A Year-Round Energy-Efficient Fresh Air Handling System with Two-Stage Heat Pumps and Lake Water Pre-Treatment
Supplying fresh air is important for indoor air quality, but the energy consumption to treat fresh air is significant. The main problems in existing fresh air system include: supplying single-temperature water to treat fresh air and not applying natural energy sufficiently restrict the efficiency improvement of cooling and heat sources; unused air handling devices under most operating conditions throughout the year increase the fan energy consumption. Thus, this study proposes an efficient fresh air system that uses lake water to pre-treat fresh air and two-stage heat pumps for further treatment, and the unused air handling devices in the system are bypassed. A fresh air system in northern China is selected as a case to show the annual energy performance of the proposed system, and a comparative analysis is conducted between the proposed system and a traditional system. The results show that the annual energy-savings of the proposed system compared to the traditional system come from fans, and compressors, which are 56.5%, and 31.1%, respectively, with an entire system energy saving of 32.2%. The proposed system can achieve an annual system coefficient of performance (COP) of 5.5. This study provides potential for further improving the energy efficiency in fresh air treatment.