At least 289 records · Page 16

Case Study for the ARRA-funded Ground Source Heat Pump Demonstration at Denver Museum of Nature & Science

High initial costs and lack of public awareness of ground-source heat pump (GSHP) technology are the two major barriers preventing rapid deployment of this energy-saving technology in the United States. Under the American Recovery and Reinvestment Act (ARRA), 26 GSHP projects were competitively selected and carried out to demonstrate the benefits of GSHP systems and innovative technologies for cost reduction and/or performance improvement. This report highlights the findings of a case study of one such GSHP demonstration projects that uses a recycled water heat pump (RWHP) system installed at the Denver Museum of Nature & Science in Denver, Colorado. The RWHP system uses recycled water from the city’s water system as the heat sink and source for a modular water-to-water heat pump (WWHP). This case study was conducted based on the available measured performance data from December 2014 through August 2015, utility bills of the building in 2014 and 2015, construction drawings, maintenance records, personal communications, and construction costs. The annual energy consumption of the RWHP system was calculated based on the available measured data and other related information. It was compared with the performance of a baseline scenario— a conventional VAV system using a water-cooled chiller and a natural gas fired boiler, both of which have the minimum energy efficiencies allowed by ASHRAE 90.1-2010. The comparison was made to determine energy savings, operating cost savings, and CO2 emission reductions achieved by the RWHP system. A cost analysis was performed to evaluate the simple payback of the RWHP system. Summarized below are the results of the performance analysis, the learned lessons, and recommended improvement in the operation of the RWHP system.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Low-Cost Gas Heat Pump for Building Space Heating

Gas-fired residential space heating in the U.S is predominantly supplied by furnaces and boilers. These technologies have been approaching their thermodynamic limit over the past 30 years and improvements for high efficiency units have approached a point of diminishing return. Electric heat pumps are growing in popularity but their heating performance at low ambient temperatures is poor. The development of a low-cost gas absorption heat pump would offer a significant improvement to current furnaces and boilers, and in heating dominated climate zones when compared to electric heat pumps. Gas absorption heat pumps (GAHP) exceed the traditional limit of thermal efficiency encountered by typical furnaces and boilers, and maintain high levels of performance at low ambient temperatures. The project team designed and demonstrated two low-cost packaged prototype GAHP space heating systems during the course of this investigation. Led by Stone Mountain Technologies Inc. (SMTI), with support from A.O. Smith, and the Gas Technology Institute (GTI), the cross-functional team completed research and development tasks including cycle modeling, 8× scaling of a compact solution pump, combustion system development, breadboard evaluation, fabrication of two packaged prototype units, third party testing of the first prototype, and the evaluation of cost and energy savings compared to high and minimum efficiency gas options. Over the course of the project and with the fabrication of two Alpha prototypes it was shown that this technology met or exceeded most of the stated project targets. At ambient temperatures of 47, 35, 17 and -13°F the prototypes achieved gas based coefficients of performance of 1.50, 1.44, 1.37, and 1.17, respectively. Both units operated with parasitic loads well below the 750 watt target with the second Alpha prototype operating 75-100 watts below the first Alpha prototype. Modulation of the units at 4:1 was achieved with the project goal of 2:1 modulation, which will allow for improved load matching. In addition, the energy savings analysis showed that a house in Albany, NY, Chicago, IL and Minneapolis, MN would save roughly 32, 28.5 and 36.5 MBtu annually when compared to a 100% efficient boiler, respectively. The gas absorption heat pump achieves this performance by using high grade heat from the combustion of natural gas in combination with low grade heat extracted from the ambient to produce medium grade heat suitable for space and water heating. Expected product features include conventional outdoor installation practices, 4:1 modulation, and reasonable economic payback. These factors position the technology to gain significant market penetration, resulting in a large reduction of energy use and greenhouse gas emissions for residential space heating.

