Geothermal Heat Pump Case Study: Greensburg, Kansas, City Hall

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Greensburg, Kansas, City Hall and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

case study↗

Impact of installation faults in air conditioners and heat pumps in single-family homes on U.S. energy usage

To ensure that new residential air conditioners and heat pumps operate optimally, care must be taken during the initial system design and installation to avoid missteps that immediately degrade a system’s performance. Laboratory and simulation studies have quantified the impact that faults can have on capacity and efficiency. Field studies have demonstrated that installation-related faults are commonplace. However, the national impact of installation-related faults cannot be accurately estimated by only simulating a limited number of homes at several fault levels because of the variety of home characteristics and climates involved. In our analysis, we use an improved residential building stock simulation tool to predict the annual energy increase and additional utility costs resulting from two common installation faults: indoor airflow rate and refrigerant charge level. Our method considers the wide range of building characteristics and climate zones of the U.S. housing stock. We use existing field data to develop fault intensity probability distributions to inform our analysis. The study shows that these two faults result in approximately 20.7 TWh/y of additional energy use for central air conditioners and air-source heat pumps in U.S. single-family detached homes, which is a 9% increase over baseline (no-fault) usage, costing homeowners approximately $2.5 billion annually on utility bills. Air-source heat pumps are responsible for a disproportionate fraction of this energy use increase because of the larger number of operating hours compared to central air conditioners and the sensitivity of heating mode performance to the faults analyzed compared to cooling mode.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A Comprehensive Review of Working Fluids for High-Temperature Heat Pumps: History, Selection, and Evaluation

High-temperature heat pumps (HTHPs) are essential for enhancing energy efficiency across various industrial applications, especially in terms of integrating with renewable energy sources and recovering waste heat. This article thoroughly investigates suitable working fluids for HTHPs, highlighting the evolution from traditional refrigerants to contemporary alternatives with low global warming potential (GWP). It proposes comprehensive selection criteria for these working fluids, pre-selects low-GWP working fluids, and outlines a screening methodology. The pre-selected low-GWP working fluids are evaluated for applications in three typical industrial scenarios involving HTHPs. Furthermore, this study demonstrates that regulatory compliance and environmental impacts significantly influence the development of next-generation refrigerants. The choice of working fluids is closely linked to the types of vapor compression cycles, tailored to the specific industrial applications for HTHPs. This study emphasizes areas for future research, including the development of innovative working fluids; integrated strategies that account for performance, safety, and regulatory standards; alignment of HTHP components; exploration of natural working fluids; and broadening the applications of existing working fluids.

Compression↗

Scoping Study of Integrated Geothermal CO 2 Heat Pump and Water Well System in Cold Climate Region (CRADA Final Report)

This study evaluates the feasibility of using ground-source heat pumps (GSHPs) integrated with water wells for residential heating demands in cold regions of the United States. Four different heat pump systems were evaluated and compared: a CO 2 air-source heat pump (ASHP), a R-410A ASHP, a CO 2 GSHP integrated with well water, and a R-410A GSHP integrated with well water. Simulations were conducted at both equipment and building integration levels, followed by a nationwide analysis across 10 selected cities. Results indicate that integrating GSHP technology with existing water wells (e.g., artesian, bedrock, drilled, and collector wells) is a feasible heating solution because of their high flow rates, good water quality, stable temperatures, and low environmental impact. Although R-410A systems demonstrate higher efficiency, CO 2 systems are more suitable for heating from contamination-free and energy security perspective. The CO 2 GSHPs maintain better performance in colder climates compared with that of ASHPs, providing higher coefficient of performance and environmental benefits because CO 2 refrigerant leakage would not contaminate well water. A national analysis confirms that CO 2 GSHPs outperform furnaces, especially in cold climates, making them a promising solution for residential heating.

