Least-cost Optimal Distribution Grid Expansion (LODGE) v1

LODGE finds the least-cost portfolio of traditional distribution system upgrades to integrate new loads and behind-the-meter DERs in combination with advanced non-wire alternative (NWA) planning solutions, such as utility-owned storage and distributed PV. Working with a set of least-cost solutions per feeder/substation allows us to benchmark and compare techno-economic performance of different traditional and NWA planning solutions. An important aspect of the LODGE model is that it includes power flow operation constraints. This means that the least-cost planning solutions delivered by LODGE are technically feasible. Available projects in LODGE portfolio include: 1) feeder reconductoring; 2) transformers upgrades; 3) non-wire alternatives, such as strategic siting and sizing of storage and distributed PV; 4) voltage regulators.

Heleno, Miguel↗

Flexible dynamic boundary microgrid operation considering network and load unbalances

Flexible microgrids with dynamic boundaries have recently been introduced in the literature. With the ability to reconfigure the topology of the microgrids dynamically through remotely controlled switches, flexible microgrids with dynamic boundaries can further improve the resiliency and energy efficiency of microgrids with distributed energy resources (DERs). This paper focuses on the optimal operation considering one of the predominant characteristics of microgrids and distribution systems – unbalanced networks and loads. In existing literature, balanced modeling of microgrids is more common due to its attractive simplicity. The three-phase power unbalance has not been considered as a constraint on the generation units in a microgrid. Further, negative sequence constraints have also been neglected. In this article, we propose a set of constraints that is specifically related to the capabilities of inverter interfaced resources to supply unbalanced current/power when the microgrid is islanded from the main distribution grid. We incorporate the new set of constraints into two optimization formulations leveraging two convex relaxations of the three-phase power flow equations: mixed-integer linear programming (MILP) and mixed-integer semidefinite programming (MISDP) that optimize the dispatch of controllable switches and DERs in the microgrid. The algorithms are then extended to networked microgrids with grid-forming sources. We test the algorithms on a realistic community microgrid model in Puerto Rico as well as standardized IEEE distribution test feeders. The testing results demonstrate the performance of the proposed algorithms. The MILP is fast and scalable, and the MISDP enforces the negative sequence voltage constraints.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-driven Minimum Entropy Control for Stochastic Nonlinear Systems using the Cumulant-Generating Function

Here, we present a novel minimum entropy control algorithm for a class of stochastic nonlinear systems subjected to non-Gaussian noises. The entropy control can be considered as an optimization problem for the system randomness attenuation, but the mean value has to be considered separately. To overcome this disadvantage, a new representation of the system stochastic properties was given using the cumulant-generating function based on the moment-generating function, in which the mean value and the entropy was reflected by the shape of the cumulant-generating function. Based on the samples of the system output and control input, a time-variant linear model was identified, and the minimum entropy optimization was transformed to system stabilization. Then, an optimal control strategy was developed to achieve the randomness attenuation, and the boundedness of the controlled system output was analyzed. The effectiveness of the presented control algorithm was demonstrated by a numerical example. In this paper, a data-driven minimum entropy design is presented without pre-knowledge of the system model; entropy optimization is achieved by the system stabilization approach in which the stochastic distribution control and minimum entropy are unified using the same identified structure; and a potential framework is obtained since all the existing system stabilization methods can be adopted to achieve the minimum entropy objective.

42 ENGINEERING↗

Multi-Timescale Optimal Operation Framework for Integrated Economic and Reliability Analysis of Hybrid Power Plants

This paper introduces a hierarchical modeling framework for hybrid power plants (HPP) to facilitate the operation of HPP in power systems similar to conventional generators (Congens) in the integrated multi-timescale optimal operation framework. To consider the uncertainties of HPP renewable power in the day-ahead scheduling, distributionally robust optimization (DRO) is used. To ensure that the state-of-charge (SOC) of energy storage systems in HPPs aligns closely with the planned value for long-term reliability, real-time SOC management is incorporated. In addition, an adjustable real-time control is designed for the robust delivery of HPP real-time services. Case studies performed on a revised IEEE 39-bus system demonstrate the effectiveness of the proposed framework for HPP operation. Simulation results highlight that the proposed framework not only can help operators schedule HPP similar to Congens in varying weather conditions but can also maintain the frequency reliability of the system.