03 NATURAL GAS↗

Driftless Area Initiative Biomass Energy Project

The Driftless Area Initiative Biomass Energy Project evaluated the potential for biomass energy production and utilization throughout the Driftless Region of Illinois, Iowa, Minnesota and Wisconsin. The research and demonstration aspect of the project specifically focused on biomass energy feedstock availability and production potential in the region, as well as utilization potential of biomass feedstocks for heat, electrical energy production, or combined heat and power operations. The Driftless Region was evaluated because the topography of the area offers more acres of marginal soils on steep slopes, wooded areas, and riparian corridors than the surrounding “Corn Belt”. These regional land characteristics were identified as potentially providing opportunity for biomass feedstock production that could compete with traditional agriculture commodity crops economically. The project researched establishment methods and costs for growing switchgrass on marginal agricultural lands to determine the economic and quantitative feasibility of switchgrass production for biomass energy purposes. The project was successful in identifying the best management and establishment practices for switchgrass in the Driftless Area, but also demonstrated that simple economic payback versus commodity crops could not be achieved at the time of the research. The project also analyzed the availability of woody biomass and production potential for growing woody biomass for large scale biomass energy production in the Driftless Area. Analysis determined that significant resources exist, but costs to harvest and deliver to the site were roughly 60% greater than that of natural gas at the time of the study. The project contributed significantly to identifying both production potential of biomass energy crops and existing feedstock availability in the Driftless Area. The project also analyzed the economic feasibility of dedicated energy crops in the Driftless Area. High commodity crop prices and land values coupled with low fossil fuel prices, particularly natural gas, hampered the likelihood of widespread production and/or utilization of for large scale heating or electrical generation at the time of the study.

09 BIOMASS FUELS↗

Idling Reduction for Long-Haul Trucks: An Economic Comparison of On-Board and Wayside Technologies

Reducing the idling of long-haul heavy-duty trucks has long been recognized as a particularly low-hanging fruit of fuel efficiency and emissions reduction. The displacement of about 10 hours of diesel idling every day, for most days of the year, for as many as a million long-haul trucks has very clear benefits. This report considers the costs and return on investment (ROI) for idling reduction (IR) equipment for both truck owners and electrified parking space (EPS) equipment owners. For the truck owners, the key variables examined are idling hours to be displaced (generally 1,000 to 2,000 hours per year) and the price of fuel ($0 to $5/gal). The ideal IR option would provide complete services in varied climates in any location and offer the best ROI on trucks that log many idling hours. For trucks that have fewer idling hours, options with a fixed cost per hour (i.e., EPS) might be most attractive if they were available to all, or even most, truck drivers. EPS, however, is particularly cost effective for trucks on prescribed routes with a need for regular, extended stops at terminals. (EPS is also called truck stop electrification, or TSE.) The analysis shows that all IR options save money when fuel costs more than $2/gal. For trucks requiring bunk heat, a simple heater (plug-in or diesel) is almost always the most costeffective way to provide heat, even if the truck is equipped with an auxiliary power unit (APU) or is parked at a single-system EPS location. For trucks requiring bunk air-conditioning, the use of single-system EPS is most cost effective for those logging fewer idling hours. Even for trucks with higher idling hours, the cost of EPS may be about the same as that for on-board air-conditioning. Clearly, trucks’ locations and seasonal factors—and the availability of EPS— are significant in the choice of “best fit” IR equipment for truck owners. This report also considers costs and payback for owners of EPS infrastructure. An industry that 5 years ago had at least five players has been narrowed to two companies—one in single-system EPS (IdleAir) and the other in dual-system EPS (Shorepower Technologies). Use of EPS by truck drivers has not met initial expectations for a variety of reasons. One area where EPS has particular promise, however, is in the cost-effective provision of reliable air-conditioning. This analysis is focused strictly on cost and fuel savings; it does not consider the important benefits of reduced emissions (i.e., greenhouse gases and criteria pollutants). It is important to note that all IR options provide some emissions benefits. Even where an IR option may not have a rapid ROI, the emissions-reduction benefit may be considerable. Finally, as the U.S. Environmental Protection Agency (EPA) and the U.S. Department of Transportation’s National Highway Traffic Safety Administration (NHTSA) set stricter standards to reduce greenhouse gas emissions and improve the fuel efficiency of medium- and heavy-duty vehicles, the emissions benefits of IR strategies will become increasingly important.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Case Study for the ARRA-Funded Ground Source Heat Pump Demonstration at Ball State University

