In-Building Fusion of Deep Data from Digital Twins and their Concomitant Control Schemes Final Technical Report
Explore the source record for details and available documents.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Explore the source record for details and available documents.
Apartment temperature data have been collected from the archives of companies that provide energy management systems (EMS) to multifamily buildings in the Northeast U.S. The data have been analyzed from more than 100 apartments in eighteen buildings where EMS systems were already installed to quantify the degree of overheating. This research attempts to answer the question, 'What is the magnitude of apartment overheating in multifamily buildings with central hot water or steam heat?' This report provides valuable information to researchers, utility program managers and building owners interested in controlling heating energy waste and improving resident comfort. Apartment temperature data were analyzed for deviation from a 70 degrees F desired setpoint and for variation by heating system type, apartment floor level and ambient conditions. The data shows that overheating is significant in these multifamily buildings with both hot water and steam heating systems.
This project advances the understanding of how roof solar PV systems and battery energy storage systems (BESS) can be effectively deployed in multifamily residential buildings, a sector that has historically faced barriers due to misaligned incentives between landlords and tenants. By leveraging high-resolution building stock data and simulation tools, the research demonstrates how energy consumption patterns vary across building types, climates, and occupant characteristics, and how these variations influence the optimal sizing and operation of distributed energy resources. A key contribution is the development of a publicly accessible, web-based tool named RESIDE (Residential Energy Systems & Infrastructure Data Evaluation) that allows users to explore building energy use and evaluate solar and battery configurations without requiring specialized expertise. This significantly lowers the barrier to entry for stakeholders such as property owners, utilities, and policymakers. From a technical perspective, the project shows that integrating rooftop solar PV with battery energy storage can substantially reduce electricity costs and peak demand through strategies such as energy arbitrage and peak shaving. The modeling framework incorporates real-world constraints, including time-of-use electricity pricing and battery degradation, providing realistic and actionable insights. Economically, the results indicate that properly sized systems can deliver meaningful cost savings, improving the feasibility of energy investments in multifamily housing. More broadly, the project benefits the public by supporting the transition to affordable and reliable energy, particularly in rental multifamily housing where adoption has traditionally lagged.
The Building Performance Database (BPD) is the largest publicly-available source of measured energy performance data for buildings in the United States. It contains information about the building's energy use, location, and physical and operational characteristics. The BPD can be used by building owners, operators, architects and engineers to compare a building's energy efficiency against customized peer groups, identify energy efficiency opportunities, and set energy efficiency targets. It can also be used by energy efficiency program implementers and policymakers to analyze energy efficiency features and trends in the building stock. The BPD compiles data from various data sources, converts it into a standard format, cleanses and quality checks the data, and provides users with access to the data in a way that maintains anonymity for data providers. This software is the database and the Application Programming Interface (API). Users can utilize the BPD's data to develop their own applications using the API. Version 2.1 included a major update for multiple years of data and refactoring of code for faster queries.
This document summarizes the findings of a Pacific Northwest National Laboratory analysis on how whole-building energy data aggregation thresholds statistically affect customer privacy.
VOLTTRON ™ is an open-source platform for distributed sensing and control. The platform provides services for collecting and storing data from buildings and devices and provides an environment for developing applications which interact with that data. The platform allows developers to build out their use cases by utilizing these frameworks and integrating new capabilities. To simplify the deployment of systems built on VOLTTRON, a new way of organizing the codebase is being explored. This document details these efforts through a new code repository layout for the VOLTTRON platform and services, and how this new layout provides targeted deployments using standard python deployment packages (wheels). In addition, this paper will discuss the development of third-party agents and how they can be integrated within the VOLTTRON ecosystem. Finally, we will discuss core platform development and direction for the modularized version of VOLTTRON.
