Search NASA⌕ Search

SEARCH · Search NASA

Results for “grid forming inverter”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 199 records · Page 11

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Field Verification of Grid-Forming Inverter-Based Power Plant Performance for Transmission System Reliability

This report describes some examples of the operation of two grid-forming (GFM) inverter-based photovoltaic-battery hybrid power plants connected to the electric system of the island of Kauai in Hawaii. Both plants are photovoltaic power plants with battery energy storage and are connected to the networked transmission system operated by Kauai Island Utility Cooperative (KIUC), along with several other power plants including an oil-fired plant, diesel generators, small hydroelectric plants, a biofuel plant, and several other photovoltaic plants.

14 SOLAR ENERGY↗

UPS XML Format and Data

This is the XML data and format for UPS supercomponent including subcomponents: Grid following inverter (GFL), Grid forming inverter (GFM), and dc-dc converter connected to the energy storage and the AI load.

Marthi, Phani Ratna Vanamali [ORNL] (ORCID:0000000↗

Grid-Forming Inverter-Based Resource Research Landscape: Understanding the Key Assets for Renewable-Rich Power Systems

The shift to net zero energy systems has changed the face of our power grid. Traditional large-scale synchronous generators found inside coal and natural gas plants are being replaced with inverter-based resource (IBR) technologies. This transition to an IBR-dominant power grid introduces new characteristics, altering how our grid operates. Therefore, the role of IBRs has expanded, requiring them to provide a range of essential services to keep our grid reliable, resilient, and secure.

energy management↗

Robust Decentralized Secondary Control Scheme for Inverter-based Power Networks

Inverter-dominated microgrids are quickly becoming a key building block of future power systems. They rely on centralized controllers that can provide reliability and resiliency in extreme events. Nonetheless, communication failures due to cyber-physical attacks or natural disasters can make autonomous operation of islanded microgrids challenging. This paper examines a unified decentralized secondary control scheme that is robust to inverter clock synchronization errors and can be seamlessly applied to grid-following or grid-forming control architectures. The proposed scheme overcomes the well-known stability problem that arises from parallel operation of local integral controllers. Theoretical guarantees for stability are provided along with criteria to appropriately tune the secondary control gains to achieve good frequency regulation performance while ensuring fair power sharing. The efficacy of our approach is demonstrated through simulations on a 5-bus microgrid with four grid-forming inverters.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Large-Scale Inverter Integration in Bulk Power Grids Using Heterogeneous Grid-Forming Control Strategies

The conventional generation within the grid is gradually being replaced by inverter based resources. However, the integration of inverters into realistic transmission grid models has not been thoroughly explored. To address this gap, this work develops an automation framework aimed at facilitating the integration of a large number of inverter-based resources into a large-scale grid. Two types of grid-forming controlled inverters—namely droop-controlled inverters and virtual synchronous machine-controlled inverters—are developed for use in positive-sequence simulation packages. Various penetration levels ranging from 23% to 100% of grid-forming inverters are tested in a grid setup in the US Western Interconnection. The dynamic performance of inverters under different control schemes is compared in response to various disturbances.

Lyu, Xue [BATTELLE (PACIFIC NW LAB)]↗

Small-Signal Stability Support from Dynamically Configurable Grid-Forming/Following Inverters for Distribution Systems: Preprint

As the penetration of inverter-based resources (IBRs) continues to increase in modern power systems, system stability is challenged by the insufficient inertia induced by IBRs; hence, there is a need to develop various methods to address the potential instabilities. In this paper, grid-forming (GFM) and grid-following (GFL) controls are implemented for inverters with flexible-mode transitions between them. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small signal stability margin. Further, a holistic and detailed small signal model of the entire system with the dynamics from both synchronous generators (SGs) and IBRs is derived. The effectiveness of the proposed work in adjusting the system small signal stability margin is validated by conducting case studies with varying penetration levels of IBRs. A test system with one SG and five inverters was implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach. Index Terms - grid-following control, grid-forming control, operation mode transition, small-signal stability analysis

grid-following control↗

Grid-Following Inverters and Synchronous Condensers: A Grid-Forming Pair?: Preprint