With funding provided by the American Recovery and Reinvestment Act (ARRA), 26 ground-source heat pump (GSHP) projects were competitively selected in 2009 to demonstrate the benefits of GSHP systems and innovative technologies for cost reduction and/or performance improvement. One of the selected demonstration projects is a district central GSHP system installed at Ball State University (BSU) in Muncie, IN. Prior to implementing the district GSHP system, 47 major buildings in BSU were served by a central steam plant with four coal-fired and three natural-gas-fired steam boilers. Cooling was provided by five water-cooled centrifugal chillers at the District Energy Station South (DESS). The new district GSHP system replaced the existing coal-fired steam boilers and conventional water-cooled chillers. It uses ground-coupled heat recovery (HR) chillers to meet the simultaneous heating and cooling demands of the campus. The actual performance of the GSHP system was analyzed based on available measured data from August 2015 through July 2016, construction drawings, maintenance records, personal communications, and construction costs. Since Phase 1 was funded in part by the ARRA grant, it is the focus of this case study. The annual energy consumption of the GSHP system was calculated based on the available measured data and other related information. It was compared with the performance of a baseline scenario— a conventional water-cooled chiller and natural-gas-fired boiler system, both of which meet the minimum energy efficiencies allowed by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE 90.1-2013). The comparison was made to determine source energy savings, energy cost savings, and CO2 emission reductions achieved by the GSHP system. A cost analysis was performed to evaluate the simple payback of the GSHP system. The following sections summarize the results of the analysis, the lessons learned, and recommendations for improvement in the operation of this district GSHP system.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Multifamily Heat Pump Water Heater Evaluation

Although heat pump water heaters (HPWHs) have gained significant attention in recent years as a high efficiency electric water heating solution for single family homes, central HPWHs for commercial or multi-family applications are not as well documented in terms of measured performance and cost effectiveness. To evaluate this technology, the Alliance for Residential Building Innovation team monitored the performance of a 10.5 ton central HPWH installed on a student apartment building at the West Village Zero Net Energy Community in Davis, California. Monitoring data collected over a 16 month period were then used to validate a TRNSYS simulation model. The TRNSYS model was then used to project performance in different climates using local electric rates. Results of the study indicate that after some initial commissioning issues, the HPWH operated reliably with an annual average efficiency of 2.12 (Coefficient of Performance). The observed efficiency was lower than the unit's rated efficiency, primarily due to the fact that the system rarely operated under steady-state conditions. Changes in the system configuration, storage tank sizing, and control settings would likely improve the observed field efficiency. Modeling results suggest significant energy savings relative to electric storage water heating systems (typical annual efficiencies around 0.90) providing for typical simple paybacks of six to ten years without any incentives. The economics versus gas water heating are currently much more challenging given the current low natural gas prices in much of the country. Increased market size for this technology would benefit cost effectiveness and spur greater technology innovation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Multifamily Heat Pump Water Heater Evaluation

Although heat pump water heaters (HPWHs) have gained significant attention in recent years as a high efficiency electric water heating solution for single family homes, central HPWHs for commercial or multi-family applications are not as well documented in terms of measured performance and cost effectiveness. To evaluate this technology, the Alliance for Residential Building Innovation team monitored the performance of a 10.5 ton central HPWH installed on a student apartment building at the West Village Zero Net Energy Community in Davis, California. Monitoring data collected over a 16 month period were then used to validate a TRNSYS simulation model. The TRNSYS model was then used to project performance in different climates using local electric rates. Results of the study indicate that after some initial commissioning issues, the HPWH operated reliably with an annual average efficiency of 2.12 (Coefficient of Performance). The observed efficiency was lower than the unit's rated efficiency, primarily due to the fact that the system rarely operated under steady-state conditions. Changes in the system configuration, storage tank sizing, and control settings would likely improve the observed field efficiency. Modeling results suggest significant energy savings relative to electric storage water heating systems (typical annual efficiencies around 0.90) providing for typical simple paybacks of six to ten years without any incentives. The economics versus gas water heating are currently much more challenging given the current low natural gas prices in much of the country. Increased market size for this technology would benefit cost effectiveness and spur greater technology innovation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Multifamily Heat Pump Water Heater Evaluation

