Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Interaction Technical Team Roadmap

The mission of the Grid Interaction Technical Team (GITT) is to support a transition scenario to large scale grid-connected vehicle charging with transformational technology, proof of concept and information dissemination. The GITT facilitates technical coordination and collaboration between vehicle-grid connectivity and communication activities among U.S. DRIVE government and industry partners.

EV smart grid↗

Analytical Expression for DC Link Capacitor Current in a Cascaded H-Bridge Multi-Level Active Front-End Converter

Medium-voltage grid-tied systems often use a cascaded H-bridge multi-level active front-end. In this converter, dc link bus capacitors play an important role in stabilizing the converter and enabling both active and reactive power injections. The present work provides analytical expressions for the capacitor current, which are essential for optimizing system design (especially capacitor size vs. lifetime). Then, the expression is incorporated into the grid connected bidirectional power system model. Consequently, this work contributes to the guiding principles to choose accurate dc link capacitor ratings against grid-side power delivery requirements. The analytical results have been validated with detailed simulations and hardware results.

cascaded H-bridge, carrier-based PWM, dc-link capa↗

Power Hardware-in-the-Loop Interfaces for Inverter-Based Microgrid Experiments Including Transitions: Preprint

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop (HIL) simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such microgrid interfaces are particularly challenging to model when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents two PHIL interfaces for such microgrids and the preliminary experimental results: One interface is suitable for those who have access to a power amplifier that can operate as a controllable current source, and the other is for those who need a solution that uses a voltage-mode power amplifier.

battery energy storage system↗

Design of an advanced energy management system for microgrid control using a state machine

A state machine is proposed as the solution for an automated microgrid energy management system (EMS) to improve transient performance during transition operations. It characterizes microgrid operation by seven states that cover all the operating modes: two for steady-state operation (grid-connected and islanded), four for transition operation (preparing for disconnection, transitioning to islanding, preparing for reconnection, and transitioning to grid-connected), and one for emergency operation (black-start operation). A unique dispatch algorithm is developed for each state to achieve the control objective, and the transition function is implemented in the state machine as control logics to transition the system from one state to the next. The feasibility and effectiveness of the developed state machine is validated by simulation in MATLAB with an example microgrid, and the test results show excellent performance of the state machine to achieve the target control objective in each state and to improve the system's transient performance during transition operation.

36 MATERIALS SCIENCE↗

Design of a State Machine for Smooth Microgrid Transition Operation

A state machine is proposed in the energy management system (EMS) of a microgrid as the solution for smooth microgrid's transition operation. This state machine includes six 'states' that cover all the operating modes during the microgrid's transition operation: two basic modes (grid-connected and islanded) and four temporary modes (preparing for disconnection, transition to islanding, preparing for resynchronization, and transition to grid-connected). Temporary modes are designed to fine-tune the control references for the microgrid assets to avoid harmful transients during microgrid transitions, therefore achieving smooth transition operation. The developed state machine is validated by simulation in MATLAB with a sample microgrid, and the test results show excellent performance of the state machine and smooth microgrid transition operation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

EXERGETIC: De-Risking Next-Generation Resilient Geothermal Hybrids via At-Scale Evaluation Using Virtual Emulation Digital Twin Environment for Efficient Operation

