Search NASA⌕ Search

SEARCH · Search NASA

Results for “distributed PV”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 271 records · Page 15

Data-Enhanced Hierarchical Control to Improve Distribution Voltage with Extremely High PV Penetration

Dynamic, scalable, and interoperable control paradigms are required to enable efficient, secure, reliable, and resilient distribution grid operations with widespread grid integration of renewable energy resources. This paper presents our recent research on developing a novel, holistic, data-enhanced hierarchical control architecture that addresses the formidable challenges faced by emerging distribution grids with increasing penetrations of distributed energy resources. The proposed architecture integrates centralized monitoring and control with distributed grid-edge control and thus effectively deals with multi-spatiotemporal dynamics existing in the grid. Simulation results are provided to demonstrate the effectiveness of the proposed control architecture.

14 SOLAR ENERGY↗

Data Enhanced Hierarchical Control to Improve Distribution Voltage with Extremely High PV Penetration: Preprint

Dynamic, scalable and interoperable control paradigm is required to enable efficient, secure, reliable and resilient distribution grid operations with widespread grid integration of renewable energy resources. This paper presents our recent research work on developing a novel, holistic, data enhanced hierarchical control architecture that addresses the formidable challenges faced by emerging distribution grids with increasing penetrations of distributed energy resources. The proposed architecture integrates centralized monitoring and control together with distributed grid edge control, and thus effectively deals with multi-spatiotemporal dynamics existing in the grid. Simulation results are provided to demonstrate the effectiveness of the proposed control architecture.

14 SOLAR ENERGY↗

Advanced Inverter Functions and Their Impact on Hosting Capacity

This presentation gives a high-level overview of past and current results related to advanced PV inverter functions, such as volt/var control, and how such functions enable higher PV hosting capacity levels in distribution systems.

advanced inverter functions↗

Determining the Impact of Steady-State PV Fault Current Injections on Distribution Protection

This report investigates the fault current contribution from a single large PV system and the impact it has on existing distribution overcurrent protection devices. Assumptions are made about the modeling of the PV system under fault to perform exhaustive steady - state fault analyses throughout distribution feeder models. Each PV interconnection location is tested to determine how the size of the PV system affects the fault current measured by each protection device. This data is then searched for logical conditions that indicate whether a protection device has operated in a manner that will cause more customer outages due to the addition of the PV system. This is referred to as a protection issue , and there are four unique types of issues that have been identified in the study. The PV system size at which any issues occur are recorded to determine the feeder's PV hosting capacity limitations due to interference with protection settings. The analysis is carried out on six feeder models. The report concludes with a discussion of the prevalence and cause of each protection issue caused by PV system fault current.

30 DIRECT ENERGY CONVERSION↗

Integrating High Penetrations of PV into Southern California: Year 2 Project Update; Preprint

Southern California Edison (SCE) is well into a five-year project to install a total of 500 MW of distributed photovoltaic (PV) energy within its utility service territory. Typical installations to date are 1-3 MW peak rooftop PV systems that interconnect to medium-voltage urban distribution circuits or larger (5 MW peak) ground-mounted systems that connect to medium-voltage rural distributioncircuits. Some of the PV system interconnections have resulted in distribution circuits that have a significant amount of PV generation compared to customer load, resulting in high-penetration PV integration scenarios. The National Renewable Energy Laboratory (NREL) and SCE have assembled a team of distribution modeling, resource assessment, and PV inverter technology experts in order toinvestigate a few of the high-penetration PV distribution circuits. Currently, the distribution circuits being studied include an urban circuit with a PV penetration of approximately 46% and a rural circuit with a PV penetration of approximately 60%. In both cases, power flow on the circuit reverses direction, compared to traditional circuit operation, during periods of high PV power productionand low circuit loading. Research efforts during year two of the five-year project were focused on modeling the distribution system level impacts of high-penetration PV integrations, the development and installation of distribution circuit data acquisition equipment appropriate for quantifying the impacts of high-penetration PV integrations, and investigating high-penetration PV impactmitigation strategies. This paper outlines these research efforts and discusses the following activities in more detail: the development of a quasi-static time-series test feeder for evaluating high-penetration PV integration modeling tools; the advanced inverter functions being investigated for deployment in the project's field demonstration and a power hardware-in-loop test of a 500-kW PVinverter implementing a limited set of advanced inverter functions.