Although heat pump water heaters (HPWHs) have gained significant attention in recent years as a high efficiency electric water heating solution for single family homes, central HPWHs for commercial or multi-family applications are not as well documented in terms of measured performance and cost effectiveness. To evaluate this technology, the Alliance for Residential Building Innovation team monitored the performance of a 10.5 ton central HPWH installed on a student apartment building at the West Village Zero Net Energy Community in Davis, California. Monitoring data collected over a 16 month period were then used to validate a TRNSYS simulation model. The TRNSYS model was then used to project performance in different climates using local electric rates. Results of the study indicate that after some initial commissioning issues, the HPWH operated reliably with an annual average efficiency of 2.12 (Coefficient of Performance). The observed efficiency was lower than the unit's rated efficiency, primarily due to the fact that the system rarely operated under steady-state conditions. Changes in the system configuration, storage tank sizing, and control settings would likely improve the observed field efficiency. Modeling results suggest significant energy savings relative to electric storage water heating systems (typical annual efficiencies around 0.90) providing for typical simple paybacks of six to ten years without any incentives. The economics versus gas water heating are currently much more challenging given the current low natural gas prices in much of the country. Increased market size for this technology would benefit cost effectiveness and spur greater technology innovation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Improved heavy-duty vehicle fuel efficiency in India, benefits, costs and environmental impacts

The main objectives of this analysis are to examine the benefits and costs of fuel-saving technologies for new heavy-duty vehicles (HDVs) in India over the next 10 years and, to explore how various scenarios for the deployment of vehicles with these technologies will impact petroleum consumption and carbon dioxide (CO 2 ) emissions over the next three decades. The study team developed simulation models for three representative HDV types—a 40-tonne tractor-trailer, 25-tonne rigid truck, and 16-tonne transit bus—based on top-selling vehicle models in the Indian market. The baseline technology profiles for all three vehicles were developed using India-specific engine data and vehicle specification information from manufacturer literature and input from industry experts. For each of the three vehicles we developed a comprehensive set of seven efficiency technology packages drawing from five major areas: engine, transmission and driveline, tires, aerodynamics, and weight reduction. Our analysis finds that India has substantial opportunity to improve HDV fuel efficiency levels using cost-effective technologies. Results from our simulation modeling of three representative HDV types—a tractor-trailer, rigid truck, and transit bus—reveal that per-vehicle fuel consumption reductions between roughly 20% and 35% are possible with technologies that provide a return on the initial capital investment within 1 to 2 years. Though most of these technologies are currently unavailable in India, experiences in other more advanced markets such as the US and EU suggest that with sufficient incentives and robust regulatory design, significant progress can be made in developing and deploying efficiency technologies that can provide real-world fuel savings for new commercial vehicles in India over the next 10 years. Bringing HDVs in India up to world-class technology levels will yield substantial petroleum and GHG reductions. By 2030, the fuel and CO2 reductions of the scenarios range from 10% to 34%, and at the end of 2050, these reductions grow to 13% and 41%. If we constrain the analysis to select the most efficient technology package that provides the fleets with payback times of 3 years or less, there are annual fleet-wide savings of roughly 11 MTOE of diesel and 34 MMT of CO 2 in 2030, and this grows to 31 MTOE and 97 MMT by 2050.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Chapter 16: Retrocommissioning Evaluation Protocol. The Uniform Methods Project: Methods for Determining Energy Efficiency Savings for Specific Measures

Retrocommissioning (RCx) is a systematic process for optimizing energy performance in existing buildings. It specifically focuses on improving the control of energy-using equipment (e.g., heating, ventilation, and air conditioning [HVAC] equipment and lighting) and typically does not involve equipment replacement. Field results have shown proper RCx can achieve energy savings ranging from 5 percent to 20 percent, with a typical payback of two years or less (Thorne 2003). The method presented in this protocol provides direction regarding: (1) how to account for each measure's specific characteristics and (2) how to choose the most appropriate savings verification approach.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Estimating Energy Consumption of Mobile Fluid Power in the United States