frequency stability↗

Resilient Design of Continuous-time Distributed Optimization Algorithm in the Presence of Cyber-attacks

This paper presents a continuous-time resilient distributed optimization algorithm based on competitive interaction design method on connected graphs in the presence of adversaries. Here, the competitive interaction method allows us to design a network that protects the multi-agent systems from adversaries without requiring high network connectivity. In addition, the proposed algorithm does not require the global information about the number of adversaries. First, we show that the proposed distributed algorithm solves the resilient distributed optimization problem with no attack on the communication links. Second, we show that the proposed continuous-time distributed optimization algorithm on connected graphs converges to the small neighborhood of the optimal solution in the presence of cyber-attacks onto the communication channel. Simulations are presented to illustrate our theoretical results.

97 MATHEMATICS AND COMPUTING↗

Steam Generator Model Design Parameter Sensitivity Study Using Advanced Optimization Tools

This study focuses on design parameter sensitivity studies pertaining to a steam generator (SG) model, using both Python and machine-learning tools. The SG model is a mathematical representation (including fluid flow and heat transfer equations/models/correlations) of a steam-generating unit in a pressurized water reactor (PWR)-type small modular reactor (SMR) system. Design studies involve changing the model’s input design parameters (e.g., temperature, pressure, mass flow rate) to observe the resulting effects on the output of the system (e.g., heat transfer coefficient [HTC], Nusselt number, heat transfer performance). Sensitivity studies analyze the degree to which system output and/or desired parameters (e.g., HTC or heat transfer performance) are sensitive to changes in input parameters. By using machine-learning tools such as the Risk Analysis Virtual Environment (RAVEN) developed at Idaho National Laboratory (INL), detailed design parametric sensitivity studies and model optimization were performed. Six input parameters—namely, the pressure, temperature, and mass flow rate for the inlet of the primary-side (hot fluid) and secondary-side (cold fluid) of the SG—were randomly perturbed via RAVEN’s Monte Carlo Sampler module, using uniform distributions (±1% relative changes). The analysis results give valuable insights into SG system performance and optimization, and provide justification for researching optimized sensor placement to effectively monitor and obtain experimental data.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Steam Generator Model Design Parameter Sensitivity Study Using Advanced Optimization Tools

This study focuses on design parameter sensitivity studies pertaining to a steam generator (SG) model, using both Python and machine-learning tools. The SG model is a mathematical representation (including fluid flow and heat transfer equations/models/correlations) of a steam-generating unit in a pressurized water reactor (PWR)-type small modular reactor (SMR) system. Design studies involve changing the model’s input design parameters (e.g., temperature, pressure, mass flow rate) to observe the resulting effects on the output of the system (e.g., heat transfer coefficient [HTC], Nusselt number, heat transfer performance). Sensitivity studies analyze the degree to which system output and/or desired parameters (e.g., HTC or heat transfer performance) are sensitive to changes in input parameters. By using machine-learning tools such as the Risk Analysis Virtual Environment (RAVEN) developed at Idaho National Laboratory (INL), detailed design parametric sensitivity studies and model optimization were performed. Six input parameters—namely, the pressure, temperature, and mass flow rate for the inlet of the primary-side (hot fluid) and secondary-side (cold fluid) of the SG—were randomly perturbed via RAVEN’s Monte Carlo Sampler module, using uniform distributions (±1% relative changes). The analysis results give valuable insights into SG system performance and optimization, and provide justification for researching optimized sensor placement to effectively monitor and obtain experimental data.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Grid Optimization Competition on Synthetic and Industrial Power Systems