The DOE-GTO-funded project, award number 5.1.2.12, entitled "EXERGETIC - De-risking Next Generation Resilient Geothermal Hybrids via at-Scale Evaluation Using a Virtual Emulation Digital Twin Environment for Efficient Operation," advances the solution to these challenges by developing and validating a geothermal co-emulation environment implemented at the National Laboratory of the Rockies (NLR)'s Advanced Research on Integrated Energy Systems (ARIES) platform. This framework enables the de-risking of next-generation geothermal and geothermal hybrid systems through high-fidelity modeling, real-time digital emulation, advanced control strategies, and techno-economic assessment. The project focused on geothermal hybrid configurations that integrate geothermal power plants with concentrated solar power and underground thermal energy storage, enabling enhanced efficiency, flexibility, and grid support capabilities. The main goal of this project was the development of a geothermal digital co-emulation environment to demonstrate the technical and economic value of geothermal hybrid systems and their contribution to grid stability and flexibility. The EXERGETIC framework combined physics-based models, controls, and real assets at ARIES, including digital real-time simulators (DRTS), a 20-MW-scale controllable grid interface (CGI), and a 2-MW conventional generator. Detailed transient models were developed for the key subsystems of a hybrid geothermal plant, including parabolic trough solar collectors, reservoir thermal energy storage (RTES), and a binary Organic Rankine Cycle (ORC) power plant. The ORC model explicitly captured thermal inertia and off-design operation and integrated control strategies to dynamically respond to electric load profiles. The models were validated against published experimental and numerical studies, demonstrating strong agreement and confirming the accuracy and robustness of the modeling approach. The resulting digital twin represents geothermal-solar-storage systems at multiple scales (1 MW to 100 MW) and enables realistic emulation of grid-connected operation. The control architecture allows the geothermal resource to provide stable baseload generation, while solar and stored thermal energy supply flexible, dispatchable support during periods of high demand or variable grid conditions. A key contribution of the EXERGETIC project is the demonstration that geothermal hybrid systems can be designed to be active grid assets rather than passive baseload generators. Using the ARIES platform, the digital twin was evaluated under multiple grid scenarios, including load following, voltage support at the distribution level, and frequency response at the transmission level. Results show that hybrid geothermal systems can respond effectively to dynamic grid conditions, providing inertia-like behavior, primary frequency support, and voltage regulation through coordinated control. In addition to the performance and grid services capability analysis of geothermal and hybrid geothermal systems, the EXERGETIC project also focused on scalability and techno-economic analysis of geothermal hybrid plants. In particular, for the scalability analysis, machine-learning (ML)-based surrogate models were trained using data generated from the geothermal digital twin under different grid-connected scenarios and plant capacities. These ML models demonstrated strong interpolation and extrapolation capabilities across plant sizes, accurately reproducing both steady-state and transient responses with very low errors. Regarding the techno-economic analysis, plant performance results were integrated with cost models for hybrid geothermal systems, and the levelized cost of electricity (LCOE) was used as the main economic metric to evaluate system performance across a range of system capacities, solar shares, solar multiples, and storage durations. Results indicate that economies of scale significantly reduce geothermal LCOE as plant capacity increases, with large-scale systems (25-100 MW) achieving substantially lower costs than small plants. Hybridization with solar thermal energy and storage further improves economic performance by increasing capacity utilization and enabling flexible dispatch. In addition, thermal storage plays a critical role in reducing LCOE by maximizing geothermal, solar, and stored energy resources. In summary, the results from this project demonstrate that geothermal hybrid systems represent a promising alternative for increasing the energy conversion efficiency of geothermal technologies, contributing to the preservation of geothermal resources, and supporting the transition of geothermal plants from traditional baseload resources into flexible, resilient, and cost-competitive energy conversion technologies.

15 GEOTHERMAL ENERGY↗

A Stabilizer based Predictive Control Scheme for Smart Inverters in Weak Grid

This paper presents a self-stabilization mechanism based on finite-set model predictive control (FCS-MPC) framework for smart inverters operating in weak grid conditions. As weak grid’s large parasitic impedance and low short-circuitratio (SCR) challenge the stable operation of grid-connected inverters. Specifically, the inverter may experience frequencies that might excite the LCL filter resonance phenomenon. The inverter stability collapses if this LCL resonance is triggered. To address this issue, a robust predictive controller is proposed that features a self-stabilization mechanism for smart inverters interacting with a weak grid. The proposed methodology utilizes the idea that in stiff grid conditions the grid current feedback (GCF) is stable and in weak grid conditions the inverter current feedback (ICF) is stable. Therefore, the proposed FCS-MPC toggles between GCF and ICF to achieve inherent LCL filter resonance damping. The toggling action between GCF and ICF is leveraged by comparing the moving RMS grid current with threshold current as a constrained in the proposed FCS-MPC cost function. The theoretical analyses are verified by several case studies for a single-phase grid-connected inverter. The analysis and results demonstrated that the proposed FCS-MPC operates well under weak, ultra-weak and stiff grid conditions.

Umar, Muhammad Farooq↗

Controller Requirements for Managing Community Microgrids

Microgrid control systems are central to the functioning of a microgrid. They are responsible for managing distributed energy resources (DER) in both grid-connected and islanded modes of operation. Although microgrids are being developed and deployed by many utilities, several questions are being raised about the control system that manages them. This document provides the detailed list of requirements for a feeder-level microgrid controller to manage various islanded and grid-connected use cases. Functionally, the use cases include control scenarios that require the controller to maintain energy balance, prevent constraint violations, manage switching equipment, manage grid-forming (GFM) and grid-following (GFL) DER, manage critical/non-critical loads, and coordinate with peer systems to operate joined island areas. In addition to detailed requirements, the document includes interface and performance metrics for functional evaluation. These requirements can be applied to utility-managed microgrid controllers that exclusively manage utility-owned equipment; requirements also apply to third-party managed microgrid controllers that coordinate with the utility- and customer-owned equipment. The document can also be used by technology developers and project developers in industry to specify desired control strategies and performance characteristics for community microgrid controllers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Forming Inverter: Laboratory-Scale Hardware Test Bed Setup and Weak Grid Operation