Graph-based representations of building metadata using ontologies like Brick are vital for smart building applications, but querying them remains a challenge for practitioners. Knowledge Graph Question Answering (KGQA) systems, meant to retrieve answers from natural language questions, traditionally require large-scale training data, making them ill-suited for the specialized and data-scarce building domain. The advent of Large Language Models (LLMs) offers a paradigm shift, enabling zero-shot natural language querying without building/domain-specific training. Yet, there is no standardized benchmark for building-specific KGQA which can guide and validate research in this area. To address this gap, our work makes three primary contributions. First, we introduce the BuildingQA Benchmark Dataset, constructed through a multi-stage process of collecting practitioner data, augmenting it with LLMs for linguistic diversity, and curating a final set of 188 questions across 4 buildings. Second, we characterize the benchmark's complexity and ambiguity, introducing a novel method to quantify its "lexical gap" and providing a four-stage diagnostic framework for analyzing how systems fail. Third, we benchmark zero-shot LLM-powered KGQA systems to establish baseline performance and analyze their failure modes. Our evaluation reveals that top-performing systems achieve a maximum F1 score of only 0.38. This result does not indicate a failure of these powerful systems, but rather underscores the unique challenges posed by our benchmark. It demonstrates a critical performance gap, showing that current methods successful on general KGs struggle with the specific lexical and structural nuances of the building domain. BuildingQA1 thus provides the benchmark dataset and foundational analysis needed to drive the development of novel, domain-aware methods required to unlock the use of semantic data in buildings.
The terra-populus library is designed for use by the LandScan HD technical team, offering a streamlined set of tools for generating and updating LandScan HD datasets from foundational building-level data, referred to as 'molecules,' provided by the building-level attribution team. This document serves as the primary technical documentation for terra-populus. Version 0.1 of the library includes the core modeling components necessary for LandScan HD production. It enables the generation of the LandScan HD Baseline dataset as well as corresponding confidence measures for the occupancy rates used. Parameters have been included for incorporating damaged building indicators and changes in population, to faciliate the creation of rapid updates for LandScan HD. Future iterations of terra-populus will introduce tools for creating a confidence index, and quantifying and propagating uncertainty, facilitating the creation of probabilistic LandScan HD outputs. This report provides an overview of the tools available in the library and the corresponding code implementations. One of the key advancements implemented in terra-populus is a redefinition of the atomic modeling unit for LandScan HD. Traditionally, the LandScan HD vector analytical framework has generated population estimates at the building sub-component (molecule) level. However, terra-populus adopts a building-level modeling approach. This shift is an operational decision aimed at aligning LandScan HD outputs with confidence measures, which are computed and validated at the building level (confidence measures are not included in this version of terra-populus, aside from those associated with the occupancy rates). Additional advancements to the LandScan HD modeling, as implemented by terra-populus, include a minimum population value parameter and an auto assignment of building floor counts. The population minimum value was implemented to prevent buildings and subsequent LandScan HD pixels that contained small values that may not rasterize in production. An 'auto' value has been included as a method for dealing with buildings lacking floor count information, where it is the average floor count of all other buildings with a residential building use type tag. The logic behind this is to remain consistent with the current logic employed for dealing with building use type null instances, where a null use type is defaulted to residential since it is the most common building type. The auto logic is intended to apply the most common building floor count of the most common type of buildings. The tools provided in terra-populus represent a significant step forward in improving the efficiency, reproducibility, and transparency of the LandScan HD modeling process. As the library evolves, it will continue to serve as a foundational resource for high-resolution population modeling.
Modeling energy consumption is critical for energy-efficient utilization of the electric appliances in a building, smart grid programs (like demand-response), and many other smart home applications. State-of-the-art energy modeling techniques either rely on theoretical models, or extensive instrumentation of the building envelope to gather ``big" data to train a deep neural network. While theoretical models are often limited by their estimation accuracy, it is not always feasible to gather a significant amount of field data. In this paper, we explore transfer learning-based strategies to train much more accurate model for energy estimation when using a sparse field data. We transferred knowledge, in the form of data and parameters, from the simulation framework to the field data. We evaluated the efficacy of our approach on field data collected from six commercial buildings and our results indicate that transfer learning-based models trained over one month data can perform comparative (and in some cases better) than the state-of-the-art machine learning and deep learning solutions.
