At least 199 records · Page 11

Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

Threshold virtual impedance (TVI)-based current limiting for grid-forming converters (GFMs) has gained great interest due to its ability to maintain voltage source behaviour during faults. However, sequence component extraction (SCE) and negative-sequence control (NSC) are often overlooked in small-signal stability assessments during faults. This paper develops small-signal sequence impedance models for GFMs under four well-known SCE methods based on TVI current limiting control during symmetrical fault conditions. Using the developed impedance models, the impacts of SCE and NSC, and the voltage and current control loop bandwidths, on system stability during faults are investigated. Additionally, since negative-sequence TVI (TVI-) is typically added along with its positive-sequence counterpart, which is often inductive, inductive and resistive TVI- are examined. The findings suggest that a higher voltage or current control loop bandwidth has a negative impact on system stability, while SCE and NSC largely reduce the stable range for voltage and current control loop bandwidth during faults, and that the severity of such impacts is determined by the particular SCE method. Furthermore, it is observed that inductive TVI- significantly degrades system stability, while resistive TVI- can enhance stability when suitable SCE methods are appropriately selected and designed. Matlab/Simulink electromagnetic transient simulations validate these analytical results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transient Stability-Enhancing Method for Grid-Forming Inverters Under Current Limiting

The primary controller of a grid-forming (GFM) inverter governs the internal reference voltage and angle, which enables the inverter to naturally synchronize and share power with the connected grid; however, during disturbances on the grid caused by, e.g., line faults, overloading, or frequency and phase shifts, a GFM inverter can be pushed into a current-limited operation to protect the device against thermal damage. This can lead to a windup of the internal reference frequency generated by the primary controller and cause a total loss of synchronism with the grid. Here, to make the primary controller of GFM inverters more robust against transient instability, this paper proposes a method that manipulates the reference signals governed by the primary controller by introducing the concept of fictitious power. The fictitious power counteracts the integrator windup in the primary controller, which enables the current-limited inverter to conceive a stable operating point. This method is benchmarked against five state-of-the-art GFM inverter stabilization methods to evaluate its stability-enhancing performance. Full-order electromagnetic-transient simulations and experimental results of a hardware inverter test setup validate the benefits of the method to improve the transient stability of GFM inverters in the face of grid disturbances.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Influence of Control and Limiter Schemes on Sequence-Domain Fault Models of Grid-Forming Inverter-Interfaced Distributed Generators

Unlike synchronous generators, the fault response of grid-forming (GFM) inverter-interfaced distributed generators (IIDGs) is notably governed by the selection of control and current limiting strategies rather than inherent physical traits. While recent research has focused on the sequence domain fault model of GFM IIDGs, a research gap exists in elucidating the influence of control and current limiting schemes on this model's characteristics. This article aims to fill this void by examining how different control and current limiting schemes influence the positive and negative sequence impedances in the phasor-domain fault model of GFM IIDGs. This investigation encompasses droop-based, virtual synchronous machine-based, and virtual oscillator-based reference generation controls alongside rotating and stationary reference-frame-based voltage controls. Furthermore, saturation-based, latching-based, circular and virtual impedance-based current limiting schemes are analyzed. To achieve this goal, a thorough numerical simulation study is conducted. Findings indicate that outer reference generation controls exhibit minimal impact. Conversely, the choice of voltage control and various current limiting schemes emerge as the predominant factors shaping the sequence models of GFM IIDGs. These analyses and results are instrumental in devising reliable protection strategies within inverter-based grids, as a comprehensive understanding of electrical elements in the sequence domain is imperative for effective protective measures.

current limiters↗

Oscillation Risks of Grid-Following and Grid-Forming Inverter-Based Resources in Series-Compensated Networks

Here, this paper investigates the dynamic behavior of a grid-connected inverter-based resource (IBR) when connected radially to a series compensated line. Potential interactions between the series compensation and the IBR have been identified for both types: grid-following (GFL) or grid-forming (GFM). The study begins with electromagnetic transient (EMT) simulations to demonstrate stability issues. Subsequently, nonlinear analytical models are formulated in the dq frame, validated against the EMT simulation, and leveraged to assess eigenvalues and participation factors. Influencing factors of the dominant oscillation modes have been identified. The analysis results show that series compensation may make a mode associated with the synchronization unit unstable. Furthermore, customized feedback systems are built for the synchronizing loop. Series compensation can increase the sensitivity of the voltage phase angle towards the synchronizing angle, and introduce phase lag in the real power response towards the synchronizing angle. These factors may cause interactions with the phase-locked loop in GFL-IBR systems and with power-based synchronization in GFM-IBR systems, potentially leading to instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Unified Model of Current-Limiting Grid-Forming Inverters for Large-Signal Analysis

