Identifying Potential Sub-Synchronous Oscillations Using Impedance Scan Approach: Preprint

This paper presents an impedance scan study on the real-world power system in Australia that has observed 17 to 20 Hz intermittent subsynchronous oscillations. Through the impedance scan of each of the IBRs, both individually and collectively, potential resonance modes are identified. The impedance scans were carried out using electromagnetic transient PSCAD models of the network. The network comprises of site-specific, black-boxed models of IBRs supplied by the generators. The impedance scan approach was divided in three major steps: (1) the first step is to identify IBRs where impedance analysis needs to be performed based on the magnitude of oscillations observed at their points of interconnection (POIs); (2) the second step focuses on performing impedance scans at selected IBRs in single-machine infinite-bus (SMIB) configuration to identify internal resonance modes of an IBR and to evaluate if any of these modes become unstable under certain grid conditions; (3) the third step performs impedance scans at a few selected IBRs while connected to the wider network model to obtain the impedance response of both the IBR and the grid - this step evaluates control interactions among IBRs. The impedance scan study found that a few IBRs have an underdamped resonance mode at around 17 Hz, which becomes unstable under a certain operating condition. Another interesting finding was that certain IBRs increase the effective grid impedance seen by another IBR in proximity for a particular operating condition. Under this operating condition, the resulting subsynchronous oscillation mode is more pronounced due to a combination of control interactions among IBRs through the transmission network under study and a resonance mode inside the IBRs.

control interactions↗

Design of a Non-PLL Grid-Forming Inverter for Smooth Microgrid Transition Operation

This paper develops a controller for a grid-forming (GFM) inverter that is capable of operating as either a GFM or grid-feeding source that can improve the operation of a microgrid during on-off grid transitions through use of a novel synchronization approach. Furthermore, this controller avoids use of a phase-locked loop (PLL) and the inverter is able to synchronize with the grid with self-generated voltage and frequency. This prevents the inverter from replicating any grid voltage disturbances in its output—a key disadvantage of many grid-connected inverters that use a PLL. To enable fast synchronization, active synchronization control is adopted both during inverter start-up and microgrid reconnection operation and a method of coordinating synchronization of the inverter with a microgrid controller and grid interconnection circuit breaker is presented. Simulation results for multiple microgrid transition operations and unplanned islanding events demonstrate that the developed non-PLL grid-connected GFM inverter controller and synchronization method are effective in synchronizing the inverter and microgrid to the grid, avoiding phase jump during microgrid transition operation, and improving microgrid islanding transients versus a traditional configuration.

27 ARPA - Advanced Research Projects Agency-Energy↗

Enhanced Large-Signal Stability Method for Grid-Forming Inverters During Current Limiting: Preprint

Grid-forming (GFM) inverters are a promising technology for the widespread integration of renewable energy sources in future power systems. As a key element of GFM inverter control, the primary controller governs the internal reference voltage and angle. During contingencies in the grid---such as faults, voltage drops, or frequency and phase jumps---an inverter can be forced into a current-limiting mode of operation modulating inverter dynamics, and, as a result, it is prone to losing synchronism with the grid. In this paper, we propose a novel GFM primary control method with an additional synchronization term that naturally activates during contingencies to improve the dynamic response. The method allows the inverter to remain synchronized with the grid, which improves the inverter's dynamic behavior both during and after current-limiting grid conditions and enhances grid support, including voltage support using full current capacity. The method is demonstrated for voltage, frequency, and phase jumps both in a single-machine-to-infinite-bus and a network-wide electromagnetic transient simulation of the IEEE 14-bus system with 5 GFM inverters. The simulations provide insights into the proposed synchronization method and confirm the high potential of the method, which robustly secures synchronism under severe contingencies.

