Search NASA⌕ Search

SEARCH · Search NASA

Results for “heat pump systems”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 217 records · Page 12

Model-based Design Optimization to Achieve the Performance Goals (16.0 SEER/9.5 HSPF), Developing Heat Pump by Using Low-GWP Refrigerants and 5 mm Diameter Tubes

Usage of low-GWP refrigerants can reduce the Green House Gas (GHG) emission of HVAC systems. Our research in previous milestone report has shown that using heat exchangers with 5 mm diameter tubes instead of 9 mm diameter tubes is a promising solution to meet the performance goals of heat pump using low-GWP refrigerants. In addition, the 5mm tube heat exchangers can lead to lower system refrigerant charge and as a result, reduce environmental impact further. However, shifting to small tube diameters requires in-depth heat exchanger design optimization to adapt to the transition to low-GWP refrigerants. In the 2nd quarter of FY21, we conducted multi-objective optimizations using Particle Swarm Optimization algorithm on a residential 5-ton air source heat pump to investigate the potential system performance improvements and material savings. 4 low-GWP refrigerants, ARM20A, ARM20B, R454A and R454C are investigated in this study. The objectives of the optimization are to minimize the heat pump material cost and to maximize the system performance simultaneously. As a result, the HXs material cost is reduced by up to 77% according to the copper and aluminum material price in current market. Under heating mode operation, the smart 4-way valve guarantees that the optimal low-GWP systems maintain or outperform the heating performance of the R410A baseline system. The model-based design optimization yields 18.3-18.9 SEER and 10.6-11.9 HSPF for optimal systems using different low-GWP refrigerants. The initial performance goals (16.0 SEER/9.5 HSPF) are achieved. Furthermore, up to 50% system refrigerant charge reduction is possible in the optimized low-GWP heat pump system using ARM20B. And 91%-95% predicted life-time direct CO 2 emission reduction is achieved by using the optimal 5mm tube low-GWP heat pumps. The significant material saving, charge reduction and direct CO 2 emission reduction help in reducing the environmental impacts of heat pump systems. The optimal heat exchangers resulting from this research can fit into the original baseline indoor and outdoor fan-coil unit. This can reduce the retrofitting effort by minimizing the change in manufacturing and installation of the heat pumps and guarantee the compatibility with end-users’ house structure. Finally, the new products can be easily accepted by manufacturers and end-users.

42 ENGINEERING↗

Thermal control systems for low-temperature heat rejection on a lunar base

In this report, Rankine-cycle heat pumps and absorption heat pumps (ammonia-water and lithium bromide-water) have been analyzed and optimized for a lunar base cooling load of 100 kW. For the Rankine cycle, a search of several commonly used commercial refrigerants provided R11 and R717 as possible working fluids. Hence, the Rankine-cycle analysis has been performed for both R11 and R717. Two different configurations were considered for the system--one in which the heat pump is directly connected to the rejection loop and another in which a heat exchanger connects the heat pump to the rejection loop. For a marginal increase in mass, the decoupling of the rejection loop and the radiator from the heat pump provides greater reliability of the system and better control. Hence, the decoupled system is the configuration of choice. The optimal TCS mass for a 100 kW cooling load at 270 K was 5940 kg at a radiator temperature of 362 K. R11 was the working fluid in the heat pump, and R717 was the transport fluid in the rejection loop. Two TCS's based on an absorption-cycle heat pump were considered, one with an ammonia-water mixture and the other with a lithium bromide-water mixture as the working fluid. A complete cycle analysis was performed for these systems. The system components were approximated as heat exchangers with no internal pressure drop for the mass estimate. This simple approach underpredicts the mass of the systems, but is a good 'optimistic' first approximation to the TCS mass in the absence of reliable component mass data. The mass estimates of the two systems reveal that, in spite of this optimistic estimate, the absorption heat pumps are not competitive with the Rankine-cycle heat pumps. Future work at the systems level will involve similar analyses for the Brayton- and Stirling-cycle heat pumps. The analyses will also consider the operation of the pump under partial-load conditions. On the component level, a capillary evaporator will be designed, built, and tested in order to investigate its suitability in lunar base TCS and microgravity two-phase applications.