14 SOLAR ENERGY↗

Examining System-Wide Impacts of Solar PV Control Systems with a Power Hardware-in-the-Loop Platform

High penetration levels of distributed solar PV power generation can lead to adverse power quality impacts such as excessive voltage rise, voltage flicker, and reactive power values that result in unacceptable voltage levels. Advanced inverter control schemes have been proposed that have the potential to mitigate many power quality concerns. However, closed-loop control may lead to unintended behavior in deployed systems as complex interactions can occur between numerous operating devices. In order to enable the study of the performance of advanced control schemes in a detailed distribution system environment, a Hardware-in-the-Loop (HIL) platform has been developed. In the HIL system, GridLAB-D, a distribution system simulation tool, runs in real-time mode at the Pacific Northwest National Laboratory (PNNL) and supplies power system parameters at a point of common coupling to hardware located at the National Renewable Energy Laboratory (NREL). Hardware inverters interact with grid and PV simulators emulating an operational distribution system and power output from the inverters is measured and sent to PNNL to update the real-time distribution system simulation. The platform is described and initial test cases are presented. The platform is used to study the system-wide impacts and the interactions of controls applied to inverters that are integrated into a simulation of the IEEE 8500-node test feeder, with inverters in either constant power factor control or active volt/VAR control. We demonstrate that this HIL platform is well-suited to the study of advanced inverter controls and their impacts on the power quality of a distribution feeder. Additionally, the results from HIL are used to validate GridLAB-D simulations of advanced inverter controls.

14 SOLAR ENERGY↗

A Fast Scalable Quasi-Static Time Series Analysis Method for PV Impact Studies Using Linear Sensitivity Model

Understanding the impact of distributed photovoltaic (PV) resources on various elements of the distribution feeder is imperative for their cost effective integration. A year-long quasi-static time series (QSTS) simulation at 1-second granularity is often necessary to fully study these impacts. However, the significant computational burden associated with running QSTS simulations is a major challenge to their adoption. In this paper, we propose a fast scalable QSTS simulation algorithm that is based on a linear sensitivity model for estimating voltage-related PV impact metrics of a three-phase unbalanced, nonradial distribution system with various discrete step control elements including tap changing transformers and capacitor banks. Here, the algorithm relies on computing voltage sensitivities while taking into account all the effects of discrete controllable elements in the circuit. Consequently, the proposed sensitivity model can accurately estimate the state of controllers at each time step and the number of control actions throughout the year. For the test case of a real distribution feeder with 2969 buses (5469 nodes), 6 load/PV time series power profiles, and 9 voltage regulating elements including controller delays, the proposed algorithm demonstrates a dramatic time reduction, more than 180 times faster than traditional QSTS techniques.

14 SOLAR ENERGY↗

Field Demonstration of Using Advanced PV Inverter Functionality to Mitigate the Impacts of High-Penetration PV Grid Integration on the Distribution System

This paper describes a field demonstration that was completed to show the ability of currently installed PV inverters to implement advanced PV inverter functionality and that such functionality was effective at reducing the voltage-related PV impacts of high-penetration PV integration. A distribution circuit was instrumented and then tested for a two week period using off-unity power factor operation. Specifically, an inductive power factor of -0.95 was demonstrated. The results show that the PV inverters were capable of such operation and that the use of off-unity power factor operation was highly effective at reducing the voltage-related impacts of the PV systems interconnected to the circuits used in the demonstration. The impacts of using off-unity power factor operation - resulting in additional reactive current flow on the distribution circuit - are also presented and analyzed.

14 SOLAR ENERGY↗

A Probabilistic Data-Driven Method for Photovoltaic Pseudo-Measurement Generation in Distribution Systems

This paper presents a probabilistic data-driven method to model the uncertainty of distributed photovoltaic (PV) generation to enhance the observability of distribution grids with a high penetration of renewable resources. The proposed method employs a kernel density estimation (KDE) technique to develop the conditional probability density function (PDF) of PV outputs given the time of the day, using the measurement data from observed PV systems. Then time series of output power of unmeasured PV generators, located at the same grid, are generated according to the corresponding PDF and used as pseudo-measurements in distribution system state estimation (DSSE). The proposed model has been tested and verified using real PV data and utility networks.

