Search NASA⌕ Search

SEARCH · Search NASA

Results for “Optimal Power Flow”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 235 records · Page 13

Detection and Characterization of Intrusions to Network Parameter Data in Electric Power Systems

Combating cyberattacks is an emerging challenge in maintaining the reliable and economic operation of electric power systems. Possible cyberattacks include intrusions to the parameter data at a control center. In this class of attacks, algorithms at the control center are correctly executed, but the attacker's modification of the associated parameter data yields improper results. This paper proposes an algorithm for detecting and characterizing cyberattacks to network parameter data, with specific application to optimal power flow problems. The proposed algorithm evaluates whether historical operating point data are consistent with the network parameters. Inconsistencies indicating potential cyberattacks are characterized using historical operational data (power injections and voltage phasors) along with network parameter data. Simulated test cases illustrate the proposed algorithm's detection and characterization capabilities.

cybersecurity↗

Multiphase Optimal and Non-Singular Power Flow by Successive Linear Approximations: Preprint

We propose an optimal power flow method for multiphase power systems. The method works for both radial and meshed networks, and is able to accommodate different types of load/source connections such as wye, delta, etc. Moreover, the method generates a sequence of non-singular points in the electrical state space and a corresponding sequence of power injections, which can be used in real-time control settings. Under certain conditions, the sequences attain the local minimum. The method has been tested using several typical networks, including the IEEE 37-bus and 123-bus test feeders.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Hierarchical Management of Distributed Energy Resources Using Chance-Constrained OPF and Extremum Seeking Control: Preprint

Distributed energy resources (DERs) are becoming an important part of distribution systems because of their economic and environmental benefits. Although their inherent intermittency and volatility introduce uncertainties into the system, they have potential to provide controllability to the system under proper coordination. In this paper, we propose a hierarchical control algorithm for distribution systems with DERs so that they have controllability similar to that of a generator bus. The upper level scheduler solves a chance-constrained optimal power flow (OPF) problem to plan the operation of the DERs based on forecasts, and the lower level distributed DER controllers leverage the extremum seeking approach to deliver the planned power at the feeder head. The proposed algorithm is tested on a modified IEEE 13-node feeder, demonstrating its effectiveness.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Hierarchical Management of Distributed Energy Resources Using Chance-Constrained OPF and Extremum Seeking Control

Distributed energy resources (DERs) are becoming an important part of distribution systems, because of their economic and environmental benefits. Although their inherent intermittency and volatility introduce uncertainties into the electric power system, they have the potential to provide controllability to the system under proper coordination. In this paper, we propose a hierarchical control algorithm for distribution systems with DERs so that they have controllability similar to a generator bus. The upper level scheduler solves a chance-constrained optimal power flow (OPF) problem to plan the operation of the DERs based on forecasts, and the lower level distributed DER controllers leverage the extremum seeking approach to deliver the planned power at the feeder head. The proposed algorithm is tested on a modified IEEE 13-node feeder, demonstrating its effectiveness.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A grid-scale study of demand bidding by large industrial users

A demand bidding mechanism for engaging large industrial electricity users in the operation of the power grid is presented. Demand bidding is formulated as an optimization problem based on a modified version of the alternating current optimal power flow problem, and can be interpreted as a tâtonnement process between the grid operator and electricity users. Here, the work provides the first – to the authors’ knowledge – grid-scale case study of demand bidding, using a synthetic grid structure in the footprint of the grid of Texas. Results reveal that the demand bidding lowers overall power generation costs, but economic benefits plateau as the number of participants increases. Transmission line and transformer capacity constraints become the limiting factors, revealing that expanding and fortifying the transmission infrastructure is key to expanding demand-side participation. Demand bidding does not substantially alter the optimal operation of existing bidding entities when the number of bidders increases, thereby supporting existing bidders to stay in the system and encouraging new ones to join.

