Hazard and risk analysis framework for nuclear power plant–based integrated energy systems

Employing integrated energy systems (IESs) with nuclear power plants (NPPs) can improve NPP utilization by leveraging dedicated thermal and electric power delivery, but it may also increase operational safety risks. This paper presents a framework to identify and quantify hazards and risks for such IESs. The framework combines accidentology to review past industrial accidents with failure modes and effects analysis (FMEA) to identify potential future incidents. Hydrogen explosion and toxic chemical release hazards are of particular concern. Explosion consequences are quantified using the Bauwens-Dorofeev (Bauwens) and trinitrotoluene equivalent mass (TNT-EM) methods, while chemical release consequences are computed using the Gaussian atmospheric dispersion method. Operational disturbances from direct electrical and thermal integration that may affect NPP safety are modeled using probabilistic risk analysis (PRA). Hazards and risks are then evaluated for regulatory compliance. The framework is applied to IESs comprising pressurized or boiling water reactors supplying three levels of thermal and electrical power to industrial customers. Case studies include high-temperature steam electrolysis hydrogen plants of varying capacities and a synthetic fuel production plant. Sensitivity analysis examines piping component failures in the PRA model as a precursor to cost estimation for thermal extraction line design. Additionally, Fussel-Vessely (FV) and risk increase importance (RII) measures identify risk-informed design improvements for the thermal extraction system. FMEA highlights hazards such as loss of offsite power, prompt loss of electrical load, loss of thermal output, and immediate steam diversion, in addition to hydrogen explosions and toxic chemical releases. Both Bauwens and TNT-EM methods suggest maintaining several hundred meters of separation between the NPP and hydrogen facility to mitigate explosion risks. PRA results show a maximum initiating event frequency increase of 1.15% and an overall risk increase of 0.28%. Importance measure analysis identifies upstream pipe leak isolation components as critical. Evaluating the results against safety regulations, it is concluded that hazards and risks can be managed to comply with regulations through risk-informed thermal and electrical connection designs, component selection, maintenance programs, and safe separation distances between NPPs and integrated industrial facilities.

08 - HYDROGEN↗

Interconnected Risks in Electricity Systems: Understanding Research Challenges, Needs, and Partnerships

The U.S. federal government has a potential role in mitigating the most poorly addressed risks across electricity markets and interdependent systems. Electricity system risks stem from extreme acute shocks (e.g., cyberattacks, extreme weather, and supply chain disruptions) and chronic stressors (e.g., global economic competition, uncertainties surrounding emerging technologies, climate change, and related conflicts). These acute shocks and chronic stressors can result in dire consequences for society, underscoring the need for better information for decision makers in both public and private sectors. Best practices and a shared understanding of risk management and risk quantification must be rapidly developed and disseminated. Informed by a quantitative treatment of risk to electrical infrastructure and interdependent systems, decision makers can more prudently and efficiently prioritize mitigation initiatives to maximize benefits to government, businesses, and the public.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of cyberattacks on safety and stability of connected and automated vehicle platoons under lane changes

Connected and automated vehicles (CAVs) offer a huge potential to improve the operations and safety of transportation systems. However, the use of smart devices and communications in CAVs introduce new risks. CAVs would leverage vehicle to vehicle (V2V) and vehicle to infrastructure (V2I) communication, thus providing additional system access points compared to traditional systems. Automation makes these systems more vulnerable and increases the consequences of cyberattacks. This study utilizes an infrastructure-based communication platform consisting of cooperative adaptive cruise control and lane control advisories developed by the authors to perform cyber risk assessment of CAVs. The study emulates three types of cyberattacks (message falsification, dedicated denial of service, and spoofing attacks) in a representative traffic environment consisting of multiple CAV platoons and lane change events to analyze the safety and stability impacts of the cyberattacks. Simulation experiments using VISSIM reveals that traffic stream and CAV string is unstable under all three types of cyberattacks. The worst case is represented by the message falsification attack. Increases in volatility are observed over a no attack case, with variations increasing by an average of 43%–51% along with an increase of over 3000 crash conflicts. Similarly, lane change crash conflicts are observed to be more severe compared to rear end crash conflicts, showing a higher probability of severe injuries. Further, the case of slight cyberattack on a single CAV also creates significant disruption in the traffic stream. Analysis of variance (ANOVA) reveals the statistical significance of the results. Furthermore, these results pave the way for future design of secure systems from a monitoring perspective.