This paper summarizes a grid optimization (GO) competition effort in the United States to find the best solution strategies for up to interconnect-scale power system networks with around 32,000 buses. The optimization problem is a mixedinteger, non-convex non-linear problem, (MINLP) and includes discrete variables such as unit commitment and line switching, control settings (transformer taps and phase shifters with impedance correction tables), and bus shunts. The case study includes six actual industry grids as well as 16 realistic synthetic grids created by three different dataset teams. The winners are selected and ranked based on scoring criteria, which consider the solution quality (such as objective functions) within time limits. Nine winner teams are selected from 26 competitor teams. The results achieved by different teams are described and the performance of different algorithms on synthetic grids and actual industry grids are compared and analyzed.

mixed-integer non-linear programming↗

A Machine Learning-Based Method to Estimate Transformer Primary-Side Voltages with Limited Customer-Side AMI Measurements

Distribution control applications such as volt/var optimization, network reconfiguration, and distribution automation require accurate knowledge of the distribution system state. The lack of sufficient sensors on the primary side of distribution networks often limits the accuracy of the control decisions by these applications. The deployment of advanced metering infrastructure (AMI) provides utilities an opportunity to translate the AMI data on the secondary onto the primary so that it can be used as pseudo-measurements to augment the limited existing measurements on the primary. This paper develops a machine learning based approach for estimating service transformer primary-side voltages by using limited secondary-side AMI measurement. The machine learning model is developed by using random forest algorithm. The estimated primary-side voltages can be used by utilities as pseudo-measurements for distribution control applications. The detailed secondary model topology, which is an essential input data for many existing algorithms, is not required for the proposed method. The performance of the proposed method is validated by using AMI measurements from the field and an actual distribution feeder model of San Diego Gas & Electric Company.

advanced metering infrastructure↗

Networked Microgrids Optimization

This project is mainly about the operation optimization of three networked microgrids (MG), including centralized optimization and distributed optimization. The alternating direction method of multipliers (ADMM) algorithm is used for distributed optimization. In the distribution network considered here, there is a Distribution Management system (DMS) as the system coordinator and several networked microgrids. In grid-connected mode, power could be imported or exported at the distribution substation bus according to the utility rate, and the exchanged power at point of common coupling (PCC) of any microgrid has a limitation. In islanded mode, the power imports/exports at the distribution substation are zero. In both grid-connected and islanded mode, the distribution substation is taken as a slack bus with fixed voltage magnitude.

Chen, Yang [Oak Ridge National Laboratory (ORNL), ↗

A Machine Learning-Based Method to Estimate Transformer Primary-Side Voltages with Limited Customer-Side AMI Measurements

Distribution control applications such as volt/var optimization, network reconfiguration, and distribution automation require accurate knowledge of the distribution system state. The lack of sufficient sensors on the primary side of distribution networks often limits the accuracy of the control decisions by these applications. The deployment of advanced metering infrastructure (AMI) provides utilities an opportunity to translate the AMI data on the secondary onto the primary so that it can be used as pseudo-measurements to augment the limited existing measurements on the primary. This paper develops an approach for estimating service transformer primary-side voltages by using limited secondary-side AMI measurements. The estimated primary-side voltages can be used by utilities as pseudo-measurements for distribution control applications. The detailed secondary model topology, which is an essential input data for many existing algorithms, is not required for the proposed method. The performance of the proposed method is validated by using AMI measurements from the field and an actual distribution feeder model of San Diego Gas & Electric Company.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

A Machine Learning-Based Method to Estimate Transformer Primary-Side Voltages with Limited Customer-Side AMI Measurements: Preprint

Distribution control applications such as volt/var optimization, network reconfiguration, and distribution automation require accurate knowledge of the distribution system state. The lack of sufficient sensors on the primary side of distribution networks often limits the accuracy of the control decisions by these applications. The deployment of advanced metering infrastructure (AMI) provides utilities an opportunity to translate the AMI data on the secondary onto the primary so that it can be used as pseudo-measurements to augment the limited existing measurements on the primary. This paper develops an approach for estimating service transformer primary-side voltages by using limited secondary-side AMI measurements. The estimated primary-side voltages can be used by utilities as pseudo-measurements for distribution control applications. The detailed secondary model topology, which is an essential input data for many existing algorithms, is not required for the proposed method. The performance of the proposed method is validated by using AMI measurements from the field and an actual distribution feeder model of San Diego Gas & Electric Company.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Managing Power Systems-Induced Wildfire Risks Using Optimal Scheduled Shutoffs: Preprint

