Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analytical Models of Frequency and Voltage in Large-Scale All-Inverter Power Systems

Low-order frequency response models for power systems have a decades-long history in optimization and control problems such as unit commitment, economic dispatch, and wide-area control. With a few exceptions, these models are built upon the Newtonian mechanics of synchronous generators, assuming that the frequency dynamics across a system are approximately homogeneous, and assume the dynamics of nodal voltages for most operating conditions are negligible, and thus are not directly computed at all buses. As a result, the use of system frequency models results in the systematic underestimation of frequency minimum nadir and maximum RoCoF, and provides no insight into the reactive power-voltage dynamics. This paper proposes a low-order model of both frequency and voltage response in grid-forming inverter-dominated power systems. The proposed model accounts for spatial-temporal variations in frequency and voltage behavior across a system and as a result, demonstrates the heterogeneity of frequency response in future renewable power systems. Electromagnetic transient (EMT) simulations are used to validate the utility, accuracy, and computational efficiency of these models, setting the basis for them to serve as fast, scalable alternatives to EMT simulation, especially when dealing with very large-scale systems, for both planning and operational studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.↗

Behavior of Single-Line-Ground Faults in Inverter-Based Resource Dominated Grids Explained

It has been observed by protection engineers that it is difficult for a protective relay to identify the faulted phase during a single-line-ground (SLG) fault in a power system with a high ingression of inverter-based resources (IBR) using currents (phase or sequence). Further studies using electromagnetic transient (EMT) simulation show that the initial operating conditions of the IBRs influence the response of phase currents during an SLG fault. In this letter, we conduct a quantitative analysis using sequence components. We find that the pre-fault condition determines the relative position of the current contributed by the grid versus that from the IBR, and further dictates which phase has the largest magnitude during an SLG condition. Finally, this finding is further verified by the EMT simulation results.

electromagnetic transient simulation↗

IEEE 123-Bus System A Matrix

System component matrix for IEEE 123 bus distribution system for dynamic simulations.

Sahu, Vibhuti [Oak Ridge National Laboratory] (ORC↗

Grid Resiliency with a 100% Renewable Microgrid

San Diego Gas & Electric Company (SDG&E) installed America’s first and largest utility-scale microgrid in Borrego Springs in 2013. The first generation Borrego Springs Microgrid utilized diesel generators to form and stabilize the microgrid island, with support from grid-scale batteries and local solar photovoltaic (PV) generation. In this project, SDG&E in partnership with National Renewable Energy Laboratory (NREL) demonstrated through modeling, simulation and utility field testing that blackstart and islanding of the microgrid can be led with 100% renewable, inverter based resources (IBRs), to help reduce community reliance on conventional generation resources. Through equipment upgrades, grid-forming island leader capability was transitioned to a battery IBR instead of the Borrego Springs Microgrid diesel generators. A new microgrid controller was integrated to the microgrid and programmed to control and manage multiple energy storage systems. Synchrophasor and other power quality data verified autonomous, high-speed response of the IBRs through blackstart, islanding, and load step testing. Results of project field evaluations provide distribution systems operators (DSO) with increased confidence that renewable, IBR can replace traditional generators to blackstart and island microgrids and rapidly establish stable island frequency with rapid changes in peak power demand. Importantly, the project validated the integration feasibility of a distributed energy resource management system (DERMS) controller that manages multiple grid-forming and grid-following IBRs, establishing a standard design interface to reduce the complexity of integrating new DERs in the future and supporting replication by the industry. As a result of learnings in this project, SDG&E has implemented the microgrid controller strategy at multiple other microgrid sites, thereby validating the replicability of the solution. Hardware-in-the-loop (HIL) simulations including power and controller HIL hardware — along with electromagnetic transient (EMT) simulations of Borrego Springs Microgrid —informed adjustments to inverter parameters and were important to characterize the performance of the IBRs in relevant operating conditions before deployment. The EMT and HIL simulations of islanding the entire community are important contributions in providing confidence in IBR performance prior to future islanding of the community in the field. High-fidelity EMT and/or HIL simulation of IBRs can de-risk field operations, and its relevance and importance as a tool is increasing as distribution grids and microgrids become more complex and dynamic with an increasing proportion of renewable generation, distributed energy storage, and two-way power and energy flows.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Fault Contribution of Grid-Following and Grid-Forming Inverters Considering Generic Inverter Controls and Ride-through Requirements