97 MATHEMATICS AND COMPUTING↗

RAMM-TM for detection of gas leakage from canisters containing spent nuclear fuel

Remote Area Modular Monitoring (RAMM) for canister surface temperature measurement (TM), or RAMM-TM, is a novel remote monitoring device for detection of gas leakage based on surface temperature measurements of canisters containing spent nuclear fuel. Here we describe the development of RAMM-TM, as is the demonstration of its performance in detecting canister gas leakage from a small, simulated chloride-induced stress corrosion crack in experiments using a 1/4.5-scale model cask. Both helium and air gas leakage from a canister were detected within hours after the start of the leakage. The change in surface temperatures at the top and bottom of the canister (ΔTBT) during gas leakage (depressurization) triggered automatic alarms, providing a sound basis for early detection of gas leakage from the canister. This methodology would allow consequence management through the implementation of mitigatory actions to continue effective aging management and to reduce risks to public safety, health, and the environment.

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Trade-off Analysis of Operational Technologies to Advance Cyber Resilience through Automated and Autonomous Response to Threats

The advancement of cyber resilience requires a preliminary stage of characterizing the trade-off space of mitigation options and how these might affect the stability and determinism of an operational technology (OT). This first step will set the stage for the proper cyber-secure and cyber-resilient design and confirm the affects that can be considered and approved by the OT and the security groups. To provide a baseline for this discussion, this paper provides a consideration of the cyberphysical interactions, possible mitigation steps against certain attacks and their corresponding affects that lend to the security design planning and evaluation process. As an integral part of the proposed scheme this work introduces the concept of systemwide fuzzer, i.e., a tool that manipulates the system state in an effort to determine mitigation response sequences that minimize detriments and maximize benefit in accordance with specified operational requirements.

97 MATHEMATICS AND COMPUTING↗

CCE Phase 4: Mitigations and Protections

During the first three phases, the CCE Team identified any instances of unverified trust in the organization’s technologies, processes, and procedures, any or all of which could be used to adversely impact the system. In Phase 4, the primary goal is to remove the possibility of the end effect—that is, to develop means or mechanisms that will ensure an adversary cannot achieve their Objective (identified in Phase 1) via cyber means. Such measures are known as “protections.” In some cases, this may not be possible, or the implementation of protections may not be desirable due to other considerations. In such cases, means and mechanisms should be developed that focus on putting an organization in a better position to identify adversary activities directed against it, increasing the cost of cyber-enabled sabotage for the adversary (including making things more difficult for the adversary and attempting to lower the chances an adversary may succeed), or decreasing the recovery cost of a victim organization. These measures are known as “mitigations.”

99 GENERAL AND MISCELLANEOUS↗

CCE Phase 3: Consequence-based Targeting

While Phase 2 was a data collection effort, Phase 3 is a targeting effort. In Phase 3, organizations systematically identify the necessary steps for adversary success - all from the adversary’s perspective. A key component to this approach is identifying the critical information needs, targets, access, and actions required for the adversary to achieve the desired effect. These Critical Needs are tied to accomplishing the HCE, such as the technical requirements for the payload (Development), or the access required to deliver a payload (Deployment).

99 GENERAL AND MISCELLANEOUS↗

CCE Case Study: Baltavia Substation Power Outage

In this case study, we will examine a fictional event broadly inspired by the real power outages in Ukraine that took place in December 2015 and December 2016 - both the result of cyber-enabled sabotage. The actual events of 2015 and 2016 were well-documented - the adversaries in these attacks gained access to a few power companies’ corporate networks, pivoted to industrial control system (ICS) networks, and created widespread physical effects in the form of power outages.

24 POWER TRANSMISSION AND DISTRIBUTION↗

RADIANCE Cybersecurity Plan: Generic Version

Under its Grid Modernization Initiative, the U.S. Department of Energy (DOE), in collaboration with energy industry stakeholders developed a multi-year research plan to support modernizing the electric grid. One of the foundational projects for accelerating modernization efforts is information and communications technology interoperability. A key element of this project has been the development of a methodology for engaging ecosystems related to grid integration to create roadmaps that advance the ease of integration of related smart technology. This document is the product of activities undertaken in 2017 through 2019. It provides a Cybersecurity Plan describing the technology to be adopted in the project with details as per the GMLC Call document.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Development of the INL Thermal Energy Distribution System (TEDS) in the Modelica Eco-System for Validation and Verification