Chlor-alkali plant↗

Peak Load Management in Distribution Systems Using Legacy Utility Equipment and Distributed Energy Resources: Preprint

The ability to perform peak load management in distribution systems has several benefits for utilities, including reduced demand charges and improved reliability, efficiency, and utilization of the network infrastructure. This paper demonstrates the coordinated operation of an advanced distribution management system (ADMS) and a distributed energy resource management system (DERMS) to achieve peak load management using a realistic laboratory test bed. A commercial ADMS reduces the peak demand by reducing system voltages using a dynamic voltage regulation (DVR) application. A prototype DERMS—based on real-time optimal power flow—controls distributed battery energy storage systems to further reduce the feeder power. Results from the experiments conducted using a model of a real distribution feeder show that the coordinated operation of the ADMS and DERMS is effective in accomplishing peak load management.

61 RADIATION PROTECTION AND DOSIMETRY↗

Spatial-Temporal PV Hosting Capacity Estimation and Evaluation

Evaluating Photovoltaic Hosting Capacity (PVHC) is an essential step in the process of integrating solar energy into power grids, particularly when focusing on the distribution network (DN) as the primary integration target. PVHC needs to be investigated, especially in cases where the grids are unbalanced, and their operational conditions vary spatially and temporally. This motivation prompted us to propose a scalable model tailored to this application. In this paper, we applied linearization to the alternating current optimal power flow (AC-OPF) and solar inverters, transforming the original problem into a mixed-integer linear programming (MILP) problem. Additionally, we accounted for the battery energy storage system (BESS) as a time-coupling factor for calculating PVHC. We then compared the PVHC results between the IEEE-13 bus and SMART-DS San Francisco (SFO) cases and discussed the extent to which BESS can enhance the PVHC of a DN. Furthermore, we designed a web-based graphical visualization for the SFO case, enabling user interaction with raw data and simulation results on a map through a graphical user interface (GUI). In summary, our results and findings provide valuable insights for future three-phase unbalanced AC-OPF PVHC practices and their visualization.

AC-optimal power flow↗

Real-Time Optimization and Control of Next-Generation Distribution Infrastructure

This presentation highlights the key developments of the ARAP-e NODES project, including the innovative real-time optimal power flow (RT-OPF) algorithm for distributed energy resource (DER) management, trip planning for T+D coordination, and extensive validation of the RT-OPF algorithm in NREL ESIF laboratory with 100+ physical hardware devices, controller-hardware-in-the-loop test at Southern California Edison (SCE), and two field demonstrations.

hardware-in-the-loop↗

Feasible region-based heuristics for optimal transmission switching

In this paper, we develop a optimal transmission switching (OTS) heuristic based on DC optimal power flow (OPF) and assess the efficacy of the approach when implemented within AC OPF. Traditional formulations of the OTS problem can result in hundreds or thousands of binary variables for large networks, making the OTS problem challenging to solve on fast timescales even for relatively small networks. Here, we identify which constraints and therefore which variables are constraining the DC OPF feasible region, and rank them based on their impact on the cost function. We develop a heuristic algorithm which iteratively removes these constraints and solves a series of standard DC OPF problems. The heuristic is tested on a variety of PGlib networks and the results show that the algorithm can provide substantial cost decreases without having to solve any mixed integer programs. Additionally, we provide insights about the OTS problem, including identifying scenarios outside congestion where OTS can prove useful. Lastly, the performance of the DC-based heuristic is shown when the line switching decisions are implemented within AC OPF.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Optimal Power Scheduling for a Medium Voltage AC/DC Hybrid Distribution Network

With the great increase of renewable generation as well as the DC loads in the distribution network; DC distribution technology is receiving more attention; since the DC distribution network can improve operating efficiency and power quality by reducing the energy conversion stages. This paper presents a new architecture for the medium voltage AC/DC hybrid distribution network; where the AC and DC subgrids are looped by normally closed AC soft open point (ACSOP) and DC soft open point (DCSOP); respectively. The proposed AC/DC hybrid distribution systems contain renewable generation (i.e., wind power and photovoltaic (PV) generation); energy storage systems (ESSs); soft open points (SOPs); and both AC and DC flexible demands. An energy management strategy for the hybrid system is presented based on the dynamic optimal power flow (DOPF) method. The main objective of the proposed power scheduling strategy is to minimize the operating cost and reduce the curtailment of renewable generation while meeting operational and technical constraints. The proposed approach is verified in five scenarios. The five scenarios are classified as pure AC system; hybrid AC/DC system; hybrid system with interlinking converter; hybrid system with DC flexible demand; and hybrid system with SOPs. Results show that the proposed scheduling method can successfully dispatch the controllable elements; and that the presented architecture for the AC/DC hybrid distribution system is beneficial for reducing operating cost and renewable generation curtailment.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Demand Bidding Model for Multi-Product Industrial Plants