current limiting↗

Evaluating asynchronous Schwarz solvers on GPUs

With the commencement of the exascale computing era, we realize that the majority of the leadership supercomputers are heterogeneous and massively parallel. Even a single node can contain multiple co-processors such as GPUs and multiple CPU cores. For example, ORNL’s Summit accumulates six NVIDIA Tesla V100 GPUs and 42 IBM Power9 cores on each node. Synchronizing across compute resources of multiple nodes can be prohibitively expensive. Hence, it is necessary to develop and study asynchronous algorithms that circumvent this issue of bulk-synchronous computing. In this study, we examine the asynchronous version of the abstract Restricted Additive Schwarz method as a solver. We do not explicitly synchronize, but allow the communication between the sub-domains to be completely asynchronous, thereby removing the bulk synchronous nature of the algorithm. We accomplish this by using the one-sided Remote Memory Access (RMA) functions of the MPI standard. We study the benefits of using such an asynchronous solver over its synchronous counterpart. We also study the communication patterns governed by the partitioning and the overlap between the sub-domains on the global solver. Finally, we show that this concept can render attractive performance benefits over the synchronous counterparts even for a well-balanced problem.

Nayak, Pratik↗

Inverter-Based Operation of Maui: Electromagnetic Transient Simulations

As larger and larger power systems approach and reach 100% inverter-based resource (IBR) operation during some hours of the year, questions arise regarding the stability of such extremely-high IBR power systems, the potential need for grid-forming (GFM) inverter technology, and the potential need for synchronous condensers. Relatedly, questions also arise about the ability of conventional positive sequence power system modeling tools to capture high-IBR system dynamics. This presentation introduces electromagnetic transient (EMT) simulations in PSCAD of the near-future (year 2023) Maui power system at and near 100% IBR operation and compares those simulations to positive sequence (PSSE) simulations. The Maui PSCAD model is parallelized on 30 cores and includes the entire transmission system (>200 three-phase buses), >170 individual and aggregate IBR models, four wind plants, and three synchronous generators plus six synchronous condensers at two locations. We investigate system stability with varying levels of inertia using conventional grid-following IBR controls, and then we investigate the impact of GFM controls on stability. Results suggest that: 1) positive sequence simulations can miss key dynamics in extremely high IBR cases; 2) EMT simulations can also miss key dynamics if inverter inner control dynamics are not modeled; 3) synchronous condensers can stabilize a system in which 100% of the energy is supplied by IBRs, even conventional grid-following IBRs; 4) GFM controls on just some of the IBRs can stabilize a 100% IBR power system, even if that system has zero inertia (i.e. no synchronous condensers, though synchronous condensers may be needed for other purposes such as protection system operations).

41 EE - Solar Energy Technologies Office (EE-4S)↗

Distribution System Blackstart and Restoration Using DERs and Dynamically Formed Microgrids

Extreme weather events have led to long-duration outages in the distribution system (DS), necessitating novel approaches to blackstart and restore the system. Existing blackstart solutions utilize blackstart units to establish multiple microgrids (MGs), sequentially energize non-blackstart units, and restore loads. However, these approaches often result in isolated MGs. In DERs-aided blackstart, the continuous operation of these MGs is limited by the finite energy capacity of commonly used blackstart units like battery energy storage (BES)-based gridforming inverters (GFMIs). To address this issue, this article proposes a holistic blackstart and restoration framework that incorporates synchronization between dynamic MGs and the entire DS with the transmission grid (TG). To support synchronization, we leveraged virtual synchronous generator-based control for GFMIs to estimate their frequency response to load pick-up events using only initial/final quasi-steady-state points. Subsequently, a synchronization switching condition is developed to model synchronizing switches, aligning them seamlessly with a linearized branch flow problem. Finally, we designed a bottomup blackstart and restoration framework that considers the switching structure of the DS, energizing/synchronizing switches, DERs with grid-following inverters, and BES-based GFMIs with frequency security constraints. In conclusion, the proposed framework is validated in IEEE-123-bus system, considering cases with two and four GFMIs under various TG recovery instants.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design of a Non-PLL Grid-Forming Inverter for Smooth Microgrid Transition Operation: Preprint