15 GEOTHERMAL ENERGY↗

Initial Design and Experimental Results of a Novel Near-Isothermal Compressor for Heat Pump Applications

In efforts to increase the efficiency of residential and commercial air conditioners and heat pumps, it is found that the compressor has the highest electrical energy usage of the system. Therefore, it is appropriate to try to increase the efficiency of this component to reduce its energy usage. Another challenge with heat pump design is that some compressor types have drawbacks that make modulation difficult. To answer these challenges, we are developing an isothermal liquid compressor. The compressor uses propylene glycol to compress carbon dioxide. In the compression chamber the propylene glycol can enter either from the bottom to create a liquid piston for compression or it can enter through a spray nozzle at the top of the chamber. In the latter case, heat transfer from the gas to be compressed to the liquid droplets is high. This allows near isothermal operation of the compressor, which increases the efficiency by 17% to 30%, compared to adiabatic compression. In addition, the isothermal liquid compressor enables very efficient and simple part load modulation.Experimental results demonstrating the operation of the liquid compressor are presented. Initial data demonstrated a temperature rise of 7 K at pressure ratios of almost 4. For comparison at the same initial pressure, temperature, and pressure ratio, adiabatic compression would result in a temperature increase of approximately 70 K. Plotting data on a P-h diagram demonstrates that the compression started at superheated state and ended in supercritical state. Testing was later performed with repeated compressions in the superheated region of the P-h diagram at liquid flow rates of 2 x 10-3 m3/min and 2 x 10-3 m3/min to understand the limitations of the prototype for use with an actual heat pump system. This work demonstrated a novel cycle on a T-s diagram. Results from this work will be used to develop a second-generation prototype where more rapid cycling is possible.

Kowalski, Steve↗

ComStock Measure Scenario Documentation: Laboratory-Informed Modeling of Standard Performance Heat Pump Rooftop Units

This measure scenario replaces gas and electric resistance RTUs in the U.S. commercial building stock with standard efficiency commercial off the shelf heat pump rooftop units. This study uses performance data informed by NREL laboratory testing of a standard efficiency 7.5-ton heat pump RTU. This is the key distinction between this measure scenario and a similar ComStock measure scenario - Standard Performance Heat Pump Rooftop Units - that uses published manufacturer data tables to inform performance. These two scenarios are compared in this report.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Model-based Co-Simulation of Heat Pump Water Heater with Phase Change Materials Thermal Energy Storage

The study analysis the behavior of a new developed heat pump water heater technology which integrates a phase change materials storage with a standard heat pump water heater to maximize the performance parameters of the Unified Energy Factor (UEF) and First Hour Rating (FHR). A model-based control development co-simulation platform is developed to include equipment models, such as heat pump, standard water tank, phase change materials storage tank, and integrate them with control model to support controls design, analysis, verification, and validation. Simulation results are compared with lab test results to validate the accuracy of developed co-simulation platform

Sun, Jian↗

Making Small-Volume Heat Pump Water Heaters Larger: A Design Framework for Integrated Phase Change Material Heat Exchangers

Those that use electricity for water heating, the majority use resistive elements rather than heat pump water heaters (HPWHs), the latter of which use 60-70% less energy than the former. One major barrier to wider HPWH adoption is the added equipment required, which prevents current 50-80-gallon tanks on the market from fitting into smaller utility closets sized for 30-40 gallons, such as those found in manufactured housing. Additionally, these smaller HPWHs tend to underperform relative to their larger counterparts. One solution that addresses both space and performance concerns is thermal energy storage, and in particular, phase change materials (PCMs). PCMs have been studied extensively in building envelope and HVAC systems, but remain a nascent technology in residential water heating. While water itself has a uniquely high energy storage capacity, PCMs have an even higher energy storage density, thus providing the potential to elevate the performance of 40-gallon HPWHs to that of 50-gallon or larger tanks. This research is part of a larger project that seeks to utilize thermal energy storage to enable decarbonized water heating in low-income communities. In this study, we outline the design process used to produce novel PCM heat exchangers for use in small-volume HPWH tanks, including the identification of design constraints and performance targets relevant to real-world applications. In order to ensure optimal PCM utilization and tank storage capacity, we focus here on co-maximizing surface area and PCM volume in the heat exchangers; therefore, this research targets triply periodic minimal surface (TPMS) lattices. TPMS lattices boast enhanced heat transfer capabilities compared to traditional heat exchanger geometries and offer highly tailorable designs; thus, they pair well with the growing field of additive manufacturing, or 3D printing. Starting with a suite of TPMS lattices, we demonstrate a systematic approach for narrowing down feasible designs that comply with identified constraints while meeting PCM performance objectives.