Grid-forming (GFM) inverters can hardly withstand any overloading. As such, GFM inverters need a current limiter in their control system to avoid hardware damage during overloading or grid disturbances. When the current limiter is engaged for inverter protection, however, it dynamically changes the inverter output impedance, which can significantly affect the system behavior against large disturbances. For example, when the current limiter curtails the output power, the primary controller of the GFM inverter-which generates the voltage and angle reference-is prone to losing synchronization with the grid. This can cause large-signal instability in the network. This paper presents a unified GFM current-limiter model to gain a deeper understanding of the impact of the GFM inverter current limiting on large-signal instability and other system behaviors. The unified model captures several well-known current limiters for GFM inverters, and it reveals their large-signal equivalence characterized by the limiter angle. We use the unified model to present in-depth insights into the driving forces that cause large-signal instability in GFM inverter-driven grids. Further, this paper illustrates that the unified model can be used as a tool for assessing the system-level impacts of various GFM current-limiter designs during grid disturbances. Using numerical, analytical, electromagnetic transient models, and a hardware setup, the validity of the unified model is evaluated.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Design for Switchable Grid-Following and Grid-Forming Control

This paper presents the design of a novel grid- forming (GFM) control structure adapted from a typical grid- following (GFL) control structure with minimal edits, thereby enabling a switchable control structure for voltage sourced converters (VSCs) to operate in either GFL or GFM mode by simply switching a flag manually. The VSC is shown to be able to operate in the GFL control mode synchronizing to the main grid through a phase-locked-loop (PLL) and operate as a GFM controller with power-based synchronization for both grid-connected and islanded conditions. To guarantee smooth operation, the control schemes and the mode switching logic have been carefully designed and examined via a series of experiments. Here, the experiment results show that the switchable control structure can fulfill the desired control and operation functions and enable smooth transition between control modes.

14 SOLAR ENERGY↗

Grid Forming Control Tuning for a Hybrid Inverter-Based Resource Power Plant

A hybrid inverter-based resource (IBR) power plant consists of grid-following (GFL) and grid-forming inverter-based resources (GFM-IBR) connected in parallel. Here, this research focuses on how to design and tune GFM's control parameters to ensure stable operation of the hybrid power plant for weak and strong grid conditions. We consider two design cases: one where the GFL-IBR does not provide frequency support, and one where it does. It is found that the GFM's power-frequency synchronizing system can lose stability when the power-frequency droop constant is large and/or the grid is strong. Additionally, if the GFL has its frequency support enabled, oscillation stability worsens. To explain the mechanism of the interactions, we construct a feedback system for the synchronizing loop, which consists of the GFM's power-frequency droop control that generates the GFM's synchronizing angle, the GFL's phase-locked loop that measures the voltage phase angle, the GFL's frequency-power control that generates its power order, and the rest of the system. The feedback system is effective in illustrating the potential stability risks. Successful design ensures that the hybrid power plant can operate smoothly and ride through grid disturbances.

feedback systems↗

Control and Real-Time Simulation of Microgrids with EV Fast-Charging and Grid-Forming Resources

Fast charging stations (FCSs) for electric vehicles (EVs) can behave as constant power loads, which is problematic for the operation of grid-forming (GFM) inverter-based resources (IBRs). To tackle this problem, this paper proposes a control suite that makes FCSs responsive to ac voltage and frequency disturbances. To test the performance of the FCS controls, the paper also sets forth theory to compensate for time-delays appearing in the real-time simulation of microgrid models divided into several central processing units (CPUs). Furthermore, these contributions are showcased via multi-CPU real-time simulations of a faulted microgrid having EV FCSs and GFM IBRs powered by photovoltaic solar arrays as well as power hardware-in-the-loop experiments. These contributions are significant to address NERC recommendations and IEEE standards.

14 SOLAR ENERGY↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

UNIFI's Grid-Forming (GFM) Inverter Reference Design: A Tutorial on Modeling, Control, and Experimental Implementation of GFM Inverters

The UNIFI Consortium's tutorial on grid-forming (GFM) inverters provides a comprehensive guide to the modeling, control, and experimental implementation of GFM inverters. As the integration of renewable energy accelerates, the transition from traditional grid following (GFL) to GFM inverters is crucial to ensure stable and sustainable power systems. This document outlines a reference design for three-phase and single-phase GFM inverters developed at the University of Texas at Austin. The tutorial also provides step-by-step guidance for accessing and using UNIFI’s GitHub repository, enabling users to design, build, and test GFM inverters efficiently. By fostering collaboration and equipping users with accessible resources, this initiative aims to drive widespread adoption of GFM technology across academia, utilities, and industries.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Reassessment of Dose Contributions from the Paducah Cask Special Waste Form Buried in the E-Area Low-Level Waste Facility

During a recent revision to the groundwater and inadvertent human intruder screening analysis report (Aleman and Hamm, 2023), weaknesses within the screening logic were observed resulting in the addition of U-235 being brought back into the list of radionuclides requiring inventory limits within the Paducah Cask special waste form (SWF). In addition, while reviewing the earlier vadose zone transport analysis efforts, an inconsistency was observed in the initial U-235P inventory that was supplied to the Consolidated Waste Tracking System (CWTS) back in 2009.