Sridhar, K. R.↗

Catalyzing the Mass Adoption of High Efficiency Technologies in the Multifamily Housing Market

ICAST’s objective was to catalyze the adoption of very-high-efficiency (VHE) heat pump HVAC (mini-splits) and water heaters (HPWH) in multifamily (MF), especially affordable housing (MFAH). Nationally, the market penetration of ENERGY STAR-certified ASHPs is estimated at 43%, and for HPWHs it’s 3% (ENERGY STAR, 2022). Note that mini-splits are a much more practical choice for MF units than ducted systems and their adoption is only a portion of the number provided above, but isolating the market penetration data for mini-split systems is difficult. Both the heat pump-based HVAC and water heater systems can be approx. three times more efficient than their conventional counterparts for space and water heating. While awareness and adoption of VHE heat pumps has been growing nationally, and electric heat pump systems have outsold gas furnaces for two years in a row, the MF segment continues to lag behind single-family. MF constitutes almost a third of the housing in the U.S., so scaling up VHE adoption in this segment can assist in achieving critical climate change goals, while preserving housing affordability for the low-to-moderate income (LMI) population (historically, 85% of residents of MF are LMI).

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Smart Monitoring and Diagnostic System (SMDS) for Packaged Air Conditioners and Heat Pumps for Small/Medium Commercial Buildings: Preparation for Commercialization: CRADA 478 [Abstract only]

This project will enable Pacific Northwest National Laboratory (PNNL) and industry partner, mCloud Technologies, to work collaboratively to ready the Smart Monitoring and Diagnostic System (SMDS) for commercial deployment and validate its performance under real-world conditions at field sites. This project will specifically focus on 1) implementing the SMDS algorithms in a scalable cloud-based software architecture, 2) designing new, innovative, complimentary commercial services based on the SMDS, 3) enhancing the SMDS energy and cost impact algorithms to reduce uncertainty in estimates, 4) determining the lower limits on SMDS performance degradation detection, 5) validating algorithm performance and default values of adjustable thresholds with existing data from controlled physical testing and from customer packaged air conditioners and heat pumps (commonly referred to as rooftop units or RTUs), 6) field testing to validate the system on multiple customer buildings in diverse environments, and 7) expanding field deployment to a larger set of mCloud’s customer buildings. Project results by validating, enhancing, and quantifying the performance of the SMDS will position mCloud, and potential future licensees, to implement the SMDS in commercial offerings that encourage and enable use of condition-based and predictive maintenance, leading to significant reductions in energy use and greenhouse gas emissions associated with space conditioning by RTUs. Furthermore, these enhancements will increase the value of the SMDS for users and increase the potential market for its use and impacts.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Influence of Thermal Energy Storage Integration Strategy on System Performance and Refrigerant Charge for Small-Scale R290 Heat Pumps

As small-scale (2.5 – 5 kW) heat pumps across the US increase straining the grid during peak hours, integrated heat pump thermal energy storage (HP-TES) systems can assist by load shifting. However, challenges arise when assembling these systems, as direct refrigerant-phase change material (PCM) heat exchangers (HXs) increase refrigerant charge, and indirect secondary loops degrade HP-TES performance. In this work, direct and indirect HP-TES configurations were sized using commercially available HXs to compare the available load shift time and performance at similar refrigerant charges. For the same indirect 5 kW HP-TES refrigerant charge, directly HP-TES can operate up to 72 and 145 minutes in cooling and heating modes, respectively, using small diameter tubes. Using Modelica, COP increases for direct and indirect HP-TES were 22% and 9%, respectively, given the parasitic losses in the indirect HP-TES. Overall, small-scale direct HP-TES can have comparable refrigerant charges with indirect HP-TES maximizing COP improvements.

25 ENERGY STORAGE↗

Energy demand reduction in the built environment using shallow geothermal integrated energy systems: Part II – Hybrid ground source heat pump for building heating

The research collection aims at finding the various possible opportunities for the effective integration of shallow geothermal energy (SGE) to decrease the energy demand in the built environment and to reduce emission associated with it. The direct utilization of SGE using a ground source heat pump (GSHP) has been reviewed in comprehensive review part I and part II. From the extensive review, we have found that the hybrid GSHP is needed to avoid ground thermal imbalance and peak demand. Hybrid GSHP can adopt various supplemental heat sources and sinks according to the local climatic conditions and the balance of energy demands. The primary focus on the integration of subsystems such as biomass, solar energy (PV, PVT, and collector), phase change material, micro gas turbine, and absorption heat pump with GSHP is presented for heating application. This comprehensive review part III highlights the recent research findings and a potential gap in hybrid GSHP for further research and developments

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Thermal management of instruments on space platforms using a high capacity two-phase heat transport system

A system utilizing a pumped, two-phase single component working fluid for heat exchange and transport services necessary to meet the temperature control requirements of typical orbiting instrument payloads on space platforms is described. The design characteristics of the system is presented, together with a presentation of a laboratory apparatus for demonstration of proof of concept. Results indicate that the pumped two-phase design concept can meet a wide range of thermal performance requirements with the only penalty being the requirement for a small liquid pump.