25 ENERGY STORAGE↗

Development and evaluation of a multi-functional heat pump with embedded thermal storage

We developed and tested a novel multi-functional packaged vertical heat pump designed for multi-family buildings, capable of providing space cooling, space heating, water heating, and energy storage integration. The system employs a 3-speed scroll compressor and supports energy-efficient cooling and heating across different ambient conditions, while utilizing both indoor and outdoor air sources for water heating. Key performance metrics include an integrated energy efficiency ratio of 18.0 for cooling, a heating seasonal performance factor of 10.0, and a coefficient of performance (COP) of 2.1 for heating in cold climates down to −15 ˚C. Additionally, the system delivers an annual water heating COP greater than 4.0, with outstanding performance in combined space cooling and water heating modes, achieving a total COP of 8.8 by recovering condenser waste heat. The heat pump also demonstrated thermal energy storage capabilities, integrating with phase change material systems to store heating and cooling energy. Furthermore, this versatile system offers a promising solution for improving energy efficiency and sustainability in multi-family buildings, providing high-performance heating, cooling, and water heating across a range of climates.

COP↗

Geothermal Heat Pump Case Study: The Town at Trilith

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on The Town at Trilith and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

15 GEOTHERMAL ENERGY↗

Geothermal Heat Pump Case Study: Berkeley County School District

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Berkeley County School District and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

15 GEOTHERMAL ENERGY↗

Impact analysis of heating electrification in US buildings with geothermal heat pumps

Few studies have investigated the impacts of large-scale deployment of geothermal heat pumps (GHPs, also called ground source heat pumps) on the electric grid. GHPs utilize the ground as a heat source to warm buildings more efficiently than other space-heating systems. The coupling with the ground offers seasonal thermal storage so that GHPs can also cool buildings in summer more efficiently than other space-cooling systems. This study simulated the performance of GHP systems for various commercial and residential buildings in 15 climate zones in the United States. Combined with the latest End-Use Load Profiles of the US building stock and grid modeling, this study aims to assess the impacts of a national deployment of GHP systems on the US electric grid in terms of energy consumption, emissions, and operational resilience. The preliminary results show that the GHP deployment can save 429 billion kWh of electricity (a 19% reduction from baseline) and reduce carbon emissions by 496 million tons per year (a 31 % reduction from baseline). A geographical view of the results indicates that retrofitting existing HVAC systems with new GHP systems can lead to further reductions in annual electricity consumption and peak electricity demand in the southern regions of the United States than in other parts of the country. On the other hand, GHP retrofits result in higher percentages of site energy savings and carbon emission reduction in the north (cold climates) than in the south (warm climates).

Liu, Xiaobing↗

Modeling and Analysis of a Heat Pump Clothes Dryer with Thermal Energy Storage

Clothes drying is an energy-intensive process that causes significant electricity consumption and carbon emissions in the US. Approximately 83% of Households in the US own a tumble clothes dryer at home and 80% of dryers are electrical resistance dryers with low energy efficiency. Heat pump technology makes it possible for highly efficient and clean drying. Additionally, the ventless design of heat pump clothes dryers (HPCD) provides more installation flexibility. HPCD involves three primary mediums: wet clothes, a closed air loop, and a refrigerant circuit. The evaporator is used to dehumidify the wet air and the condenser is used to re-heat the dry air. One of the critical technological barriers to HPCD market penetration is its long drying time, primarily due to the relatively low discharging temperature and the slow response during the warm-up period. In this study, the thermal energy storage (TES) technology is adopted to address this challenge by providing pre-heating of air prior to the condenser to increase the operating temperature of the process air. The heat pump will charge the phase change material (PCM) in the TES device with heating energy during clothes washing and the PCM will discharge the stored heat to facilitate air heating during clothes drying. To analyze the optimal design and potential for energy saving and drying time reduction, a mathematical model of the HPCD system was developed. The HPCD is a highly dynamic system with a coupled heat and mass transfer and heat pumping cycle. This paper provides solutions to simulate the transient behavior of the system while maintaining low computational cost. The modeling result indicates reduced energy consumption and drying time by integrating TES with HPCD, as compared to electrical resistance dryers. The study can provide significant insights into improving building flexibility with TES and smart appliances.