In recent times, the concept of grid forming inverters has gained popularity. Grid forming inverters have proven to be a promising alternative to the grid following inverters. In this paper, we present the hardware test bed implementation of grid forming inverter in islanding mode as well as in grid connected mode. The control structure includes inverter-level inner current control and outer voltage control, and plant-level P - f and Q - V droop control. The Q - V droop provides the voltage command, whereas P - f droop provides the frequency command and is also key for the synchronization process. While it is straightforward to set up the test bed for the islanded operation, it is a challenging process to set up the grid-forming inverter in the grid-connected mode. We present the key technologies and demonstrate the start-up process and weak grid operation using the hardware experiment results. Results from EMT model developed in MATLAB/SimPowerSystems are also presented for side-by-side comparison.

Mittal, Ratik↗

Advanced Distributed Wind Turbine Controls Series: Part 4-Wind Energy in Microgrids – Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL)

In recent years, the technical capabilities and requirements for distributed wind turbines to provide ancillary services beyond maximum energy production has increased. Ancillary services, leveraged through advanced wind turbine controls, can support grid stability, reliability, and resilience. In the context of a microgrid, wind turbines can provide ancillary services that are useful in both islanded and grid-connected modes, as demonstrated in previous parts of this report series. This report focuses on how wind turbines with advanced controls and power electronics can support the stability of the microgrid during transitions from grid-connected to island mode, and back. This report documents simulation results from a model of the National Renewable Energy Laboratory (NREL) Flatirons Campus containing NREL's 600-kilowatt Controls Advanced Research Turbine. Using this turbine, we demonstrate through desktop simulation how a wind turbine can support the voltage and frequency of a microgrid during transitions - from making planned transitions seamless to keeping all loads online during some unplanned transitions to supporting black start in the event of an open transition (blackout).

17 WIND ENERGY↗

Environmental and economic optima of solar home systems design: A combined LCA and LCC approach

Here, we compare the economic and environmental optimal design of Solar Home Systems (SHSs) and explore the role of economic incentives (such as tariffs and technology costs) in approximating the two optima. To achieve that, we present a methodology for the environmental and economic evaluation of grid-connected SHSs: user-scale electric systems involving a photovoltaic (PV) power system and a battery energy storage system. The proposed methodology is based on a mixed integer linear programming (MILP) optimization, life cycle assessment and life cycle costing. This methodological framework is applied to a case study involving a typical SHS installation in Italy. The results of the environmental optimal design brought to the evaluation of a 3.25 kW PV assisted by 8.66 kWh of nickel cobalt manganese batteries, whereas the costs of the SHS are minimized by a small PV system (less than 1 kW). Results underline that the environmental optimal configurations rely on battery technologies, which entails a significant cost compared to the grid connection. In contrast, the economic optimal design solutions is less impactful than the grid mix both from an environmental and economic points of view. Thanks to a reduction of batteries and PV costs, the environmental impact of the economic optimal design is expected to decrease in the future.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Detailed Evaluation of Electric Demand Load Shifting Potential of Heat Pump Water Heaters

Future utilities will emphasize home appliances to reduce greenhouse gas emissions while providing electric load shifting and demand profile management. Heat pump water heaters (HPWH) have demonstrated the ability to cut water heating energy by more than 65% compared with conventional electric resistance waters (ERWH). Laboratory research was conducted on the load shifting potential of grid-connected heat pump water heaters (HPWH), compared to ERWHs. Testing applied different CTA-2045 command designs. Highly-controlled laboratory experiments were conducted on one ERWH and four HPWHs, including a prototype incorporating the new CTA-2045-B protocol feature allowing ‘advanced’ load up above the tank setpoint. The prototype unit with the B-protocol increased tank temperature by 15oF (8.3C) under the advanced load up providing an increase of 1.8 kWh of storage for a 50-gallon (189 liter) tank. The prototype includes a built-in mixing valve to meet anti-scalding codes. With the load-shaping ability of CTA-2045-B, utilities might be able to store excess renewable energy in connected tanks when renewable wind and solar resource production is high. Tests were performed under baseline conditions (no load shift) and under several load-shifting schemes, including load up and advanced load up, ahead of shed commands. Grid-connected HPWHs reduced peak demand by as much as 0.5 kW, depending on tank volume, time of day, control scheme, and draw profile.

heat pump water heater, Demand flexibility, load s↗

Real Power and Reactive Power Control of a Three-Phase Single-Stage-PV System and PV voltage Stability