This report provides an overview on the development of the Thermal Energy Distribution System (TEDS) in the Modelica process model eco-system at Idaho National Laboratory as part of the integrated energy system initiative. Model development has led to the creation of a dynamic process model of the experimental TEDS facility housed within the Engineering Science Laboratory (ESL) at INL. The model was then used during the pre-construction phase of the experimental effort to inform experimental design (insulation requirements, bypass line placement, expected performance of components) and to test innovative control schemes prior to the initial operation. The TEDS model developed in Modelica includes the primary components of the TEDS experimental unit including: a 200kW Chromalox heater, a single-tank packed bed thermal energy storage system filled with 0.125 inch Alumina (Al 2 O 3 ), an ethylene-glycol to Therminol-66 heat exchanger, system piping, six control valves, and all associated temperature, pressure, and mass flow sensors. The model does not include nitrogen fill gas tanks, or associated overfill tanks, as these are not part of standard system control. Two simulation sets were run. The first is a five-hour test that operates as a shakedown test for the facility. This simulation puts the facility through all five potential operating modes and showcases the ability of valving, control sensors, and component controllers to meet the system demands. The second case imposes a typical summer day demand on the system from a region with mixed commercial and residential electrical needs where the generator alone cannot meet peak demand but instead requires the thermal storage unit to act as a peaking unit. Over the course of the fifteen-hour discharge cycle heat losses account for a heat loss of approximately 15°C in outlet temperature. Such heat losses would lead to a decrease in overall system efficiency and may lead to additional design changes for such designs in the future that may include a topping heater. Through commencement of this work, a systems level model of TEDS with associated control systems, sensors, piping diameters, and component capabilities has been created. This model has been utilized in the pre-experimental phase to inform system design, insulation thicknesses, and potential control schemes to operate the system effectively and safely. Once TEDS begins operation, this model will be refined, tuned, and used for validation and verification purposes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Securing Distributed Energy Resource Integration

The penetration of distributed energy resources (DER) is growing at much higher rates than predicted 20 years ago. Far from being used only in residential settings, DER are now installed on distribution and transmission circuits. In this position, they do not have the same properties as traditional generators and are more flexible in many cases. The growing penetration and range of uses for DER motivate the need to reliably and safely integrate them into the grid. Operators must be able to rely on them not only for normal operation, but also during abnormal conditions like black starts or adverse cyber scenarios. To that end, we study the communications, device interfaces, and potential consequences of DER operation under abnormal and adversarial conditions. The weaknesses of communications networks are studied based on the industrial protocols used, and the benefits of security features are examined. The device interfaces are found to be vulnerable to attack based on the requirements in the IEEE-1547 standard for DER interconnection and interoperability, which is expected to be adopted in the next ten years. In addition to exploring the requirements of the standard, we show that these vulnerabilities and others do exist and can be used maliciously in a modern storage system DER. Consequences of these vulnerabilities range from exacerbated grid instability, to simultaneous loss of large portions of DER penetration, to physical damage to inverters or DER themselves and other sensitive equipment. We tie these outcomes to specific attacker actions in an effort to give operators a better threat intelligence view that allows them to prioritize mitigations. Finally, we discuss mitigations that could prevent many of the adversarial scenarios described. Some solutions can be added to existing infrastructure, while others may require longer term planning for grid modernization with consideration for security.

25 ENERGY STORAGE↗

Materials and Fuels Complex Five-Year Mission Strategy (FY21- FY25)

The Idaho National Laboratory (INL), through its designated mission of advancing innovative nuclear energy solutions, is actively engaged in the research, development, demonstration and deployment of advanced nuclear technology, as well as in fostering private-public partnership for technology development. Key to the success of INL’s mission is the Materials and Fuels Complex (MFC), the only complex in the U.S. that hosts a world-class assemblage of facilities, capabilities and instruments for handling, testing, and characterizing radioactive materials. Driven by its mission/vision of “Engineering and Experiments that Drive the World’s Nuclear Energy Future,” MFC is at the center of INL’s – and indeed the Department of Energy’s – advanced nuclear technology development initiatives, providing essential capabilities such as engineering-scale high-assay low-enriched uranium (HALEU) fuel production, reactor demonstration facilities, post-irradiation examination, and transient irradiation testing. Furthermore, MFC provides an ideal environment for test beds that are utilized for research, development and demonstration (RD&D) activities on used fuel treatment, nuclear non-proliferation, forensics, and nuclear power sources used for space exploration missions conducted by the National Aeronautics and Space Administration (NASA).