Liu, Xiaoli↗

Geothermal Heat Pump Case Study: Seattle Public Schools

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Seattle Public Schools and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

geothermal↗

Geothermal Heat Pump Case Study: Montana State University

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Montana State University and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

case study↗

Geothermal Heat Pump Case Study: Norton Commons, Kentucky

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Norton Commons, Kentucky and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

case study↗

Assessments of advanced reactor heat supply to high temperature industrial unit operations: Heat Engines and Heat Pumps

In this report, the feasibility of employing Advanced Nuclear Reactors to supply the necessary high-quality heat to Industrial Processes is investigated. As a first step, the most relevant industrial applications that could benefit from this coupling were identified. Four industries including petroleum refining (distillation, catalyst regeneration, hydro-steam cracking), chemical polymers, steel manufacturing (metals annealing/soaking) and cement manufacturing (calcination of limestone and dolomite industries) were considered. An overview of the heat duties, i.e., the temperatures and thermal powers required by representative plants of the different processes, was provided. Secondly, the thermodynamic conditions of the steam produced by representative designs of Advanced Reactor concepts (Liquid Metal Fast Breeder Reactors, Molten Salt Reactors, and High Temperature Gas-cooled Reactors) were summarized. The comparison between the requirements of the industrial processes and the capabilities of the candidate nuclear power plants showed that only a few processes could benefit from the coupling. Although Advanced Reactors operate at higher temperatures than Light Water Reactors, the thermodynamic conditions of the generated steam flow rates are generally not suitable for the selected applications. At the same time, data indicate that most of the processes can be suitably supplied if the temperature of steam is elevated to 900 °C. One possible solution to boost the quality of the steam from the nuclear island involves the use of a heat pump. Based on a technology similar to that found in refrigerators and air conditioners, heat pumps extract heat from a source, elevate its temperature and transfer it to where it is needed. A simple numerical example illustrating the viability of this method is described. Specifically, the energy conversion cycle of a conventional Pressurized Water Reactor was extended to incorporate a compressor to raise the heating value of the steam produced by the reactor. Two reference configurations, i.e., one where the industrial process coupled to the nuclear power plant exhausts saturated liquid and the other where it exhausts saturated steam, were considered. The thermal efficiencies achievable by increasing the heating value of the reactor steam in this way are significantly greater than by direct electric heating.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Performance evaluation of underground thermal storage integrated dual-source heat pump systems

The increasing demand for electricity stresses the existing electric grids. Buildings consume 73% of all U.S. electricity and are responsible for 30% of U.S. greenhouse gas emissions. Integrating thermal energy storage (TES) in building heating/cooling systems, which consume considerable electricity, can mitigate the challenges to electric grids. Here, this study reports on a novel thermal energy storage device integrated heat pump system to reshape the building electricity demand profile while maintaining thermal comfort. The annual performance of the proposed system has been evaluated through a dynamic system simulation with high fidelity in the Modelica platform. The dynamic model of the novel hybrid component named ‘dual purpose underground thermal battery’ was developed and validated. It was then incorporated into the system model. Given a time-of-use tariff, a rule-based control strategy was designed to shift the electric demand and switch the heat pump source for a typical single-family house in different climate zones of the United States. The system performance of the new TES-integrated dual-source heat pump was compared with that of a conventional air-source heat pump system. The results indicate that the proposed system can reduce the annual HVAC electricity cost by up to 52% while saving 45.2% on electricity consumption. In the Northern areas, the annual peak load of the HVAC system can be reduced by 64.9%. However, this reduction is less in the Southern areas as the system’s higher efficiency in winter dominates the overall energy-saving potential.

25 ENERGY STORAGE↗