The growing contribution of renewable energy sources has increased volatility and uncertainty in electricity markets, challenging traditional grid operation paradigms. Demand bidding (DB), a market participation model where (large) electricity users communicate their willingness to pay for electricity to the grid operator, was shown in previous work to enhance grid stability and lower generation cost. We present a DB model for multi-product industrial plants, based on an extended optimal power flow problem where the plant dynamics are represented using autoregressive with extra inputs (ARX) models. We compare DB to price-based demand-side management, showing that, under certain assumptions, the two approaches are equivalent, while DB provides more transparency and predictability to the grid operator. A case study based on an industrial air separation unit is discussed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Introducing Uncertainty Components in Locational Marginal Prices for Pricing Wind Power and Load Uncertainties

With substantially increasing penetration levels of wind power, electric power system flexibility is needed to address the variability and uncertainty of wind power output. Thus, it has become an urgent issue to obtain an optimal trade-off between economics and reliability, and to price system uncertainties. This paper proposes a new electricity market-clearing mechanism based on locational marginal prices (LMPs) for pricing uncertain generation and load. The uncertainty contained locational marginal price (U-LMP) is derived from a distributionally robust chance-constrained optimal power flow (DRCC-OPF) model in which only the first-order and second-order moments of the uncertain sources' probability distribution are needed. Compared with traditional LMPs, the proposed U-LMP formulation includes two new uncertainty components: transmission line overload uncertainty price and generation violation uncertainty price. These LMP uncertainty components are the price signals reflecting the system costs as a result of wind generation and demand uncertainty at different locations. Finally, using parametric case studies, the relationship among uncertainty levels, system generation cost, and LMP uncertainty components are established. Case studies performed on the PJM 5-bus and IEEE 118-bus systems verify the proposed U-LMP method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power System Decomposition for Practical Implementation of Bulk-Grid Voltage Control Methods

Power system algorithms such as AC optimal power flow and coordinated volt/var control of the bulk power system are computationally intensive and become difficult to solve in operational time frames. The computational time required to run these algorithms increases exponentially as the size of the power system increases. The solution time for multiple subsystems is less than that for solving the entire system simultaneously, and the local nature of the voltage problem lends itself to such decomposition. This paper describes an algorithm that can be used to perform power system decomposition from the point of view of the voltage control problem. Our approach takes advantage of the dominant localized effect of voltage control and is based on clustering buses according to the electrical distances between them. One of the contributions of the paper is to use multidimensional scaling to compute n-dimensional Euclidean coordinates for each bus based on electrical distance to perform algorithms like K-means clustering. A simple coordinated reactive power control of photovoltaic inverters for voltage regulation is used to demonstrate the effectiveness of the proposed decomposition algorithm and its components. The proposed decomposition method is demonstrated on the IEEE 118-bus system.

multidimensional scaling↗

Bi-Level Volt-VAR Optimization to Coordinate Smart Inverters with Voltage Control Devices

Conservation voltage reduction (CVR) uses voltage control to reduce customer power demand and help improve the operational efficiency of the electric power distribution system. With the advent of advanced distribution management systems (ADMS), the underlying data and control-rich platform can be utilized to enable a centralized Volt-VAR optimization (VVO) scheme that includes smart inverter controls along with legacy voltage control devices such as voltage regulators and capacitor banks to ensure a maximum CVR benefit. The objective of this paper to present a VVO approach that controls system’s legacy voltage control devices and coordinates their operation with smart inverter control. An optimal power flow (OPF) formulation is proposed by developing linear and nonlinear power flow approximations for a three-phase unbalanced electric power distribution system. A bi-level VVO approach is proposed where, Level-1 optimizes the control of legacy devices and smart inverters using a linear approximate three-phase power flow. In Level-2, the control parameters for smart inverters are adjusted to obtain an optimal and feasible solution by solving the approximate nonlinear OPF model. Level-1 is modeled as a Mixed Integer Linear Program (MILP) while Level-2 as a Quadratically Constrained Quadratic Program (QCQP). The proposed approach is validated using IEEE test cases and the results demonstrate the applicability of the framework in achieving the CVR objective.