The growing demands for electricity and the increase in extreme weather conditions are putting unprecedented pressure on our electrical grids. Oftentimes, this pressure leads to electrical components failures which might ignite wildfires. This work develops a novel model to balance the reliability of power networks operations and risks of wildfires ignition by optimizing the operational schedule of power transmission networks considering time-varying risk measures that consider exogenous and operational factors. Energy storage systems are considered to deliver power during peak wildfire hours and enable temporal load shifting. The problem is formulated as a mixed-integer linear program that maximizes a weighted sum of the served power demand and the reduction in grid-induced wildfires risk. The results demonstrate the ability of the model to reduce wildfires risks significantly without considerable load shedding.

energy scheduling↗

Evaluating the Impact of Managed EV Charging for Reliable Operation of Bulk Power Systems with High Non-Dispatchable Generation

The growth of electric vehicles (EVs) and variable-generation (VG) sources introduces new challenges for power-system operations. This study introduces a modeling framework and evaluates five EV charging strategies under projected 2040 grid conditions in the Evergy service territory with high non-dispatchable generation. Using realistic EV behavior and generation models, their impacts on system peak demand, ramp rate, and reserve capacity are evaluated. Results show that only the peak-avoidance strategy effectively reduces system peak demand, while decentralized strategies-particularly cost based dynamic charging-can exacerbate peaks due to synchronized user behavior. However, ramp-rate minimization strategy significantly reduce the stress on dispatchable generation achieving the lowest maximum absolute ramp rate (MARR) (56.81 MW) and lowest reserve requirement (2.39 GW). In contrast, unmanaged and TOU random strategies increase the stress on dispatchable generation sources with increased MARR and reserve requirements. These findings highlight the importance of coordinated, system-aware managed charging strategies to ensure reliable and affordable grid operation in the presence of EVs and VG sources.

14 - SOLAR ENERGY↗

Distribution System State Estimation With High Penetration of Demand Response Enabled Loads

Demand-side operations incentivize utility customers to take part in various grid services. A demand response enabled load (DREL) is a flexible grid asset that schedules electricity consumption in response to a time-of-use (TOU) energy price. Consequently, its energy profile differs from that of a conventional load that is insensitive to price. This difference may cause new challenges for distribution system state estimation (DSSE). It is well known that DSSE often needs to use pseudo-measurements based on historic load profiles to increase system observability. However, historic profiles of conventional loads are not representative of DREL behaviors. Additionally, the inaccuracy impacts DSSE results and other DSSE-dependent operations. In this paper, we propose an online pseudo-measurement generation approach for DSSE with DRELs. We formulate an optimization model to represent DRELs self-adjusting actions. Sampling-based stochastic optimization techniques are proposed to account for uncertainties in DRELs. A set of representative DREL behavior data corresponding to the samples are used to characterize DREL pseudo-measurements. Case studies with modified IEEE 123-bus test system verify the validity of the proposed work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluating Manual Sampling Locations for Regulatory and Emergency Response

Drinking water systems commonly use manual or grab sampling to monitor water quality, identify or confirm issues, and verify that corrective or emergency response actions have been effective. In this paper, the effectiveness of regulatory sampling locations for emergency response is explored. An optimization formulation based on the literature was used to identify manual sampling locations to maximize overall nodal coverage of the system. Results showed that sampling locations could be effective in confirming incidents for which they were not designed. When evaluating sampling locations optimized for emergency response against regulatory scenarios, the average performance was reduced by 3%–4%, while using optimized regulatory sampling locations for emergency response reduced performance by 7%–10%. Secondary constraints were also included in the formulation to ensure geographical and water age diversity with minimal impact on the performance. This work highlighted that regulatory sampling locations provide value in responding to an emergency for these networks.

54 ENVIRONMENTAL SCIENCES↗