This paper develops a non-phase-locked loop (PLL) grid-connected inverter that can improve the microgrid’s transients during transition operation. By emulating the operation of a synchronous machine, the inverter generates its own voltage and frequency during startup, synchronizes and connects to the grid, then operates in reactive power mode (grid-feeding) with self-generated voltage and frequency, and switches to voltage-frequency mode to establish system voltage and frequency (grid-forming) when the microgrid disconnects from the main grid, and vice versa. To enable fast synchronization, active synchronization control is adopted both during inverter startup and microgrid reconnection operation. The simulation results show that the developed non-PLL grid-connected inverter works effectively to synchronize the inverter and microgrid to the grid and avoids a phase jump during microgrid transition operation. Thus, the microgrid’s transients are significantly improved with the proposed control technique.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Enhanced flood synchrony and downstream severity in the Delaware River under rising temperatures

River floods threaten life and economic stability, with risks increasing globally, especially in densely populated coastal areas. In mountainous coastal watersheds like the Delaware River Basin, rising temperature is projected to reduce snowpack, reshaping upstream–downstream flood dynamics. However, the impact on flood synchronization between upland tributaries and estuarine mainstems remains poorly understood. Using multidecadal streamflow simulations from a high-resolution hydrological model, we find significant increases in the frequency and magnitude of synchronized floods under future warming scenarios, particularly severe floods (above the 75 th percentile). Under higher warming scenarios, snowpack and rain-on-snow floods in headwater subbasins nearly vanish. Surprisingly, this regime shift amplifies estuarine flooding by enhancing synchronization between historically snow-dominated subbasins and their downstream counterparts. Despite intensified synchronization and flood magnitude, cold-season flood risk declines due to fewer rain-on-snow events. Conversely, summer floods grow larger, more frequent, and synchronized, driving a seasonal reconfiguration of flood risk that should be considered in future mitigation strategies.

59 BASIC BIOLOGICAL SCIENCES↗

Developing a Reduced 240-Bus WECC Dynamic Model for Frequency Response Study of High Renewable Integration

The ongoing changes in the generation resource mix, driven by the rapid adoption of inverter-based resources (IBR) as well as the early retirement of synchronous generators, are bringing new challenges to the planning and operation of bulk electric power systems. Consequently, there is an increasing need to understand, design, and quantify the reliability service provision from IBRs by performing integrated scheduling and dynamic simulations. However, test systems that have consistent scheduling and dynamic models rarely exist largely because of the decoupled nature of the two simulations on a synchronous generator-dominated system. This paper develops the dynamic model of a reduced Western Electricity Coordinating Council (WECC) system. In conjunction with the existing scheduling model, it is suitable for integrating scheduling and dynamic simulations. The reduced 240-bus WECC model reflects the generation resource mix of the Western Interconnection as of 2018. Moreover, the developed dynamic model is validated against field frequency events measured by FNET/GridEye and preserves the dominant inter-area oscillation mode in WECC.

dynamic simulation↗

Oscillation Risks of Grid-Following and Grid-Forming Inverter-Based Resources in Series-Compensated Networks

Here, this paper investigates the dynamic behavior of a grid-connected inverter-based resource (IBR) when connected radially to a series compensated line. Potential interactions between the series compensation and the IBR have been identified for both types: grid-following (GFL) or grid-forming (GFM). The study begins with electromagnetic transient (EMT) simulations to demonstrate stability issues. Subsequently, nonlinear analytical models are formulated in the dq frame, validated against the EMT simulation, and leveraged to assess eigenvalues and participation factors. Influencing factors of the dominant oscillation modes have been identified. The analysis results show that series compensation may make a mode associated with the synchronization unit unstable. Furthermore, customized feedback systems are built for the synchronizing loop. Series compensation can increase the sensitivity of the voltage phase angle towards the synchronizing angle, and introduce phase lag in the real power response towards the synchronizing angle. These factors may cause interactions with the phase-locked loop in GFL-IBR systems and with power-based synchronization in GFM-IBR systems, potentially leading to instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decentralized Control of Cascaded H-Bridge Inverters for Medium-Voltage Grid Integration: Preprint