Jha, Rahul Ranjan↗

ARPA-E Grid Optimization (GO) Competition Challenge 3

Synthetic Input Data and Team Results for the GO Competition Challenge 3 for Events 1 - 4 and the Sandbox, along with problem and format descriptions and code to validate data and solutions, are available here. Data for industry scenarios will not be made public. The Grid Optimization (GO) Competition Challenge 3 focused on the security-constrained optimal power flow (SCOPF) problem. It is part of a continuing effort begun with Challenges 1 and 2, to successfully discover, develop, and test innovative and disruptive software solutions for critical energy challenges and to overcome existing barriers. The broader goal of the of the GO Competition is to accelerate the development of transformational and disruptive methods for solving problems related to the electric power grid and to provide a transparent, fair, and comprehensive evaluation of new solution methods. Challenge 3 used multiperiod dynamic markets, including advisory models for extreme weather events, day-ahead markets, and the real-time markets with an extended look-ahead. In Event 4, whose submission window was August 31-September 4, 2023, 14 teams solved for the objective values of 669 scenarios (39 scenarios required solutions both with and without line switching being allowed). The 591 synthetic scenarios from 9 network models (3.6 GB) are available here. Ten teams were funded to participate and 7 won prizes totaling $2,400,000. The largest prize ($550,000) went to Mississippi State University. An additional $600,000 was awarded in Event 3 (6/15-16/2023). No prizes were awarded in Events 1 (1/25-27/2023) or 2 (4/13-14/2023). For more information on the competition and challenge see the "GO Competition Challenge 3 Information" resource below.

ACOPF↗

Iteration-based Linearized Distribution-level Locational Marginal Price for Three-phase Unbalanced Distribution Systems

Distributed energy resources (DERs) are rocking the utilities’ business landscape. It calls for competitive market environments that incentivize DERs to form maximum operating efficiency. Among proposed pricing schemes, distribution-level locational marginal price (DLMP) is effective in signaling the marginal generation cost differences driven by energy losses and network constraints. It can be derived from a distribution-level optimal power flow (OPF) framework, as it essentially presents the sensitivity of optimized generation cost towards incremental loads. However, due to the high resistance-to-inductance ratio and unbalanced characteristics of distribution networks, computational affordable DLMPs are highly challenged. This article provides a linear-approximated DLMP that can be solved efficiently and generalized to account for reactive power flow, three-phase unbalanced loads and meshed network structure. The successive linear programming technique is introduced to enhance the model accuracy. Case studies on an IEEE 123-Bus system validate its accuracy against a nonlinear benchmark and capability in offering proper incentives.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Assessing the Optimality of LinDist3Flow for Optimal Tap Selection of Step Voltage Regulators in Unbalanced Distribution Networks: Preprint

The adoption of distributed energy resources such as photovoltaics (PVs) has increased dramatically during the previous decade. The increased penetration of PVs into distribution networks (DNs) can cause voltage fluctuations that have to be mitigated. One of the key utility assets employed to this end are step-voltage regulators (SVRs). It is desirable to include tap selection of SVRs in optimal power flow (OPF) routines, a task that turns out to be challenging because the resultant OPF problem is nonconvex with added complexities stemming from accurate SVR modeling. While several convex relaxations based on semi-definite programming (SDP) have been presented in the literature for optimal tap selection, SDP based schemes do not scale well and are challenging to implement in large-scale planning or operational frameworks. This paper deals with the optimal tap selection (OPTS) problem for wye-connected SVRs using linear approximations of power flow equations. Specifically, the LinDist3Flow model is adopted and the effective SVR ratio is assumed to be continuous–enabling the formulation of a problem called LinDist3Flow-OPTS, which amounts to a linear program. The scalability and optimality gap of LinDist3Flow-OPTS are evaluated with respect to existing SDP-based and nonlinear programming techniques for optimal tap selection in three standard feeders, namely, the IEEE 13-bus, 123-bus, and 8500-node DNs. For all DNs considered, LinDist3Flow-OPTS achieves an optimality gap of approximately 1% or less while significantly lowering the computational burden.

linear approximations↗