This report estimates the market size and energy consumption of mobile off-road applications utilizing hydraulic fluid power, and summarizes technology gaps and implementation barriers. Mobile fluid power is the use of hydraulic fluids under pressure to transmit power in mobile equipment applications. The mobile off-road fluid power sector includes various uses of hydraulic fluid power equipment with fundamentally diverse end-use application and operational requirements, such as a skid steer loader, a wheel loader or an agriculture tractor. The agriculture and construction segments dominate the mobile off-road fluid power market in component unit sales volume. An estimated range of energy consumed by the mobile off-road fluid power sector is 0.36 - 1.8 quads per year, which was 1.3 percent - 6.5 percent of the total energy consumed in 2016 by the transportation sector. Opportunities for efficiency improvements within the fluid power system result from needs to level and reduce the peak system load requirements and develop new technologies to reduce fluid power system level losses, both of which may be facilitated by characterizing duty cycles to define standardized performance test methods. There are currently no commonly accepted standardized test methods for evaluating equipment level efficiency over a duty cycle. The off-road transportation sector currently meets criteria emissions requirements, and there are no efficiency regulations requiring original equipment manufacturers (OEM) to invest in new architecture development to improve the fuel economy of mobile off-road fluid power systems. In addition, the end-user efficiency interests are outweighed by low equipment purchase or lease price concerns, required payback periods, and reliability and durability requirements of new architecture. Current economics, low market volumes with high product diversity, and regulation compliance challenge OEM investment in commercialization of new architecture development.

13 HYDRO ENERGY↗

Industrial Scale Demonstration of Smart Manufacturing, Achieving Transformational Energy Productivity Gains