This paper introduces a fully decentralized control strategy that allows for individualized active and reactive power control of H-bridge inverters connected in series. After formulating a model of the system power flows, we outline a communications-free approach where each inverter can act on independent commands. Inverter-level feedback is accomplished locally via a measurement of current flowing through the stack. A key feature is the lack of any centralized control routines or phase-locked loop. In this framework, the reactive power control loops achieve voltage synchronization among the converters and the grid, and the active power control loops modulate the terminal voltage amplitudes that influence power delivery. Furthermore, pole placement via state feedback is used to ensure stability of voltage synchronization while also enabling tracking of bidirectional power commands. Simulations are presented to validate the proposed approach.

communication-free modular converter control↗

Vulnerability of a VOC-Based Inverter Due to Noise Injection and Its Mitigation

Even though virtual oscillator control (VOC)-based inverters do not communicate with each other, they need to make local measurements for control. The impact of tampering with these measured or sensed signals on the performance of a VOC-based inverter and synchronization of multiple such inverters is an important but open-ended issue. As such, this letter explores the impact of intentional side-channel noise intrusion (SNI) on the synchronization of VOC-based communication-free self-synchronizing inverters (CFSIs). Two different scenarios are investigated via experimental and analytical studies using a half-bridge neutral point clamped (NPC) single-phase CFSI. Furthermore, they address the impact of SNI on the ability of a CFSI to ensure a stable 60-Hz limit cycle and on the parallel operation of two such CFSIs to ensure synchronism to a common 60-Hz load frequency.

42 ENGINEERING↗

Roles of Dynamic State Estimation in Power System Modeling, Monitoring and Operation

—Power system dynamic state estimation (DSE) remains an active research area. This is driven by the absence of accurate models, the increasing availability of fast-sampled, time synchronized measurements, and the advances in the capability, scalability, and affordability of computing and communications. This paper discusses the advantages of DSE as compared to static state estimation, and the implementation differences between the two, including the measurement configuration, modeling framework and support software features. The important roles of DSE are discussed from modeling, monitoring and operation aspects for today’s synchronous machine dominated systems and the future power electronics-interfaced generation systems. Several examples are presented to demonstrate the benefits of DSE on enhancing the operational robustness and resilience of 21st century power system through time critical applications. Future research directions are identified and discussed, paving the way for developing the next generation of energy management systems.

Zhao, Junbo↗

Employing Interacting Qubits for Distributed Microgrid Control

To empower flexible and scalable operations, distributed control of multi-inverter microgrids, based on classical communication networks among distributed energy resources, has attracted considerable attention as it can guarantee synchronization and provide suitable remedies to the problem of improper power sharing. Notwithstanding this, resilience of the current schemes on classical communication makes microgrids vulnerable to cyber attacks. Inspired by recent revolutionary breakthroughs in quantum communication, in this paper, we devise a novel synchronization mechanism. We extend the synchronization framework utilized in distributed control algorithms to networks of quantum systems by generating pinning terms and coupling mechanism for the new synchronization rule via exploiting proper quantum jump operators and observables, and show that the quantum system will converge to a time-variant target state. Our devised quantum distributed controller (QDC) gives rise to a novel quantum communication scheme for distributed control of microgrids and enables microgrids to exploit the state-of-the-art quantum communication frameworks as communication infrastructure. Finally, test results on two representative AC and DC networked microgrids validate the efficacy and universality of the quantum distributed control.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Tempus Project (Final Report)

