Robust Dynamic Watermarking for Cyber-Physical Security of Inverter-Based Resources in Power Distribution Systems
Not provided.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not provided.
Microgrid control systems are central to the functioning of a microgrid. They are responsible for managing distributed energy resources (DER) in both grid-connected and islanded modes of operation. Although microgrids are being developed and deployed by many utilities, several questions are being raised about the control system that manages them. This document provides the detailed list of requirements for a feeder-level microgrid controller to manage various islanded and grid-connected use cases. Functionally, the use cases include control scenarios that require the controller to maintain energy balance, prevent constraint violations, manage switching equipment, manage grid-forming (GFM) and grid-following (GFL) DER, manage critical/non-critical loads, and coordinate with peer systems to operate joined island areas. In addition to detailed requirements, the document includes interface and performance metrics for functional evaluation. These requirements can be applied to utility-managed microgrid controllers that exclusively manage utility-owned equipment; requirements also apply to third-party managed microgrid controllers that coordinate with the utility- and customer-owned equipment. The document can also be used by technology developers and project developers in industry to specify desired control strategies and performance characteristics for community microgrid controllers.
In recent times, the concept of grid forming inverters has gained popularity. Grid forming inverters have proven to be a promising alternative to the grid following inverters. In this paper, we present the hardware test bed implementation of grid forming inverter in islanding mode as well as in grid connected mode. The control structure includes inverter-level inner current control and outer voltage control, and plant-level P - f and Q - V droop control. The Q - V droop provides the voltage command, whereas P - f droop provides the frequency command and is also key for the synchronization process. While it is straightforward to set up the test bed for the islanded operation, it is a challenging process to set up the grid-forming inverter in the grid-connected mode. We present the key technologies and demonstrate the start-up process and weak grid operation using the hardware experiment results. Results from EMT model developed in MATLAB/SimPowerSystems are also presented for side-by-side comparison.
In recent years, the technical capabilities and requirements for distributed wind turbines to provide ancillary services beyond maximum energy production has increased. Ancillary services, leveraged through advanced wind turbine controls, can support grid stability, reliability, and resilience. In the context of a microgrid, wind turbines can provide ancillary services that are useful in both islanded and grid-connected modes, as demonstrated in previous parts of this report series. This report focuses on how wind turbines with advanced controls and power electronics can support the stability of the microgrid during transitions from grid-connected to island mode, and back. This report documents simulation results from a model of the National Renewable Energy Laboratory (NREL) Flatirons Campus containing NREL's 600-kilowatt Controls Advanced Research Turbine. Using this turbine, we demonstrate through desktop simulation how a wind turbine can support the voltage and frequency of a microgrid during transitions - from making planned transitions seamless to keeping all loads online during some unplanned transitions to supporting black start in the event of an open transition (blackout).
Here, we compare the economic and environmental optimal design of Solar Home Systems (SHSs) and explore the role of economic incentives (such as tariffs and technology costs) in approximating the two optima. To achieve that, we present a methodology for the environmental and economic evaluation of grid-connected SHSs: user-scale electric systems involving a photovoltaic (PV) power system and a battery energy storage system. The proposed methodology is based on a mixed integer linear programming (MILP) optimization, life cycle assessment and life cycle costing. This methodological framework is applied to a case study involving a typical SHS installation in Italy. The results of the environmental optimal design brought to the evaluation of a 3.25 kW PV assisted by 8.66 kWh of nickel cobalt manganese batteries, whereas the costs of the SHS are minimized by a small PV system (less than 1 kW). Results underline that the environmental optimal configurations rely on battery technologies, which entails a significant cost compared to the grid connection. In contrast, the economic optimal design solutions is less impactful than the grid mix both from an environmental and economic points of view. Thanks to a reduction of batteries and PV costs, the environmental impact of the economic optimal design is expected to decrease in the future.
Future utilities will emphasize home appliances to reduce greenhouse gas emissions while providing electric load shifting and demand profile management. Heat pump water heaters (HPWH) have demonstrated the ability to cut water heating energy by more than 65% compared with conventional electric resistance waters (ERWH). Laboratory research was conducted on the load shifting potential of grid-connected heat pump water heaters (HPWH), compared to ERWHs. Testing applied different CTA-2045 command designs. Highly-controlled laboratory experiments were conducted on one ERWH and four HPWHs, including a prototype incorporating the new CTA-2045-B protocol feature allowing ‘advanced’ load up above the tank setpoint. The prototype unit with the B-protocol increased tank temperature by 15oF (8.3C) under the advanced load up providing an increase of 1.8 kWh of storage for a 50-gallon (189 liter) tank. The prototype includes a built-in mixing valve to meet anti-scalding codes. With the load-shaping ability of CTA-2045-B, utilities might be able to store excess renewable energy in connected tanks when renewable wind and solar resource production is high. Tests were performed under baseline conditions (no load shift) and under several load-shifting schemes, including load up and advanced load up, ahead of shed commands. Grid-connected HPWHs reduced peak demand by as much as 0.5 kW, depending on tank volume, time of day, control scheme, and draw profile.