Variable air volume (VAV) and variable refrigerant flow (VRF) systems are widely used in office buildings. This study investigated VAV and VRF systems in five typical office buildings in China, and compared their cooling energy use. Site survey and field measurements were conducted to collect the data of building characteristics and operation. Measured cooling electricity use was collected from sub-metering in the five buildings. The sub-metering data normalized by climate and operating hours indicated that the cooling energy consumed by VRF systems was up to 70% lower than that consumed by VAV systems. This was mainly because of the different operation modes of both system types that led to significantly fewer operating hours for the VRF systems. Building simulations were used to quantify the impact of operation modes of VRF and VAV systems on cooling loads. A prototype office building in China was used as the model. The simulation results showed that the VRF operation mode required much lower cooling load when compared to the VAV operation mode. For example, the cooling loads decreased by 42% in Hong Kong and 53% in Qingdao. Key findings include the following: the VRF systems operated in the part-time-part-space mode enabling occupants to turn on the air-conditioning only when needed and when the spaces were occupied. However, the VAV systems operated in the full-time-full-space mode limiting occupants’ control of operation. These findings provide insights into VRF systems operation and controls as well as their energy performance, which could help guide HVAC designers on system selection and building operators or facility managers on system operations to achieve low- or zero-net energy buildings.
Modern buildings are complex energy systems that must be controlled for energy efficiency. The Research Support Facility (RSF) at the National Renewable Energy Laboratory (NREL) has hundreds of controllers -- computers that communicate with the building's various control systems -- to control the building based on tens of thousands of variables and sensor points. These control strategies were designed for the RSF's systems to efficiently support research activities. Many events that affect energy use cannot be reliably predicted, but certain decisions (such as control strategies) must be made ahead of time. NREL researchers modeled the RSF systems to predict how they might perform. They then monitor these systems to understand how they are actually performing and reacting to the dynamic conditions of weather, occupancy, and maintenance. This submission includes the Measured Energy Data from the RSF Systems Model. The data includes a csv with measured data from NREL's Research and Support Facility (RSF) for 2011. The dataset contains hourly data for: Total Cooling (kW)- Total Heating (kW)- Total Mechanical (kW)- Total Lighting (kW)- Total Plug Loads (kW)- Total Data Center (kW)- Total Building (kW)- PV (kW)- Building Net (kW). Energy Model data and Weather data related to the RSF Systems Model can be found in the "Related Datasets" section of this submission.
We present an integrated camera motion design and path generation system for building volume data animations. Creating animations is an essential task in presenting complex scientific visualizations. Existing visualization systems use an established animation function based on keyframes selected by the user. This approach is limited in providing the optimal in-between views of the data. Alternatively, computer graphics and virtual reality camera motion planning is frequently focused on collision free movement in a virtual walkthrough. For semi-transparent, fuzzy, or blobby volume data the collision free objective becomes insufficient. Here, we provide a set of essential criteria focused on computing camera paths to establish effective animations of volume data. Our dynamic multi-criteria solver coupled with a force-directed routing algorithm enables rapid generation of camera paths. Once users review the resulting animation and evaluate the camera motion, they are able to determine how each criterion impacts path generation. In this paper, we demonstrate how incorporating this animation approach with an interactive volume visualization system reduces the effort in creating context-aware and coherent animations. This frees the user to focus on visualization tasks with the objective of gaining additional insight from the volume data.