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Developments in Processing Criteria for Iron Phosphate Waste Form Design for Treating Electrorefiner Salt Wastes

This report describes work done under a Nuclear Energy University Partnership (NEUP) project that included a collaborative effort between Pacific Northwest National laboratory, University of Nevada Reno, University to Utah, and Missouri University of Science and Technology. In this project, the main goals were the following: (1) to assess H3PO4 dechlorination parameters for halide removal from salt simulants, (2) to evaluate crucible compatibility with iron phosphate glass melts, and (3) to evaluate waste form properties within a ternary system of P2O5 (added as H3PO4), Fe2O3 and fission product simulants.

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Standard Library Plant Controller Model Specification for a Grid-Forming Hybrid Control Inverter-Based Resource (REPCGFM_C1)

This document describes a standard library plant controller model to interface with the grid-forming hybrid control inverter-based resource (IBR) model. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control algorithms to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Standard Library Grid-Forming Hybrid Control Inverter-Based Resource Model Specification (REGFM_C1)

This document describes a standard library grid-forming (GFM) hybrid control inverter-based resource (IBR) model. The GFM hybrid control approach implements both a typical GFM control and a typical grid-following (GFL) control inside one single inverter simultaneously, so that it can take advantage of both methods without comprising the benefits of a typical GFM. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control blocks to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of a Microgrid System with Grid-Forming and Grid-Following Inverters with Diesel Generators: Insights From Hardware Experiments

This paper presents a comprehensive performance evaluation of a microgrid system integrating grid-forming (GFM) inverters, grid-following (GFL) inverters, and a diesel generator, focusing on their interactions and behavior under various dynamic events. The study is conducted using a pure hardware setup comprising two GFM inverters, one GFL inverter, a diesel generator, load banks, a point of common coupling (PCC), and an emulated main grid. The evaluation specifically examines dynamic scenarios, including voltage jumps, phase jumps, rate of change of frequency (ROCOF), synchronization, and islanding operations, which pose critical challenges to system stability. Among all the tests conducted, the overloading and phase jump tests proved to be the most challenging. The capacity of the DC side is crucial for withstanding overloading and grid disturbance tests; otherwise, GFM inverters frequently trip due to DC undervoltage. Throughout all grid disturbance tests, the diesel generator consistently stands out as the most robust and reliable GFM unit in the system. Overall, insights from these hardware experiments shed light on the response characteristics of different generation types during grid disturbances and identify potential stability concerns in such hybrid microgrid systems.

14 SOLAR ENERGY↗

A Large-Scale Hardware Experiment Demonstration of Operating High Inverter-Based Resource Power Systems With Grid-Forming Inverters

This paper presents experimental hardware results from a microgrid system as the penetration level of grid-forming (GFM) inverters increases. The experiment aims to showcase the advantages of GFM inverters in enhancing system stability and to investigate the operational challenges in systems relying entirely on inverter-based resources (IBRs). Five test scenarios are devised to progressively increase GFM inverter penetration levels: 0% (S1), 19% (S2), 37% (S3), 68% (S4), and 100% (S5). To ensure consistency, identical loading conditions and dynamic events are applied across all scenarios. The conducted tests include load step changes, output variation of grid-following (GFL) inverters during islanded mode, transition operations (such as synchronization to the grid and islanding), and rateof- change-of-frequency (ROCOF) and voltage jump tests during grid-connected mode. Key findings from the tests are summarized as follows: (1) Scenario S1 proved most challenging for load steps, and GFL variations because of insufficient GFM capacity, leaving the diesel generator unable to handle transient ridethrough; (2) Scenario S5 was the most difficult for transition operations, because the lack of a diesel generator to maintain stiff bus voltage resulted in unexpected reactive power flows during synchronization, causing the point of common coupling (PCC) breaker to trip; (3) Scenarios S4 and S5 were particularly challenging for ROCOF tests because of minimal system inertia, leading to large transients that triggered breaker trips; and (4) Scenario S4 exhibited the strongest voltage recovery capability because of the presence of the diesel generator and a higher number of GFM inverters, both of which possess the highest capacity for reactive power injection.

24 POWER TRANSMISSION AND DISTRIBUTION↗