Grid-connected photovoltaic (PV) systems with power electronic interfaces can provide both real and reactive power to meet power system needs with appropriate control algorithms. This paper presents the control algorithm design for a three-phase single-stage grid-connected PV inverter to achieve either maximum power point tracking (MPPT) or a certain amount of real power injection, as well as the voltage/var control. The switching between MPPT control mode and a certain amount of real power control mode is automatic and seamless. Without the DC-to-DC booster stage, PV DC voltage stability is an important issue in the control design especially when the PV inverter is operating at maximum power point (MPP) with voltage/var control. The PV DC voltage collapse phenomenon and its reason are discussed. The method based on dynamic correction of the PV inverter output is proposed to ensure PV DC voltage stability. Simulation results of the single-stage PV system during system disturbances and fast solar irradiation changes confirm that the proposed control algorithm for single-stage PV inverters can provide appropriate real and reactive power services and ensure PV DC voltage stability during dynamic system operation and atmospheric conditions.
The electrical grid is facing unprecedented challenges due to the increasing penetration of inverter-based resources. Grid forming inverters (GFMIs) are a promising technology to address these challenges. Recently, the virtual oscillator based GFMI control is attracting more attention due to its superior performance over other control strategies. In this article, an adaptive control strategy is proposed to provide flexible operation and transition between grid-connected and islanded modes. The controller adapts the virtual oscillator's parameter values depending on the operation mode. It also provides a feedback signal using a measured frequency to account for any steady-state errors and to allow a seamless transition from grid-connected to islanded mode. Finally, to show the feasibility of the proposed controller, this article discusses the simulation results from the implementation of the controller on a single inverter system and on a group of inverters on a large practical utility feeder, the IEEE 13 node feeder, using the DIgSILENT simulation environment.
Most microgrid protection schemes found in published literature suffer from a lack of generality in that they work well for the assumed topology, including type and placement of sources. Other generic protection schemes tend to be too complicated, too expensive, or both. To overcome these draw- backs, a topology-agnostic, scalable, and cost-aware protection based on fundamental principles that work in the presence of high penetration of inverter-based resources (IBRs) is developed and tested in this paper. Here, the protection system also implements stable automatic reconfiguration of the healthy sections of the system after clearance of fault, thus increasing resilience by self- healing. To achieve this ambitious goal, stable inverter models are developed that operate in unbalanced networks in grid-connected and islanded modes, even with 100% IBRs, share power without conflicting controls, and can ride through faults while limiting fault currents. The scheme is tested for primary and backup protection and reconfiguration on the IEEE 123-node feeder in grid-connected and islanded modes with 15 IBRs connected to the system.
The objective of this project was to research, develop and test a Microgrid Master Controller (MMC) with applications to the Bronzeville Community Microgrid (BCM), capable of monitoring and controlling a microgrid cluster, as well as to demonstrate its performance in an environment that will closely resemble actual operation of the microgrid. During the project, a hierarchical control strategy of the MMC consisting of primary, secondary, and tertiary layers of control was developed, to operate the MMC in conjunction with the IIT microgrid controller for the coordinated operation of the microgrid cluster, including the control of DERs and facilitation of power flow between the microgrids. A detailed laboratory test plan, including methodology, test setup, test scenarios, and techniques for data gathering and analysis, was developed to verify the MMC functionalities and to validate the performance of the control algorithms under various microgrid operating conditions and potential system contingencies. The MMC underwent a thorough lab testing with more than 320 test cases assigned to 14 performance categories. The final project review and technology feasibility demonstration was held with Department of Energy (DOE) team, in the ComEd’s Grid of the Future lab. During this review, technical performance of the MMC was demonstrated in all key scenarios where the proper performance of the MMC was witnessed under a wide array of scenarios, including planned islanding, unplanned islanding, re-synchronization, load restoration, and basic dispatch in grid-connected and islanded mode. The demonstration was based on use cases focused on main microgrid capabilities and features, which further and the microgrid performance. The following cases were shown to DOE: Planned Islanding; Re-synchronization; Load Restoration; Basic Dispatch (grid-connected mode); Basic Dispatch (islanded mode); Unplanned Islanding. The outcome of this project is a viable microgrid control technology that served as a basis for further enhancement and commercialization of the utility-grade microgrid controller that will be employed for control of the BCM.