As power systems across the globe continue to achieve higher instantaneous penetrations of power electronic converterinterfaced renewable sources, the stability of these power systems is challenged because of the removal of synchronous machines, from which stability is traditionally derived. Although technological solutions to these stability challenges are on the horizon, such as the use of grid-forming inverters, they are not yet widely applied to larger power systems, which presents operational challenges for power systems achieving these high instantaneous penetrations today. An interim solution using existing technologies is to pair synchronous condensers with grid-following inverters, which might prolong the stability of an operating power system while synchronous generators are turned off during periods of high renewable energy availability. This work examines the transient stability of such a solution using PSCAD simulations of a two-bus system coupled to a variedlength transmission line, with a synchronous condenser at one bus and a grid-following inverter with grid-support functionality at the other. The system is exposed to load step, balanced fault, and unbalanced fault perturbations. It was found that this simple system returned to a steady state for transmission line lengths up to 125 km after 10% load steps, or a variety of fault types.

14 SOLAR ENERGY↗

Grid-Following Inverters and Synchronous Condensers: A Grid-Forming Pair?

As power systems across the globe continue to achieve higher instantaneous penetrations of power electronic converter-interfaced renewable sources, the stability of these power systems is challenged because of the removal of synchronous machines, from which stability is traditionally derived. Although technological solutions to these stability challenges are on the horizon, such as the use of grid-forming inverters, they are not yet widely applied to larger power systems, which presents operational challenges for power systems achieving these high instantaneous penetrations today. A potential interim solution using existing technologies is to pair synchronous condensers with grid-following inverters, which might prolong the stability of an operating power system while synchronous generators are turned off during periods of high renewable energy availability. This work examines the transient stability of such a solution using PSCAD simulations of a two-bus system coupled to a varied-length transmission line, with a synchronous condenser at one bus and a grid-following inverter with grid-support functionality at the other. The system is exposed to load step, balanced fault, and unbalanced fault perturbations. It was found that this simple system returned to a steady state for transmission line lengths up to 125 km after 10% load steps, or a variety of fault types.

grid-following inverters↗

Enhancing Distribution System Resiliency Using Grid-Forming Fuel Cell Inverter: Preprint

Legacy inverters interfacing distributed energy re-sources are traditionally grid-following (GFL) in nature. GFL assets typically follow real power and reactive power set points. Recently, inverters with grid-forming (GFM) capability are gaining attention as GFM assets can increase the resiliency of the distribution system under stressed conditions. These GFM inverters can use photovoltaics, batteries, or fuel cells as their energy source. In this paper, we present information on inverters interfacing fuel cell assets, specifically with GFM capability. By introducing a fuel cell powered GFM coupled with hydrogen production and storage, the GFM can continuously provide GFM activities during periods of low renewable resource availability, and/or during power outages exceeding typical electric battery duration. Finally, we present information on the need for updates on interconnection and interoperability standards that can be leveraged by utilities for including fuel cell inverters in their asset mix.

fuel cell inverters↗

Small-Signal Stability Support from Dynamically Configurable Grid-Forming/Following Inverters for Distribution Systems

The growth of inverter-based resources (IBRs) in modern power systems can challenge system stability since they do not natively provide inertia, prompting a need to develop new methods to address the potential instabilities. In this paper, a dynamically configurable grid-forming (GFM) and grid-following (GFL) control is proposed, which enables inverters to flexibly transition to support system needs. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small-signal stability margin. In addition, a holistic and detailed small-signal model for a distribution feeder that captures the dynamics from both synchronous generators (SGs) and IBRs is also derived and used to evaluate the effectiveness of the proposed GFM/GFL controls to augment the system small-signal stability margin. Case studies with varying levels of IBRs were implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach.