While many U.S. manufacturing operations utilize optimization for individual unit processes, smart manufacturing (SM) systems that integrate manufacturing intelligence in real time across an entire production operation are rare in large companies and virtually nonexistent in smaller organizations. One example of an area where SM systems can be applied is in the management of waste heat. A smart system that not only seeks to recover waste heat, but also to use energy more efficiently, is a more cost-effective approach because energy use, waste energy loss and product output are optimized together. The overall objective of this project was to develop an industry-accepted SM Platform that enables smart systems by accelerating and lowering the cost of development and implementation scales for use in diverse sets of manufacturing industry sectors, manufacturing operations and company sizes. Specifically, the project (1) designed and demonstrated the application of a prototype SM Platform for two diverse commercial test beds, (2) demonstrated at one and estimated for the other test bed the potential reduction in waste heat generation, and (3) worked with leading automation vendors to catalyze low-cost commercialization of the technology developed. The Smart Manufacturing Application and Data Platform (SM Platform) developed during this project is an innovative approach that marries IT virtualization technologies with operational data and modeling system requirements to construct a ready-to-go platform for enabling sensor – data – modeling – actuation systems, driven by real-time plant data and performance metrics. This SM Platform allows manufacturing organizations, regardless of their industry or size, to assemble new operational systems at a much lower cost, optimizing process knowledge and improving energy productivity by integrating with existing process control and automation systems. Also developed during this project is a methodology for developing energy productivity metrics that use real-time process information and provide comparisons for potential, practical, and actual performance, as well as examples and the methodology for provisioning of an Energy Dashboard that displays alternatives to optimize energy use within specific business contexts aimed at helping improve energy productivity and reduce emissions in U.S. manufacturing. The SM Platform designed utilizes current manufacturing, operational and IT industry standards. The platform can be used to expedite sensor – data – model – actuation system development and deployment in a cloud-based environment using a novel end-to-end workflow as a service capability that is already integrated with data connection, ingestion, and contextualization services. In addition, the methodology for development of energy productivity metrics and reusable application templates called Toolkits have been defined so that they can be tailored to a specific business situation. The project’s two test beds, one in a hydrogen production plant and the other in a forging, heat treatment, and machining operation, utilize sensor-driven modeling, measurement, and simulation systems. In these two test beds, the implementation of these as a comprehensive system has made it possible for energy productivity to be managed in real-time throughout the plant and enterprise using an energy dashboard. The development pathway to direct machine actuation was articulated. During the first year, the project team developed the most highly instrumented steam-methane reformer (SMR) in the U.S. using infrared cameras and thermocouples. Real-time data are streamed to high fidelity and reduced-order models for analysis. A high fidelity CFD model, parallelized in the SM Platform cloud environment, was demonstrated for operational use. This is the first real-time operational productivity system of a steam methane reformer using both high fidelity and data-driven models together in a real time situation to balance natural gas flow to the reformer tubes. An infrared camera system was developed and shown to outperform thermocouples in coverage, accuracy, reliability, and cost effectiveness for use in a high temperature, harsh environment. A forging, heat-treating, machining line operation test bed includes new instrumentation for data capture analysis, modeling, and simulation and will be integrated into SM Platform workflows so that business performance can be managed in real-time. Composable metrics were developed using the SM Platform to drive improvements in energy productivity, environmental performance, safety, asset management, costs, and overall operations. A major focus of the SM systems developed was optimization of energy productivity at the enterprise level, which resulted in reductions in waste heat generation for the two project test beds. Reductions in the waste heat generated will result in greater energy savings than will waste heat recovery due to inefficiencies in the heat transfer process. For the SMR test bed an efficiency improvement of 1 – 2% with a corresponding waste heat reduction of 5% were demonstrated. It should be noted that the test bed SMR unit had an efficiency of more than 90% as compared to 70 to 80% efficiencies of most SMR units. So implementation of similar SM systems at typical SMR units could yield more than 15 to 25% waste heat reductions. Similarly the forging, heat-treating, machining line operation test bed is a DOE AMO Platinum Level Superior Energy Performance plant with a much higher than typical overall operating efficiency. For this test bed heat integration using recuperators is estimated to result in fuel savings of 15.9% due to waste heat recovery compared to the base case without recuperators with negligible changes in part exit conditions. This results in an 18.9% energy efficiency improvement. The project team estimates that broad multi-sector adoption of the developed technology could reduce waste heat generation by an amount equivalent to 1.3% of total U.S. energy use. This waste heat reduction is associated with 69 million tons reduction in annual carbon dioxide emissions. Other potential benefits include reducing process times, solid and liquid wastes, environmental impacts, and water use. It is estimated that this investment has an anticipated payback period of less than one year in energy-intensive applications. The SM Platform could also reduce the costs of deploying SM systems by 50% in manufacturing operations. Commercialization of the SM Platform will require significant cross-industry collaboration and technology provider market changes. Steps taken toward commercialization included 1) analyzing savings from deployment of the SM Platform and 2) holding SM Platform workshops, webinars, and conferences with targeted individual industry segments, with a focus on small and medium-sized organizations. An upgraded community website has been established as a portal for accessing and distributing information. Most importantly, the SM platform enabling technology developed during this project and its commercialization will continue, evolve and expand under the Clean Energy Smart Manufacturing Innovation Institute (CESMII).

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Analysis of Cost Reduction Potential of Vertical Bore Ground Heat Exchanger (Final)

The geothermal heat pump (GHP), also referred to as a ground source heat pump, is a proven technology that can provide space conditioning and water heating with efficiencies higher than conventional heating, ventilation, and air-conditioning (HVAC) systems. This technology possesses great potential to become a mainstream technology for satisfying the thermal demands in the built environment. Analysis from the ongoing Geothermal Vision Study indicates that 100% retrofitting of commercial and residential markets with GHPs has the potential to save on the order of 6 quadrillion Btu per year (Liu et al. 2017). However, the current high installation costs and long payback periods limit the attractiveness of GHP installation in the United States. The cost of installing ground heat exchangers (GHXs) used for GHPs accounts for more than 30% of the total cost of a GHP system (NYSERDA 2017), and it is the biggest contributor to the cost premium of GHPs compared with conventional HVAC systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Modeling, Testing, and Analysis of Volvo Truck Tractor Cabins (Final Report)