2010 marked the emergence of the utility sector photovoltaic market. Utility sector photovoltaic installations quadrupled over 2009 installations. The share of utility sector installations of all U.S. grid-connected PV installations grew from virtually none in 2006 to 15 percent in 2009 and 32 percent in 2010. In addition, 2010 saw installation of a 75 MWAC concentrating solar power plant, the largest installed in the U.S. since 1991. In 2010, annual distributed grid-connected PV installations in the United States grew by 62 percent, to 606 MWDC. Photovoltaic arrays were installed at more than 50,000 sites in 2010, a 45 percent increase over the number of installations in 2009. Solar water heating installations increased by 6 percent in 2010, compared with 2009. Solar water heating has shown only two years of higher growth in the last 10 years. Solar pool heating installations increased by 13 percent in 2010, the largest growth in five years.
The U.S. Department of Energy Solar Decathlon challenges collegiate teams to design, build, and operate solar-powered houses that are cost-effective, energy-efficient, and attractive. The Solar Decathlon 2011 was held in Washington, D.C., from September 23 to October 2, 2011 . A high-penetration microgrid was designed, installed, and operated for the Solar Decathlon 2011 to grid-connect 19 highlyenergy-efficient, solar-powered competition houses to a single utility connection point. The capacity penetration of this microgrid (defined as maximum PV generation divided by maximum system load over a two-week period) was 74% based on 1-minute averaged data. Temporary, ground-laid conductors and electrical distribution equipment were installed to grid-connect the Solar Decathlon village,which included the houses as well as other electrical loads used by the event organizers. While 16 of the houses were connected to the 60 Hz microgrid, three houses from Belgium, China, and New Zealand were supplied with 50 Hz power. The design of the microgrid, including the connection of the houses powered by 50 Hz and a standby diesel generator, is discussed in this paper. In addition to theutility-supplied net energy meters at each house, a microgrid monitoring system was installed to measure and record energy consumption and PV energy production at 1-second intervals at each house. Bidirectional electronic voltage regulators were installed for groups of competition houses, which held the service voltage at each house to acceptable levels. The design and successful performance ofthis high-penetration microgrid is presented from the house, microgrid operator, and utility perspectives.
This paper presents a per-phase controller for a grid-connected Cascaded H-Bridge (CHB) converter featuring negative sequence current regulation and DC bus voltage balancing capabilities. Unlike conventional three-phase controllers, each phase of the CHB can be separately and controlled to regulate the DC voltage and reactive power flow. per-phase negative sequence current control strategy is incorporated into the proposed controller to ensure compliance with IEEE Standard 2800-2022, which requires the absorption of negative-sequence reactive current during grid voltage disturbances. Furthermore, a feed-forward control-based DC bus voltage balancing method is employed, which eliminates the need for the integrator commonly used in traditional approaches. The performance of the proposed controller is validated under various unbalanced grid scenarios and DC bus voltage imbalances through electromagnetic transient (EMT) simulation using a three-phase, three-level grid-connected CHB–Dual Active Bridge (DAB) converter testbed developed on MATLAB/Simulink. Additionally, the performance of the negative-sequence current regulation is investigated through simulation under different unbalanced grid voltage scenarios.
This project is mainly about the operation optimization of three networked microgrids (MG), including centralized optimization and distributed optimization. The alternating direction method of multipliers (ADMM) algorithm is used for distributed optimization. In the distribution network considered here, there is a Distribution Management system (DMS) as the system coordinator and several networked microgrids. In grid-connected mode, power could be imported or exported at the distribution substation bus according to the utility rate, and the exchanged power at point of common coupling (PCC) of any microgrid has a limitation. In islanded mode, the power imports/exports at the distribution substation are zero. In both grid-connected and islanded mode, the distribution substation is taken as a slack bus with fixed voltage magnitude.
Voltage source inverters (VSIs) are power converters that are considered essential in grid connected photovoltaic (PV) generators. There are several types of topologies for these converters. However, from the point of view of high‐quality AC output voltage, multilevel inverters are considered the most adequate. Under this context, this study proposes a new structure for the three‐phase DC−AC conversion stage for a grid‐connected PV system. It consists of two four‐leg two‐level voltage source inverters that are connected to two PV generators. These inverters are associated with two Scott transformers. The secondary windings of the transformer are connected in a way that allows a series connection. Due to this, a multilevel operation will be achieved. The performance of the proposed power conditioning system will be verified through simulation and experimental results.