grid-following control↗

Optimal Control for Fast Frequency Response and Black-Start using Embedded Storages with Grid-Forming Control

The grid-forming inverter is regarded as the solution for integrating high levels of renewable resources into future power systems. Ensuring the stable operation of grids necessitates that grid-forming inverters offer fast frequency response. This report introduces an optimal control method that coordinates the embedded storage within the grid-forming control model with conventional synchronous generators. The optimized active power reference for the embedded storage is generated using receding horizon optimization control, aiming to keep the center of inertia frequency within acceptable limits. The effectiveness of the proposed control is verified through testing in the IEEE 39-bus system. In addition, with grid-forming capability, we will also investigate the application of using mobile embedded storages as black-start units to provide cranking power to energize non-blackstart generators in a black-start process.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Oscillation Risks of Grid-Following and Grid-Forming Inverter-Based Resources in Series-Compensated Networks

Here, this paper investigates the dynamic behavior of a grid-connected inverter-based resource (IBR) when connected radially to a series compensated line. Potential interactions between the series compensation and the IBR have been identified for both types: grid-following (GFL) or grid-forming (GFM). The study begins with electromagnetic transient (EMT) simulations to demonstrate stability issues. Subsequently, nonlinear analytical models are formulated in the dq frame, validated against the EMT simulation, and leveraged to assess eigenvalues and participation factors. Influencing factors of the dominant oscillation modes have been identified. The analysis results show that series compensation may make a mode associated with the synchronization unit unstable. Furthermore, customized feedback systems are built for the synchronizing loop. Series compensation can increase the sensitivity of the voltage phase angle towards the synchronizing angle, and introduce phase lag in the real power response towards the synchronizing angle. These factors may cause interactions with the phase-locked loop in GFL-IBR systems and with power-based synchronization in GFM-IBR systems, potentially leading to instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling and Automation Framework for High IBR Integration in Large-Scale Power Systems

The increasing prevalence of power electronics- interfaced renewable generation sources is leading to a gradual replacement of traditional thermal generation-based synchronous machines. In this context, the modeling of a large-scale power grid that incorporates a significant number of inverter-based resources is crucial for understanding the dynamics and effects of these resources on the power system. This study investigates the positive sequence model of grid-following and grid-forming inverters. Additionally, this work explores the integration of distributed energy resources using population as an indicator of their relative geographic locations. To address challenge to integrate these inverter based resources into a realistic grid of the US Western interconnection, automation scripts are developed to streamline the process of replacing conventional generators with grid-following and grid-forming inverters, as well as allocating distributed energy resources. Different penetration levels of these inverters are considered, and their frequency regulation support following a disturbance is compared through dynamic simulations.

Lyu, Xue↗

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.↗

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation: Preprint

This paper presents the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., lost a large generation unit). The NLM engine is a central dispatch control system that provides high-speed cost-optimal coordination of a set of net loads (combination of generation and deferrable loads) connected to the same electrical network. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm. The experimental results indicate that the NLM engine can achieve the targeted system voltage and frequency and balance load and generation to serve the critical facility.

droop control↗

Grid-Forming Frequency Shaping Control for Low-Inertia Power Systems

As power systems transit to a state of high renewable penetration, little or no presence of synchronous generators makes the prerequisite of well-regulated frequency for grid-following inverters unrealistic. Thus, there is a trend to resort to grid-forming inverters which set frequency directly. We propose a novel grid-forming frequency shaping control that is able to shape the aggregate system frequency dynamics into a first-order one with the desired steady-state frequency deviation and Rate of Change of Frequency (RoCoF) after a sudden power imbalance. The no overshoot property resulting from the first-order dynamics allows the system frequency to monotonically move towards its new steady-state without experiencing frequency Nadir, which largely improves frequency security. We prove that our grid-forming frequency-shaping control renders the system internally stable under mild assumptions. The performance of the proposed control is verified via numerical simulations on a modified Icelandic Power Network test case.

control systems↗

Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