT data generation

The integration of inverter-based resources (IBRs) in power systems is accelerating, bringing with it significant benefits such as reduced greenhouse gas emissions, improved grid resilience, and increased energy independence. Despite these advantages, the widespread adoption of IBRs introduces several challenges, including issues related to grid stability, increased operational complexity, and the need for updated regulatory frameworks. To address these challenges, IEEE released Standard 2800 in 2022, which sets forth the necessary interconnection capabilities and performance criteria for IBRs connected to transmission and sub-transmission systems. This standard outlines the performance requirements to ensure the reliable integration of IBRs into the bulk power system. Furthermore, in 2023, the North American Electric Reliability Corporation (NERC) published a reliability guideline for electromagnetic transient (EMT) modeling of BPS-connected IBRs. This guideline provides recommendations for developing EMT model requirements, performing model quality checks, and implementing verification practices specifically for EMT models representing BPS-connected inverter-based resources in reliability studies conducted by transmission planners and planning coordinators. These standards and guidelines have a profound impact on EMT studies for transmission networks, influencing system stability analyses, grid recovery and resynchronization processes, fault ride-through evaluations, protection and coordination strategies, advanced control methodologies, and the inclusion of IBRs in transient models of transmission networks. As a result, the generation of EMT data is crucial for conducting various transient-based studies to understand the impact of IBRs. EMT data generation use cases serve as the basis for scenarios in event detection and identification use cases, providing comprehensive details about EMT data generation for transmission grids with inverter-based resources. These use cases supply sufficient training and validation datasets for subsequent EMT analysis algorithms.

Xia, Qianxue↗

Impact of Inverter Based Resource Negative Sequence Current Injection on Transmission System Protection

This report documents the results of analysis performed to investigate the impact of inverter-based resource (IBR) response to unbalanced faults on transmission system protective relay dependability and security. Electromagnetic transient (EMT) simulations were performed to simulate IBR response to these faults using existing manufacturer-developed EMT models for four separate IBRs. The study team was composed of IBR manufacturers, relay manufacturers, transmission providers, reliability coordinators and industry consultants with experience in EMT simulation and system protection. The results indicate that under certain conditions, IBR response can result in protective relay misoperations if current protection practices, which were developed based on conventional power sources, are not adapted to the characteristics of IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Test Bed for Evaluating Frequency Estimation Algorithms in Synthetic Inertia Control: User Manual

As penetration of converter interfaced generators (CIGs) increases, the need for CIG frequency control participation increases. Traditionally, research in this area has been performed using positive sequence simulation software, which provides voltage magnitude and phase measurements, but not point-on-wave (POW) measurements. This means that the effect of frequency estimation algorithms cannot be accurately modeled, especially when the voltage waveform is distorted by faults or load connection events. This report serves as a user manual for an electromagnetic transient simulation testbed, which allows for accurate modeling of frequency estimation and control techniques.

42 ENGINEERING↗

Protection of Distribution Circuits with High Penetration of Solar PV: Distance, Learning, and Estimation-Based Methods

The results of DOE Solar Energy Technologies Office project 34233 are presented. The newest version of IEEE Standard 1547 enables photovoltaic inverters to ride through voltage disturbances, improving bulk system reliability, at the expense of removing undervoltage trip as a fast method of de facto fault detection in high PV adoption scenarios. The project explored new methods of fault detection that don't rely on communication systems and could be available quickly, including distance-based schemes, focused directional relays, and two different data-driven schemes. The schemes were evaluated with fast-phasor simulation, electromagnetic transient simulation, and field data collection at partner utilities Chattanooga Electric Power Board and Dominion Energy Virginia. Accomplishments and possible paths forward are summarized.

14 SOLAR ENERGY↗

Joint Inversion of Surface Electrical Resistivity Tomography and Seismic Refraction Data between the 200 Areas