Installations of grid-connected photovoltaic (PV) systems in the United States have increased dramatically in recent years, growing from less than 20 MW in 2000 to nearly 500 MW at the end of 2007, a compound average annual growth rate of 59%. Of particular note is the increasing contribution of 'non-residential' grid-connected PV systems--defined here as those systems installed on the customer (rather than utility) side of the meter at commercial, institutional, non-profit, or governmental properties--to the overall growth trend. Although there is some uncertainty in the numbers, non-residential PV capacity grew from less than half of aggregate annual capacity installations in 2000-2002 to nearly two-thirds in 2007. This relative growth trend is expected to have continued through 2008. The non-residential sector's commanding lead in terms of installed capacity in recent years primarily reflects two important differences between the non-residential and residential markets: (1) the greater federal 'Tax Benefits'--including the 30% investment tax credit (ITC) and accelerated tax depreciation--provided to commercial (relative to residential) PV systems, at least historically (this relative tax advantage has largely disappeared starting in 2009) and (2) larger non-residential project size. These two attributes have attracted to the market a number of institutional investors (referred to in this report as 'Tax Investors') seeking to invest in PV projects primarily to capture their Tax Benefits. The presence of these Tax Investors, in turn, has fostered a variety of innovative approaches to financing non-residential PV systems. This financial innovation--which is the topic of this report--has helped to overcome some of the largest barriers to the adoption of non-residential PV, and is therefore partly responsible (along with the policy changes that have driven this innovation) for the rapid growth in the market seen in recent years.ii Specifically, due to financial innovation, non-residential entities interested in PV no longer face prohibitively high up-front costs, no longer need to be able to absorb Tax Benefits in order to make the economics pencil out, no longer need to be able to operate and maintain the system, and no longer need to accept the risk that the system does not perform as expected.
Installations of grid-connected photovoltaic (PV) systems in the United States have increased dramatically in recent years, growing from less than 20 MW in 2000 to nearly 500 MW at the end of 2007, a compound average annual growth rate of 59%. Of particular note is the increasing contribution of 'non-residential' grid-connected PV systems--defined here as those systems installed on the customer (rather than utility) side of the meter at commercial, institutional, non-profit, or governmental properties--to the overall growth trend. Although there is some uncertainty in the numbers, non-residential PV capacity grew from less than half of aggregate annual capacity installations in 2000-2002 to nearly two-thirds in 2007. This relative growth trend is expected to have continued through 2008. This article, which is excerpted from a longer report, focuses specifically on just one subset of the non-residential PV market: systems hosted (and perhaps owned) by commercial, tax-paying entities. Tax-exempt entities (e.g., non-profits or municipalities) face unique issues and have different financing options at their disposal; readers interested in PV financing options for tax-exempt entities can find more information in the Bolinger report.
Installations of PV systems have been expanding at a rapid pace in recent years. In the United States, the market for PV is driven by national, state, and local government incentives, including upfront cash rebates, production-based incentives, requirements that electricity suppliers purchase a certain amount of solar energy, and Federal and state tax benefits. These programs are, in part, motivated by the popular appeal of solar energy and by the positive attributes of PV - e.g., modest environmental impacts, avoidance of fuel price risks, coincidence with peak electrical demand, and the location of PV at the point of use. Given the relatively high cost of PV, however, a key goal of these policies is to encourage cost reductions over time. Therefore, as policy incentives have become more significant and as PV deployment has accelerated, so too has the desire to track the installed cost of PV systems over time, by system characteristics, by system location, and by component. A new Lawrence Berkeley National Laboratory report, 'Tracking the Sun: The Installed Cost of Photovoltaics in the U.S. from 1998-2007', helps to fill this need by summarizing trends in the installed cost (i.e., the cost paid by the system owner) of grid-connected PV systems in the U.S. The report is based on an analysis of project-level cost data from nearly 37,000 residential and non-residential PV systems completed from 1998-2007 and installed on the utility-customer-side of the meter. These systems total 363 MW, equal to 76% of all grid-connected PV capacity installed in the U.S. through 2007, representing the most comprehensive data source available on the installed cost of PV in the United States. The data were obtained from administrators of PV incentive programs around the country, who typically collect installed cost data for systems receiving incentives. A total of 16 programs, spanning 12 states, ultimately provided data for the study. Reflecting the broader geographical trends in the U.S. PV market, the vast majority of the systems in the data sample are located in California (83%, by capacity) and New Jersey (12%), The remaining systems are located in Arizona, Connecticut, Illinois, Massachusetts, Maryland, Minnesota, New York, Oregon, Pennsylvania, and Wisconsin. The PV systems in the dataset range in size from 100 W to 1.3 MW, almost 90% of which are smaller than 10 kW. This article briefly summarizes some of the key findings from the Berkeley Lab study (the full report can be downloaded at http://eetd.lbl.gov/ea/emp/re-pubs.html). The article begins by summarizing trends related to the installed cost of PV systems prior to receipt of any financial incentives, and then discusses how changes in incentive levels over time and variation across states have impacted the net installed cost of PV to the customer, after receipt of incentives. Note that all cost and incentive data are presented in real 2007 dollars (2007$), and all capacity and dollars-perwatt ($/W) data are presented in terms of rated module power output under Standard Test Conditions (DC-STC).