Ollendorf, S.↗

Heat pump processes induced by laser radiation

A carbon dioxide laser system was constructed for the demonstration of heat pump processes induced by laser radiation. The system consisted of a frequency doubling stage, a gas reaction cell with its vacuum and high purity gas supply system, and provisions to measure the temperature changes by pressure, or alternatively, by density changes. The theoretical considerations for the choice of designs and components are dicussed.

Garbuny, M.↗

A pumped two-phase cooling system for spacecraft

A pumped, two-phase heat-transport system is being developed for possible use for temperature control of scientific instruments on future NASA missions. As compared to a single-phase system, this two-phase system can maintain tighter temperature control with less pumping power. A laboratory model of the system has been built and tested. The measured heat transfer coefficients were approximately the same as in heat pipes, 220 Btu/hr-sq ft-F, as compared to 25 Btu/hr-sq ft-F for single-phase liquid flow. Heat shearing between experiments has been demonstrated wherein vapor generated in the cold plate of an active experiment was condensed in a cold, unheated experiment. System stability has been observed. However, additional development is needed. The use of non-azeotropic mixtures of coolants appears especially promising as a simple way to determine exit quality and thus control the flow rates to prevent dryout.

Ollendorf, S.↗

Solar energy

The book opens with a review of the patterns of energy use and resources in the United States, and an exploration of the potential of solar energy to supply some of this energy in the future. This is followed by background material on solar geometry, solar intensities, flat plate collectors, and economics. Detailed attention is then given to a variety of solar units and systems, including domestic hot water systems, space heating systems, solar-assisted heat pumps, intermediate temperature collectors, space heating/cooling systems, concentrating collectors for high temperatures, storage systems, and solar total energy systems. Finally, rights to solar access are discussed.

Rapp, D.↗

Chemical/Hydrogen Energy Storage Systems

Electrochemical and thermochemical systems are reviewed. Chemical heat pumps, end-use applications and systems studies, and storage systems and materials are also discussed.

Miller, D. S.↗

Analysis of pumped thermal energy storage using particle media integrated with concentrating solar power

Pumped Thermal Energy Storage (PTES) is an electricity storage system that converts electricity into thermal energy which is stored and later transformed back into electricity. Previous work has illustrated that particles have low capital costs and can be operated over a wide range of temperatures. PTES with particle storage achieves higher round-trip efficiency and specific power output than when molten salt thermal energy storage is used. This article explores hybrid systems that combine PTES with Concentrating Solar Power (CSP). Hybrid systems share the majority of components thereby reducing costs compared to two stand-alone devices. In addition, hybrid systems can provide multiple services (such as renewable power generation and electricity storage services). Using particle thermal storage in these hybrid concepts provides freedom in choosing the design conditions, since a wide range of operating temperatures is allowable, therefore making it possible to identify hybrid system designs that have good performance. In this article, two concepts for hybrid PTES-CSP are introduced. Thermodynamic models are developed and these are used to evaluate the performance of two hybrid systems. These models account for turbomachinery efficiency, and approach temperature and pressure loss in heat exchangers, as well as other sources of inefficiency, such as motor-generator losses, and air fan power. The “Solar Top-Up” Concept uses CSP to increase the temperature delivered by the charging heat pump. The discharging system uses a topping gas cycle and a bottoming steam cycle to fully exploit the available energy. Using solar heat to increase the maximum temperature from 750 K to 1100 K increases the round-trip efficiency from 41 % to 62 % and the specific work output from 88 kJ/kg to 301 kJ/kg. The second concept is a “Dual-Mode” device which provides both electricity storage and solar electricity generation with the same set of components. The PTES-mode and CSP-mode performance are optimized at different design values but careful parameter selection leads to good performance of both modes: one design produces PTES round-trip efficiency > 60 %, CSP heat engine efficiency > 40 %, and specific work outputs > 150 kJ/kg (for both cycles), when the particle receiver temperature is > 1200 K and maximum heat pump temperature is 1100 K.