Geologic stratigraphy on the Hanford Site influences groundwater and contaminant migration through the aquifer system and the vadose zone. The current geologic framework model (GFM) relies heavily on a sparse distribution of borehole data in some locations to map geologic contacts and hydrologic properties in the subsurface. Non-invasive geophysical methods such as electrical resistivity tomography (ERT), transient electromagnetic surveying, and seismic imaging are being used at Hanford to map subsurface structure in areas with limited well observations. This is to develop and mature the capability of geophysical methods to aid in GFM refinement, to identify regions of subsurface complexity, and for optimal well siting. A joint inversion of co-located seismic refraction and ERT data was carried out for data collected on a ~2.3-km profile between the 200 Areas on the Hanford Site. While ERT and seismic refraction images have sensitivity to overlapping physical properties (porosity, moisture content, lithology), the resolution and physics used to acquire each of these datasets are different and therefore information can be different or mutually complementary. Performing a joint inversion provides a reasonable option for a coherent, coupled interpretation for mutually complementary datasets. Between the 200 Areas, there are few boreholes to interpret the geologic framework model, and these data sets were obtained to provide a first line of evidence toward identifying stratigraphic structure. The seismic refraction and ERT data were independently inverted during fiscal year 2022 and broadly showed a two-layer structure with a trough-like feature that is ~1 km wide and upwards of 150 m deep. The depth of the trough feature was greater in the ERT image compared to the seismic image, which indicated a maximum depth of approximately 110 m. The objective of the joint inversion described in this report was to invert the seismic refraction and ERT data together while constraining the ERT image to be structurally similar to the seismic refraction image. The approach was applied using the geophysical inverse modeling program E4D, which has the capability to invert first-arrival times from seismic refraction data and ERT resistances using a “cross-gradient” constraint. The application of cross-gradient constraints with different weights produces ERT models that show a high degree of similarity within the upper 100 m (above ~120 m elevation). None of the ERT models show an improved structural similarity to the seismic result; therefore, it is recommended that further attempts to jointly interpret these models focus on petrophysics and image resolution. Petrophysical measurements of core samples would improve knowledge of what drives the ERT response in this region and, along with downhole geophysical measurements, could be used to “ground truth” the surface-based geophysical results. Image resolution studies would provide insight into which regions of the inverted images are reliable and which regions are poorly constrained.

58 GEOSCIENCES↗

Library of Advanced Models of large-scale PV (LAMP) (Final Technical Report)

A suite of dynamic models of photovoltaic (PV) systems is developed in this project to accurately capture PV system dynamics during different contingencies. The following models are included: (i) quasi-dynamic, (ii) high-fidelity electromagnetic transient (EMT), (iii) advanced, and (iv) baseline. The models have the flexibility to consider different control functionalities at different controller levels. The study’s requirements determine the type of model needed. For example, high-fidelity EMT models are recommended for contingency studies. Advanced models are recommended for online or real-time implementations with resource constraints, whereas quasi-dynamic models are useful for studying the impact of weather variations.

14 SOLAR ENERGY↗

Grid Resiliency with a 100% Renewable Microgrid

San Diego Gas & Electric Company (SDG&E) installed America’s first and largest utility-scale microgrid in Borrego Springs in 2013. The first generation Borrego Springs Microgrid utilized diesel generators to form and stabilize the microgrid island, with support from grid-scale batteries and local solar photovoltaic (PV) generation. In this project, SDG&E in partnership with National Renewable Energy Laboratory (NREL) demonstrated through modeling, simulation and utility field testing that blackstart and islanding of the microgrid can be led with 100% renewable, inverter based resources (IBRs), to help reduce community reliance on conventional generation resources. Through equipment upgrades, grid-forming island leader capability was transitioned to a battery IBR instead of the Borrego Springs Microgrid diesel generators. A new microgrid controller was integrated to the microgrid and programmed to control and manage multiple energy storage systems. Synchrophasor and other power quality data verified autonomous, high-speed response of the IBRs through blackstart, islanding, and load step testing. Results of project field evaluations provide distribution systems operators (DSO) with increased confidence that renewable, IBR can replace traditional generators to blackstart and island microgrids and rapidly establish stable island frequency with rapid changes in peak power demand. Importantly, the project validated the integration feasibility of a distributed energy resource management system (DERMS) controller that manages multiple grid-forming and grid-following IBRs, establishing a standard design interface to reduce the complexity of integrating new DERs in the future and supporting replication by the industry. As a result of learnings in this project, SDG&E has implemented the microgrid controller strategy at multiple other microgrid sites, thereby validating the replicability of the solution. Hardware-in-the-loop (HIL) simulations including power and controller HIL hardware — along with electromagnetic transient (EMT) simulations of Borrego Springs Microgrid —informed adjustments to inverter parameters and were important to characterize the performance of the IBRs in relevant operating conditions before deployment. The EMT and HIL simulations of islanding the entire community are important contributions in providing confidence in IBR performance prior to future islanding of the community in the field. High-fidelity EMT and/or HIL simulation of IBRs can de-risk field operations, and its relevance and importance as a tool is increasing as distribution grids and microgrids become more complex and dynamic with an increasing proportion of renewable generation, distributed energy storage, and two-way power and energy flows.

24 POWER TRANSMISSION AND DISTRIBUTION↗