Buildings consume more than 40% of primary energy in the U.S. Malfunctioning sensors, components, and control systems, as well as degrading components in Heating, Ventilating and Air-conditioning (HVAC) and lighting systems are main reasons for energy waste and unsatisfactory indoor environment. Field studies have shown that an energy saving of 5-30% of total building energy consumption and improved indoor air quality can be achieved by simply applying automated fault detection and diagnosis (AFDD), followed by corrections even if these are not done in real time. Extensive research has been made on the development of component level AFDD tools in the past two decades. However, in recent years, the development of method for a whole building level AFDD has received much attention. Here, a whole building fault refers to a fault happening in one subsystem but impact on more than one subsystems, or has a significant impact on building performances, such as building’s energy consumption. Existing component level AFDD tools could fail to detect or give false alarm for faults that trigger abnormalities in multiple subsystems. Isolating such whole building faults, which have impacts on multiple subsystems, is also challenging by simply using component based AFDD solutions. On the other hand, it might be more cost-effective for medium- or small-sized commercial buildings that have subsystems (e.g. primary cooling subsystem, air loop subsystem, heating subsystem, lighting subsystem, etc.) to install one whole building level AFDD tool, rather than many component level AFDD tools, to focus on significant faults. The focus of this project is firstly to provide training opportunities in building AFDD research area for undergraduate students and to develop a workforce pipeline in building sciences. The objective of the proposed research activities is to develop cost-effective and scalable AFDD solutions for whole building level faults. The developed AFDD solution is VOLTTRONTM compatible to further increase its plug-n-play capacity and the market penetration. VOLTTRONTM is an open-source innovative distributed control and sensing software platform developed by the Pacific Northwest National Laboratory. A VOLTTRONTM compatible AFDD tool brings the benefits such as low-cost deployment, and better building to grid integration, etc. The performance of the developed whole building AFDD tools is evaluated using data collected from a mixed-use medium-sized university campus building. Another significant goal of this project is to engage undergraduate students in research activities and expose them to building control and AFDD fields. A demonstration building – Nesbitt Hall at Drexel University is identified for this study. This demonstration building has a typical HVAC system configuration, which includes a water-cooled chiller system, three variable air volume (VAV) air handling unit (AHU) systems, and a hydronic heating system. Faults, that are expected to have a whole building level impact, are artificially implemented in this demonstration building for three different seasons. Building data have been collected in this project, which include fault free building automation system (BAS) data and BAS data that contain system behaviors caused by artificially implemented and naturally occurred faults. These collected data are used to evaluate the developed whole building AFDD tools. A data-driven method, which includes a weather and schedule-based pattern matching (WPM) method and Feature based Principal Component Analysis (FPCA) method, is developed for whole building level fault detection. Parameter sensitivity tests, including snapshot window size, data sample searching pool size, etc., are implemented to evaluate the impacts of various WPM-FPCA parameters. A data-driven and expert knowledge/rule-based method using Bayesian Network (BN) and WPM is developed for whole building level fault diagnosis. The developed WPM-BN method, which includes a two-layer BN structure model and BN parameters, are either learned from baseline data or developed from expert knowledge. The developed whole building AFDD tools are evaluated using BAS data collected from the demonstration building. Using the evaluation data set, the WPM-FPCA fault detection method is evaluated under two different Principle Component (PC) retention rates, i.e., 0.65 retention rate and 0.95 retention rate. It is observed that when using 0.65 PC retention rate, the WPM-FPCA fault detection method achieves a 79% fault detection rate (this rate reaches to 85% when including the six make-up fault test cases discussed in the next bullet), while when using 0.95 PC retention rate, the WPM-FPCA fault detection method achieves 100% fault detection rate (this rate remains to be 100% when including the six make-up fault test cases). Under both PC retention rates, the WPM-FPCA fault detection method demonstrates 0% false alarm rates. Using the evaluation data set, the developed WPM-BN fault diagnosis method has successfully diagnosed thirteen (13) faults out of the fourteen (14) fault test cases. The one mis-diagnosed case exhibits fewer fault symptoms in different subsystems, when compared with other fault test cases. Overall speaking, the developed whole building AFDD solutions demonstrate satisfactory fault detection/diagnosis accuracy with very low false alarm rate. Lastly, a survey and market study has been performed to understand the existing AFDD market, including its gaps and needs.