Annual fuel use for sleeper cab truck rest period idling is estimated at 667 million gallons in the United States, or 6.8% of long-haul truck fuel use. Truck idling during a rest period represents zero freight efficiency and is largely done to supply accessory power for climate conditioning of the cab. This project aimed to reduce heating, ventilating, and air conditioning (HVAC) loads and resulting fuel use from rest period idling by using efficient long-haul truck thermal management systems while maintaining occupant comfort. Enhancing the thermal performance of cab/sleepers will enable smaller, lighter, and more cost-effective idle reduction solutions. In addition, if the fuel savings provide a one- to three-year payback period, fleet owners will be economically motivated to incorporate them. This project evaluated several promising candidate technologies through experimentation and modeling to determine their effectiveness in reducing rest period HVAC loads. Load reduction strategies were grouped into the focus areas of solar envelope, occupant environment, conductive pathways, and efficient equipment. Technologies in each of these focus areas were investigated. The most promising of these technologies were then combined with the goal of exceeding a 30% reduction in HVAC loads. These technologies included 'ultra-white' paint, advanced insulation, and advanced curtain design. This project showed more than a 35.7% reduction in rest period idle air conditioning loads using thermal load reduction technologies. Overall heat transfer coefficient testing during cab heating, showed a 43% reduction in heating load using this technology package.

30 DIRECT ENERGY CONVERSION↗

Addressing Food Insecurity on the Navajo Reservation Through Sustainable Greenhouses

Navajo (Diné) tribal members experience alarming rates of diabetes and food insecurity on the reservation. Increasing involvement with food production through gardening is a crucial step to rebuilding Diné food systems and improving the health of Navajos. The main challenges are drought, lack of available land, limited food production knowledge, and large up-front costs. However, implementing community-based gardens would help alleviate land space issues, leverage community knowledge, and shift financial responsibility to local community level or chapter level. Greenhouses are advantageous because they reduce water consumption and allow for year-round production, but require energy intensive heating, ventilation, and air conditioning (HVAC) systems. Therefore, the purpose of this paper is to compare a propane heating and evaporative cooling HVAC system to a ground source heat pump (GSHP). Using EnergyPlus to simulate annual energy loads, this paper compares the financial feasibility and environmental impact of each system. The operating cost of GSHPs was found to be 57% — 72% less than traditional HVAC systems based on location and fuel prices. Additionally, GSHPs required 72% — 90% less water and emitted 35% — 69% less carbon dioxide annually. Given the large up-front cost of GSHPs, conservative estimates showed payback periods from 5.2 — 10.8 years when using renewable energy grants. A life cycle cost analysis over 20 years showed greenhouses with GSHPs could cost $1,272 — $1,605 per year or 27% — 44% less than traditional HVAC systems. Tax revenue for chapters showed that funding is available to carry out such projects. Food produced using GSHP systems was found to cost $2.26 — $2.30 per daily serving of fruit and vegetables, which is competitive with grocery store prices. More importantly, greenhouses equipped with GSHPs present a compelling case because they cost less to operate and are more environmentally friendly than traditional HVAC systems. Future work should focus on adding a photovoltaic (PV) and battery storage system, which would completely eliminate HVAC water consumption and carbon dioxide emissions.

42 ENGINEERING↗

Efficiency-Optimized Dual Fuel Engine with In-Cylinder Gasoline/CNG Blending

The objective of the proposed project is to demonstrate targeted blending of gasoline and natural gas as a means to reduce petroleum consumption of light-duty spark-ignition engine vehicles by at least 50%. This goal will be achieved through petroleum displacement with natural gas (NG) combined with a relative engine efficiency improvement in excess of 10% while meeting retrofitability requirements with an anticipated payback period of less than 36 months. Further through NG direct injection (DI) a 10% improvement in power density over the PFI baseline will be demonstrated. The proposed project employs a sound R&D approach and combines experimental work with state-of-the-art computational modeling to be able to demonstrate the ambitious project goals. The project spans a 30 month period and is divided in 3 phases with the initial phase focused on experimental characterization of the gaseous jet structure of the high-pressure NG DI injector which is used to validate the 3D-CFD simulation tool. The phase also includes an experimental demonstration of the fundamental feasibility of the proposed dual-fuel approach on an automotive single-cylinder research engine. The scope of the second phase includes optimization of the combustion system by means of virtual design combined with 3D-CFD analysis. The resulting optimized combustion system will be built and experimentally evaluated by the end of the 12 month period. The third and final phase expands the scope by integrating the engine results in a vehicle level simulation tool with the objective of developing an optimized engine control strategy that maximizes the efficiency benefits attainable with the limited on-board NG supplies. A detailed cost analysis to verify that the 36 month amortization period requirement is met will conclude the proposed effort.