14 SOLAR ENERGY↗

Solar-powered Rankine heat pump for heating and cooling

The design, operation and performance of a familyy of solar heating and cooling systems are discussed. The systems feature a reversible heat pump operating with R-11 as the working fluid and using a motor-driven centrifugal compressor. In the cooling mode, solar energy provides the heat source for a Rankine power loop. The system is operational with heat source temperatures ranging from 155 to 220 F; the estimated coefficient of performance is 0.7. In the heating mode, the vapor-cycle heat pump processes solar energy collected at low temperatures (40 to 80 F). The speed of the compressor can be adjusted so that the heat pump capacity matches the load, allowing a seasonal coefficient of performance of about 8 to be attained.

Rousseau, J.↗

Synergistic heat pumped thermal storage and flexible carbon capture system

A power plant system is disclosed. The power plant system includes a combustor configured, a turbine configured to generate electricity, a heat exchanger and a steam turbine, a carbon capture system configured to remove at least a portion of carbon-based gasses from the flue gas downstream from the heat recovery steam generator, and a thermal storage system including a hot storage unit configured to store thermal energy at a hot temperature, the hot temperature greater than ambient temperature. The power plant is configured to operate in at least a first mode for storing thermal energy in the thermal storage system and a second mode for releasing the stored thermal energy from the thermal storage system and during the second mode, heat stored in the hot storage unit is transferred to the carbon capture system.

Bandhauer, Todd M.↗

Contact Heat Exchanger

Fluid pressure controls contact between heat pipe and heat exchanger. Heat exchanger system in cross section provides contact interface between fluid system and heat pipe with easy assembly/disassembly of heat-pipe/ pumped-liquid system. Originally developed for use in space, new device applicable on Earth where fluid system is linked with heat pipe, where rapid assembly/disassembly required, or where high pressures or corrosive fluids used.

Fleming, M. L.↗

Field Measurement of Central CO2 Heat Pump Water Heater for Multifamily Retrofit

Domestic hot water heating of multifamily buildings accounts for a substantial portion of the energy load of existing buildings. This load is made up of both the energy required to produce hot water and the energy needed to maintain the temperature of the heated water within a building’s distribution piping so that heat can be promptly delivered to building occupants as needed. Properly designed heat pump water heater (HPWH) systems have the ability to improve efficiency in both water heating and temperature control operations. Further, CO2 heat pump technology reflects a shift away from traditional refrigerants and toward refrigerants with low global warming potential (GWP). In this paper’s case study, a design consisting of multiple CO2 heat pump water heaters (commonly used in single-family homes) with a novel “swing tank” was proposed to meet the demand for domestic hot water heating and recirculation loop temperature maintenance. The proposed design was applied to the retrofit of a 60-unit, low-rise, multi-family building located in the Pacific Northwest of the United States. The purpose of this paper is to verify the performance of the system including the proposed “swing tank” in a centralized SHW system using CO2 HPWH. It also provides practical information and lessons learned from the retrofit project. Long-term monitoring data showed that the system had a coefficient of performance (COP) of three or greater and provided an average of 20 gallons of hot water per day per apartment. The results of this work indicate that residential-scale CO2 HPWH equipment and a “swing tank” design can efficiently provide domestic hot water heating and temperature maintenance for mid-sized multifamily buildings.

Banks, Adria↗

Retrofit Energy Analysis and Central Thermal modeling (REACT) v1.0

REACT is a website designed to simplify the analysis and decision-making process for retrofitting existing central plant heating and cooling systems with advanced heat pump technologies. The tool evaluates the technical and economic viability of replacing traditional boilers with various options including water-to-water or air-to-water heat pumps, which can provide efficient and lower-cost heating and cooling. It allows users to compare current central plant configurations with retrofit scenarios, assessing energy consumption, life-cycle costs, and environmental impact. Retrofitting traditional boiler and chiller systems with water-to-water or air-to-water heat pumps can significantly reduce energy consumption and lower lifecycle costs. The REACT provides: User-Friendly Tools: A user friendly web interface for quick, intuitive analysis accessible to non-experts. Advanced Modeling: A Python-powered engine for detailed parametric studies, optimization, and research applications. Comprehensive Analysis: Lifecycle cost evaluation, energy consumption modeling, and environmental impact assessment. Visual Insights: A variety of plots to visualize system performance and design trade-offs. The engine for the website (REACT) bases on several Python libraries, and the website will be hosted on an ETA server.

Kim, Donghun [Lawrence Berkeley National Laborator↗