This final technical report tracks the accomplishments of the Tempus Project to the statement of project objectives and resulting deliverables. The objective of the Tempus project was to develop and demonstrate the capabilities of a secure, modular, and customizable time synchronization platform that provides layers of protection from GPS spoofing attacks and other vulnerabilities. These vulnerabilities present a challenge to power system operators utilizing GPS-based time synchronization, as time synchronization increasingly plays a critical role in the efficient and reliable operation of power systems. The Tempus project addressed these concerns through the development of a secure, customizable time synchronization platform. The Tempus platform applies a layered approach to time security that protects from manipulation of timing systems used by power utilities. The Tempus platform consists of a component framework utilizing modularized time sources and customizable manipulation detection algorithms. With multiple time sources, and comparisons between sources and tracking sudden or subtle changes to the timing phase and time information, the Tempus system can detect and mitigate compromised timing sources.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Unified Universal Control and Coordination of Inverter-Based Resources, and Validation for a PV + Battery Hybrid Plant

As renewable energy deployment grows, hybrid power plants (HPPs) combining photovoltaic (PV) and battery systems must evolve to offer both energy and grid stability services. These systems typically include a mix of grid-following (GFL) and grid-forming (GFM) inverters, presenting unique coordination and control challenges. This Department of Energy–funded project developed and validated a Unified Universal Control and Coordination (UUCC) framework for such PV + battery hybrid plants, enabling seamless and stable operation, including ultrafast black start, autonomous synchronization, and robust frequency and voltage regulation, under different grid conditions. The project significantly advanced the understanding of inverter-based resource (IBR) control by developing and validating three complementary system-level approaches for hybrid GFL/GFM operation: 1. A combined Virtual Resistance (VR)-based GFL and Virtual Oscillator Control (VOC)-based GFM method, where each inverter type is governed by a specialized control strategy. Together, these achieve stable, fast-response coordination, eliminating inrush current and enabling smooth black start and grid synchronization across a wide range of grid strengths. 2. A Deadbeat-based UUCC strategy, which uses discrete-time, switching-cycle-level control for both GFL and GFM inverters. This approach replaces traditional PI/PLL control with a control parameter-free, high-bandwidth framework that supports stable LVRT and instantaneous synchronization under all conditions. 3. A benchmark comparison with Siemens’ commercial GFM microgrid controller, which provided a fast baseline platform. The commercial approach decoupled v & f control was implemented on a commercial microgrid controller.The baseline commercial benchmark helped highlight superior transient response and black start performance offered by the deadbeat and VOC approaches. These technical contributions offer substantial improvements over conventional inverter control schemes, which often rely on slow phase-locked loop (PLL)-based synchronization, require careful control parameters tuning, and prone to unstable in weak grids with GFL inverters and in stiff grid with GFM inverters therefore challenging for hybrid GFL+GFM under all grid conditions. The deadbeat-based UUCC framework enables simpler, faster, and more robust operation of hybrid IBR systems using wide-bandgap (WBG) devices such as SiC power semiconductors. The rapid expansion of hybrid distributed energy resources (DERs), including residential and commercial PV-BESS installations such as Tesla Powerwall, PV with vehicle-to-grid (V2G) capability, and other integrated configurations, presents complex operational challenges for medium-voltage radial distribution feeders. These networks are subject to frequent disturbances such as faults, switching operations, rapid reclosing sequences, and feeder reconfigurations, all of which introduce dynamic stress on IBRs. In addition, planned feeder segmentation and deliberate islanding for resilience will require DERs that can autonomously perform blackstart, establish voltage and frequency references, and resynchronize with the main grid. The advanced deadbeat-based UUCC control and blackstart functionalities developed in this project directly address these requirements, enabling decentralized and autonomous operation of inverter-dominated DERs in distribution systems under a wide range of fault and reconfiguration scenarios. From a public benefit perspective, these innovations enable more reliable and cost-effective integration of renewable energy into distribution networks. The ability to autonomously black start and stabilize grids under varying grid conditions support accelerates recovery from outages and support decentralized resilient energy systems. By reducing system complexity and improving performance, this project lays critical groundwork for future inverter-dominated power grids that are clean, reliable, and accessible to all.

14 SOLAR ENERGY↗