42 ENGINEERING↗

Design and Characterization of High Thermal Conductivity Pipes from Roll-to- Roll Processed Hybrid Copper-Polymer Strips for Waste Heat Recovery

Metal based heat exchangers targeting low temperature (<150°C) waste heat recovery (WHR) face high maintenance and material costs [1] that result in long payback periods (>1 year). Low-cost polymer pipes suffer from poor thermal conductivity (~0.2 W/m.K), and thus a low overall heat transfer coefficient. Previous reports demonstrated thermal conductivity enhancement in polymers through systematic molecular alignment [2, 3, 4], or by metal micro-particle inclusions [5]. However, these approaches suffer from scalability issues for WHR heat exchangers in terms of cost [1, 3], and thermomechanical considerations [6, 7]. In this work, we propose hybrid metal-polymer strips that are strategically designed to enhance thermal conductivity by cladding copper around polymer strips. The polymer strips with copper-clad edges are wound helically to form the pipes for a heat exchanger. Through numerical simulations, we optimize the copper-polymer strip layouts to achieve high wall thermal conductivity (k > 1 W/m.K) and also have low volume fraction of copper (<70%) for the composite pipes. In copper-polymer composite heat exchangers, the bottlenecks for heat transfer are the thermal interfacial resistances of copper-copper and copper-polymer joints. We experimentally measured interfacial resistances to be ~1x10 -5 K.m 2 /W and ~4x10 -5 K.m 2 /W for copper-copper and copper-polymer joints, respectively. Using the measured interfacial resistances, we further optimized the design of the hybrid pipes to find high thermal conductivity (> 1 W/m.K) designs. We predict up to ~20 % enhancement in overall heat transfer relative to an all polymer (k = 0.2 W/m.K) heat exchanger system. Using a cohesive zone modelling (CZM) for predicting delamination at the weld joints, we find that our hybrid pipes can have operating internal pressures > 200 psi. The optimized designs of hybrid metal-polymer pipes provide a scalable and cost- effective means for harvesting waste heat from low temperature sources. Thekdi, A., and Nimbalkar, S. Oak Ridge National Lab (2014). Shen, Sheng, et al. Nature nanotechnology 5.4 (2010). Xu, Yanfei, et al. Science advances 4.3 (2018). Smith et al. ACS nano, 9(2), (2015). Sofian, N.M., et al., Journal of Thermoplastic Composite Materials (2001). Aymonier et al. Chemistry of Materials, 15(25), (2003). Tavman, I.H., Journal of Applied Polymer Science, 62(12), (1996).

C Rajagopal, Manjunath↗

Life cycle cost analysis comparing redesigned CCHP to existing heat pump systems for cities in cold climates

This report indicates that the project progress has met the Go criterion, i.e. demonstrating favorable results of life cycle cost assessment for the redesigned CCHPs. Considering the market price of a baseline heat pump, and required improvements in heat exchangers, fans and an electronic expansion valve of the CCHPs, we estimated that the CCHP using a 3-stage scroll compressor will incur with a cost increment of $\$386$ per rated cooling tonnage, and the CCHP using tandem compressors will increase by $\$770$. Based on the energy savings of the CCHPs, simulated by EnergyPlus, the two CCHPs achieve payback periods less than 4 years among all the cold climate cities. Within a typical heat pump life cycle of 20 years, the CCHPs can achieve cost savings around $\$2000$ per rated cooling tonnage, and the savings are even higher for the extremely cold cities like Duluth and Fairbanks.