Yuan, Yuxuan↗

PV Inverter Testing for Momentary Cessation and Rate-of-Change-of-Frequency Events: Preprint

To understand the power system stability and develop better electromagnetic transient (EMT) models of field deployed photovoltaic (PV) inverters, it is important to characterize inverters' response to abnormal voltage and frequency scenarios. Because EMT models are not typically available for small distribution-connected PV inverters, and because inerterconnection standards historically did not specify desired ride-through behaviors, we tested two such inverters in the lab to characterize their responses to severe undervoltage events and high rate-of-change-of-frequency (ROCOF) conditions. The inverters tested were pre-IEEE 1547-2018 residential PV inverters widely used in the Hawaiian Electric territory and many other areas. The testing results for undervoltage scenarios showed that the inverter from one vendor exhibited momentary cessation while the inverter from the other vendor did not exhibit momentary cessation behavior or tripping for most of the events below the 120 ms undervoltage trip threshold duration set by IEEE 1547-2003. The testing results for ROCOF scenarios showed that the inverter from one vendor temporarily lost synchronization during ROCOF conditions while the inverter from the other vendor did not lose synchronization or cease generation for any ROCOF conditions. Both the inverters were also tested for EMT-simulated grid events with severe changes in frequency and voltage. The observed responses of the inverters were different from the simulated response of PV inverters represented the best available assumptions from pre-existing information. The results from these experiments can be used to update the inverter models used in bulk power system studies.

IEEE 1547 2018↗

Coordinative Real-time Sub-Transmission Volt-VAr Control for Reactive Power Regulation between Transmission and Distribution Systems

This paper introduces an integrated voltage regulation approach to coordinate the Volt-VAr control between transmission and distribution systems. Distributed photovoltaic (PV) systems are aggregated as a virtual power plant (VPP). At the sub-transmission level, a Coordinated Real-time Sub-Transmission Volt-VAr Control Tool (CReST-VCT) is introduced to coordinate the operation of the shunt devices and the reactive power provided by the VPPs. The CReST-VCT uses an enhanced Volt-VAr control algorithm with weighted voltage control objects that include minimizing losses, maintaining the voltage within desirable levels, and minimizing the number of mechanical switching of shunt elements. The algorithm runs every 5 minutes and is solved using AC optimal power flow (OPF) solution technique. The outputs include the settings for each sub-transmission-level Volt-VAr control devices and the reactive power generation requirements for each VPP. Then, each VPP will run a distribution Volt-VAr control algorithm to select the PV inverters that provide the Volt-VAr control services considering the distribution network topology. The goal of the VPP reactive power control is to meet the transmission level service requirements while maintaining the voltage and line flow in the distribution system within limits. Each VPP will update its voltage regulation capacity every 5 minutes to allow the CReST-VCT to formulate the optimization problem for the next dispatch interval. The proposed tool is simulated on Duke Energy Carolina system to demonstrate the capability of providing voltage support service by dispatching of reactive power of distributed PV as VPP.

Ke, Xinda↗

Characterizing local high-frequency solar variability and its impact to distribution studies

Accurately representing the local solar variability at timescales relevant to distribution grid operations (30-seconds and shorter) is essential to modeling the impact of solar photovoltaics (PV) on distribution feeders. Due to a lack of available high-frequency solar data, some distribution grid studies have used synthetically-created PV variability or measured PV variability from a different location than their study location. In this work, we show the importance of using accurate solar PV variability inputs in distribution studies. Using high-frequency solar irradiance data from 10 locations in the United States, we compare the ramp rate distributions at the different locations, use a quantitative metric to describe the solar variability, and run distribution simulations using representative 1-week samples from each location to determine the impact of solar variability on the number of tap change operations. Results indicate up to a 300% difference in the number of tap change operations when using PV variability profiles from the different locations.