Grid-connected photovoltaic (PV) systems with power electronic interfaces can provide both real and reactive power to meet power system needs with appropriate control algorithms. This paper presents the control algorithm design for a three-phase single-stage grid-connected PV inverter to achieve either maximum power point tracking (MPPT) or a certain amount of real power injection, as well as the voltage/var control. The switching between MPPT control mode and a certain amount of real power control mode is automatic and seamless. Without the DC-to-DC booster stage, PV DC voltage stability is an important issue in the control design especially when the PV inverter is operating at maximum power point (MPP) with voltage/var control. The PV DC voltage collapse phenomenon and its reason are discussed. The method based on dynamic correction of the PV inverter output is proposed to ensure PV DC voltage stability. Simulation results of the single-stage PV system during system disturbances and fast solar irradiation changes confirm that the proposed control algorithm for single-stage PV inverters can provide appropriate real and reactive power services and ensure PV DC voltage stability during dynamic system operation and atmospheric conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Adaptive Virtual Oscillator Control Structure for Grid-Forming Inverters

The electrical grid is facing unprecedented challenges due to the increasing penetration of inverter-based resources. Grid forming inverters (GFMIs) are a promising technology to address these challenges. Recently, the virtual oscillator based GFMI control is attracting more attention due to its superior performance over other control strategies. In this article, an adaptive control strategy is proposed to provide flexible operation and transition between grid-connected and islanded modes. The controller adapts the virtual oscillator's parameter values depending on the operation mode. It also provides a feedback signal using a measured frequency to account for any steady-state errors and to allow a seamless transition from grid-connected to islanded mode. Finally, to show the feasibility of the proposed controller, this article discusses the simulation results from the implementation of the controller on a single inverter system and on a group of inverters on a large practical utility feeder, the IEEE 13 node feeder, using the DIgSILENT simulation environment.

adaptive control↗

Topology-Agnostic, Scalable, Self-Healing, and Cost-Aware Protection of Microgrids

Most microgrid protection schemes found in published literature suffer from a lack of generality in that they work well for the assumed topology, including type and placement of sources. Other generic protection schemes tend to be too complicated, too expensive, or both. To overcome these draw- backs, a topology-agnostic, scalable, and cost-aware protection based on fundamental principles that work in the presence of high penetration of inverter-based resources (IBRs) is developed and tested in this paper. Here, the protection system also implements stable automatic reconfiguration of the healthy sections of the system after clearance of fault, thus increasing resilience by self- healing. To achieve this ambitious goal, stable inverter models are developed that operate in unbalanced networks in grid-connected and islanded modes, even with 100% IBRs, share power without conflicting controls, and can ride through faults while limiting fault currents. The scheme is tested for primary and backup protection and reconfiguration on the IEEE 123-node feeder in grid-connected and islanded modes with 15 IBRs connected to the system.

42 ENGINEERING↗

Research, Development, and Testing of a Master Controller with Applications to the Bronzeville Community Microgrid System

The objective of this project was to research, develop and test a Microgrid Master Controller (MMC) with applications to the Bronzeville Community Microgrid (BCM), capable of monitoring and controlling a microgrid cluster, as well as to demonstrate its performance in an environment that will closely resemble actual operation of the microgrid. During the project, a hierarchical control strategy of the MMC consisting of primary, secondary, and tertiary layers of control was developed, to operate the MMC in conjunction with the IIT microgrid controller for the coordinated operation of the microgrid cluster, including the control of DERs and facilitation of power flow between the microgrids. A detailed laboratory test plan, including methodology, test setup, test scenarios, and techniques for data gathering and analysis, was developed to verify the MMC functionalities and to validate the performance of the control algorithms under various microgrid operating conditions and potential system contingencies. The MMC underwent a thorough lab testing with more than 320 test cases assigned to 14 performance categories. The final project review and technology feasibility demonstration was held with Department of Energy (DOE) team, in the ComEd’s Grid of the Future lab. During this review, technical performance of the MMC was demonstrated in all key scenarios where the proper performance of the MMC was witnessed under a wide array of scenarios, including planned islanding, unplanned islanding, re-synchronization, load restoration, and basic dispatch in grid-connected and islanded mode. The demonstration was based on use cases focused on main microgrid capabilities and features, which further and the microgrid performance. The following cases were shown to DOE: Planned Islanding; Re-synchronization; Load Restoration; Basic Dispatch (grid-connected mode); Basic Dispatch (islanded mode); Unplanned Islanding. The outcome of this project is a viable microgrid control technology that served as a basis for further enhancement and commercialization of the utility-grade microgrid controller that will be employed for control of the BCM.

24 POWER TRANSMISSION AND DISTRIBUTION↗