11 NUCLEAR FUEL CYCLE AND FUEL MATERIALS↗

Materials and Fuels Complex (FY2021-2025 Five-Year Mission Strategy)

The Idaho National Laboratory (INL), through its designated mission of advancing innovative nuclear energy solutions, is actively engaged in the research, development, demonstration and deployment of advanced nuclear technology, as well as in fostering private-public partnership for technology development. Key to the success of INL’s mission is the Materials and Fuels Complex (MFC), the only complex in the U.S. that hosts a world-class assemblage of facilities, capabilities and instruments for handling, testing, and characterizing radioactive materials. Driven by its mission/vision of “Engineering and Experiments that Drive the World’s Nuclear Energy Future,” MFC is at the center of INL’s – and indeed the Department of Energy’s – advanced nuclear technology development initiatives, providing essential capabilities such as engineering-scale high-assay low-enriched uranium (HALEU) fuel production, reactor demonstration facilities, post-irradiation examination, and transient irradiation testing. Furthermore, MFC provides an ideal environment for test beds that are utilized for research, development and demonstration (RD&D) activities on used fuel treatment, nuclear non-proliferation, forensics, and nuclear power sources used for space exploration missions conducted by the National Aeronautics and Space Administration (NASA).

99 GENERAL AND MISCELLANEOUS↗

DOE Fffice of Nuclear Energy cybersecurity research, development and demonstration program plan

This document describes the Cybersecurity Research Development and Demonstration (RD&D) Program, established by the Department of Energy Office of Nuclear Energy (NE) to provide sciencebased methods and technologies necessary for cost-effective, cyber-secure digital instrumentation, control and communication in collaboration with nuclear energy stakeholders. It provides an overview of program goals, objectives, linkages to organizational strategies, management structure, and stakeholder and cross-program interfaces.

97 MATHEMATICS AND COMPUTING↗

Electrification FY2020 Annual Progress Report

The Electric Drive Technologies (EDT) program’s mission is to conduct early-stage research and development on transportation electrification technologies that accelerate the development of cost-effective and compact electric traction drive systems that meet or exceed performance and reliability requirements of internal combustion engine (ICE)-based vehicles, thereby enabling electrification across all light-duty vehicle types.

33 ADVANCED PROPULSION SYSTEMS↗

Cybersecurity Certification Recommendations for Interconnected Grid Edge Devices and Inverter Based Resources

Escalating deployment of PV and grid-edge devices on the distribution grid has increased the sustainability and efficiency of the electric grid. However, the increasing number of distributed energy resources (DERs) deployed creates a heightened cyber-physical interdependency on the distribution grid and thus creates more vectors for cyber-attacks to exploit through information and communication technology (ICT) systems and networks. For example, control signal packets can be modified, intercepted, or corrupted due to vulnerabilities in communication protocols used by microgrid controllers and grid edge devices for power control. Therefore, to mitigate and prevent cyber-attacks on grid edge devices and the inverter-based resources connected to the distribution grid, the U.S. Department of Solar Energy Technologies Office (SETO) awarded funding to the National Renewable Energy Laboratory and Sandia National Laboratory (SNL) to research, develop, and harmonize cybersecurity standards for Photovoltaic (PV) systems and for other kinds of DERs. To help develop a standard for DER cybersecurity, NREL established certification recommendations and test cases, in consensus with the solar industry and UL, for ensuring intrinsic design security for DERs. These recommendations were developed to bolster the cybersecure functionalities such as TLS, MAC, CRL, session resumption/renegotiation, and password, system, and service security management within the DER devices. The proposed test cases verify authentication, authorization, confidentiality, and data integrity for data and communications of DERs that use Transmission Control Protocol/Internet Protocol (TCP/IP). They were also developed to protect DER communications from eavesdropping, replay, man-in-the-middle, denial of service (DoS), spoofing through security certificates, least-privilege violation, and brute-force credentials. This report, which has been validated and reviewed by UL, expands upon those test cases to provide DER cybersecurity certification recommendations which increase DER resiliency and help to mitigate cyber-attacks. UL's collaboration with NREL and approval of this document will accelerate the adoption of a UL standard for DER cybersecurity.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Engineering-In Cybersecurity

Cyber-Informed Engineering is a framework which allows engineers to build resiliency to the impacts of cyber attack into engineered systems starting in the early design phases. This article introduces the framework and provides a description of some of its principles and resources for learning more.