14 SOLAR ENERGY↗

Estimating PV power from aggregate power measurements within the distribution grid

The increased integration of photovoltaic (PV) systems in distribution grids reduces visibility and situational awareness for utilities because the PV systems' power production is usually not monitored by them. To address this problem, a method called Contextually Supervised Source Separation (CSSS) has been recently adapted for real-time estimation of aggregate PV active power generation from aggregate net active and reactive power measurements at a point in a radially configured distribution grid (e.g., substation). In its original version, PV disaggregation is formulated as an optimization problem that fits linear regression models for the aggregate PV active power generation and true substation active power load. This paper extends the previous work by adding regularization terms in the objective function to capture additional contextual information such as smoothness, by adding new constraints, by introducing new regressors such as ambient temperature, and by investigating the use of time-varying regressors. Furthermore, we perform extensive parametric analysis to study tuning of the objective function weighting factors in a way that maximizes performance and robustness. The proposed PV disaggregation method can be applied to networks with either a single PV system (e.g., megawatt scale) or many distributed ones (e.g., residential scale) connected downstream of the substation. Simulation studies with real field recorded data show that the enhancements of the proposed method reduce disaggregation error by 58% in winter and 35% in summer compared to previous CSSS-based work. When compared against a commonly used transposition model based approach, the reduction in disaggregation error is more pronounced (78% reduction in winter and 45% in summer). Additional simulations indicate that the proposed algorithm is also applicable for PV systems with time-varying power factors. In conclusion, overall, our results show that—with appropriate modeling and tuning—it is possible to accurately estimate the aggregated PV active power generation of a distribution feeder with minimal or no additional sensor deployment.

14 SOLAR ENERGY↗

Evaluation of Adaptive Volt-VAR to Mitigate PV Impacts [Slides]

Distributed generation (DG) sources like photovoltaic (PV) systems with advanced inverters are able to perform grid-support functions, like autonomous Volt-VAR that attempts to mitigate voltage issues by injecting or consuming reactive power. However, the Volt-VAR function operates with VAR priority, meaning real power may be curtailed to provide additional reactive power support. Since some locations on the grid may be more prone to higher voltages than others, PV systems installed at those locations may be forced to curtail more power, adversely impacting the value of that PV system. Adaptive Volt-VAR (AVV) could be implemented as an alternative, whereby the Volt-VAR reference voltage changes over time, but this functionality has not been well-explored in the literature. In this work, the potential benefits and grid impacts of AVV were investigated using yearlong quasi-static time-series (QSTS) simulations. After testing a variety of allowable AVV settings, we found that even with aggressive settings AVV resulted in <0.01% real power curtailment and significantly reduced the reactive power support required from the PV inverter compared to conventional Volt-VAR but did not provide much mitigation for extreme voltage conditions. The reactive power support provided by AVV was injected to oppose large deviations in voltage (in either direction), indicating that it could be useful for other applications like reducing voltage flicker or minimizing interactions with other voltage regulating devices.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Cost-Effectiveness of Local Distribution Tied Solar within KyMEA

KyMEA is a Kentucky joint action agency which provides electric transmission and energy services to eleven municipal utilities. One of KyMEA's member cities, Frankfort, has set a goal to reach 100% renewable generation for the city load by 2023 and 100% carbon free city operations and 100% renewable generation community-wide by 2030. The aim of this research was to determine if the Frankfort city government could reduce its power costs by implementing distribution tied solar while also avoiding any cross subsidization between other KyMEA member utilities or other Frankfort Plant Board customers. The project simulated the KyMEA generation portfolio and transmission system from KyMEA's cost perspective using the NREL Engage capacity expansion model. Running in operate mode, the authors used Engage to compare KyMEA's costs to operate the baseline system to its costs to operate the system with Frankfort meeting some of its load with distribution-tied PV. The cost perspective of Frankfort Plant Board, meanwhile, was simulated using Python. The simulations indicated that it would be cost-beneficial to KyMEA, i.e., that no additional costs would be borne by other members, and that it would be cost-neutral to Frankfort Plant Board for Frankfort city government to implement distribution tied utility-scale PV. The new load attributes resulting from the distribution-tied PV lowered KyMEA's cost to serve load by improving system load factor, reducing system transmission and energy costs, and increasing revenues from market energy sales.

14 SOLAR ENERGY↗