Overview and update of Livewire, a platform for sharing, preserving, and discovering energy efficiency and mobility research data funded by VTO and maintained by experts leveraging experience building successful data platforms at NLR, INL, and PNNL.
This fact sheet "Asheville, North Carolina: Reducing Electricity Demand through Building Programs & Policies" explains how the City of Asheville used data from the U.S. Department of Energy's Cities Leading through Energy Analysis and Planning (Cities-LEAP) and the State and Local Energy Data (SLED) programs to inform its city energy planning. It is one of ten fact sheets in the "City Energy: From Data to Decisions" series.
This protocol was written for the Department of Energy’s Federal Energy Management Program (FEMP) to be used by the public as a tool for assessing building cost and performance measurement. The primary audiences are sustainable design professionals, asset owners, building managers, and research professionals within the Federal sector. The protocol was developed based on the need for measured performance and cost data on sustainable design projects. Historically there has not been a significant driver in the public or private sector to quantify whole building performance in comparable terms. The deployment of sustainable design into the building sector has initiated many questions on the performance and operational cost of these buildings.
Developing location-specific district energy models is essential for understanding energy patterns and supporting efficient management and planning decisions. However, accurately characterizing these models remains challenging due to gaps in building characteristics and labor-intensive traditional modeling workflows. To address these challenges, we develop an AI-based framework that integrates top-down and bottom-up building energy data to automate urban energy model characterization. The framework trains multimodal deep learning models using heterogeneous ResStockTM datasets to infer missing building characteristics from varying levels of known information and generate simulation-ready inputs for district-scale energy modeling. It also employs a conditioning-based injection approach to generate ”what-if” scenarios, enabling users to explore retrofit, efficiency, and technology-upgrade pathways. Integrated within URBANoptTM, a bottom-up district energy modeling platform for simulating co-located buildings, the framework infers detailed building-level inputs required for bottom-up simulations. Both localized and generalized AI models are developed to learn relationships across categorical, numerical, and time-series data, enabling reconstruction of missing attributes and generation of targeted upgrade scenarios. We demonstrate this methodology on a residential neighborhood in Baltimore, MD, assessing internal consistency against ResStock reference data and URBANopt simulation, and comparing selected attributes against real-world building characteristics. Results show strong overall predictive accuracy in data completion and scenario generation, with localized and generalized models offering complementary trade-offs between precision and scalability. Overall, our automated framework streamlines energy modeling and provides a reliable framework for urban building energy characterization.
Commercial buildings consume significant amount of energy. Facility managers are increasingly grappling with the problem of reducing their buildings’ peak power, overall energy consumption and energy bills. In this paper, we first develop an optimization framework – based on a gray box model for zone thermal dynamics – to determine a pre-cooling strategy that simultaneously shifts the peak power to low energy tariff regimes, and reduces both the peak power and overall energy consumption by exploiting the flexibility in a building’s thermal comfort range. We then evaluate the efficacy of the pre-cooling optimization framework by applying it to building management system data, spanning several days, obtained from a large commercial building located in a tropical region of the world. The results from simulations show that optimal pre-cooling reduces peak power by over 50%, energy consumption by up to 30% and energy bills by up to 37%. Next, to enable ease of use of our framework, we also propose a shortest path based heuristic algorithmfor solving the optimization problemand show that it has comparable erformance with the optimal solution. Finally, we describe an application of the proposed optimization framework for developing countries to reduce the dependency on expensive fossil fuels, which are often used as a source for energy backup.We conclude by highlighting our real world deployment of the optimal pre-cooling framework via a software service on the cloud platform of a major provider. Our pre-cooling methodology, based on the gray box optimization framework, incurs no capital expense and relies on data readily available from a building management system, thus enabling facility managers to take informed decisions for improving the energy and cost footprints of their buildings