Gradual transformation of the synchronous generator (SG)-dominated power systems to inverter-based resource (IBR)-dominated power systems is bringing new challenges regarding power system protection. Increasing IBR’s penetration will reduce the reliability of protection coordination, originally developed for SG-dominated power systems, potentially leading to less accurate calculation or even mis-operation. Thus, new protection schemes compatible with IBR-dominated power systems should be established. Prior to establishing the protection schemes, research on the fault contribution of generic IBR models should be conducted considering interconnection requirements. This paper conducts fault current contribution analysis of generic grid-following (GFL) and grid-forming (GFM) inverters considering interconnection requirements using an electromagnetic transient (EMT) simulation tool. To do this, EMT-based generic GFL models have been developed with the ride-through requirements from IEEE-1547 standards. In addition, the major functions of the generic models are explained. Then, the fault current analysis was conducted using GFL and GFM inverters in a single-inverter-infinite-bus system and a modified IEEE 34-node system considering different grid, fault, inverter control parameters.

Kim, Jinho [BATTELLE (PACIFIC NW LAB)]↗

A Semi-Analytical Approach for State-Space Electromagnetic Transient Simulation

Here, this paper proposes a semi-analytical approach for efficient and accurate electromagnetic transient (EMT) simulation of a power grid. The approach first derives a high-order semi-analytical solution (SAS) of the grid’s state-space EMT model using the differential transformation (DT), and then evaluates the solution over enlarged, variable time steps to significantly accelerate the simulations while maintaining its high accuracy on detailed fast EMT dynamics. The approach also addresses switches during large time steps by using a limit violation detection algorithm with a binary search-enhanced quadratic interpolation. Case studies are conducted on EMT models of the IEEE 39-bus system and large-scale systems to demonstrate the merits of the new simulation approach against traditional numerical methods.

electromagnetic transient↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: Droop, Virtual Synchronous Machine (VSM), and dispatchable Virtual Oscillator Control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy, and with no explicit tuning of the solver, lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

electromagnetic transient simulation↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Dynamic Model of Back-to-Back Converter for System Level Phasor Simulation

The power system is expected to evolve rapidly with increasing deployment of power electronic interface and conditioning systems, microgrids, and hybrid AC/DC grids. Among power electronic systems, back-to-back (BTB) converters can be a powerful interface to integrate microgrids and networked microgrids. However, in system level dynamic simulations for synchronous machine dominated system with BTB converters, a detailed electromagnetic sinusoidal models is not warranted as these simulations are focused on electromechanical transients. This paper focus on developing a simple phasor model for back- to-back converters that can be easily integrated into powerflow solvers to facilitate large-scale power system simulations. The model is implemented using C++ language and integrated into GridLAB-D software as a potential new capability. The GridLAB-D phasor domain model is validated against the electromagnetic transient (EMT) simulation of the detailed switching model. Simulation results show that the phasor model successfully captures the dominant dynamics of the converters.

Mahmood, Hisham↗

Equivalent-Circuit Models for Grid-Forming Inverters under Unbalanced Steady-State Operating Conditions: Preprint

Positive- and negative-sequence equivalent-circuit models are put forth to capture the operation of grid-forming (GFM) inverters in unbalanced steady-state operating conditions acknowledging the impact of current limiting. The particular control architecture examined adopts droop control (for primary control), nested inner-current and outer-voltage control (in the stationary reference frame), and it is adaptable to two different types of current limiting (current-reference saturation and virtual-impedance limiting). We anticipate the proposed models to be of interest in modeling, analysis, and simulation of GFM inverters in unbalanced settings that may arise, e.g., in the face of faults. Validation of the equivalent-circuit models is pursued via comparison with full-order electromagnetic-transient (EMT) simulations for representative balanced and unbalanced faults.

equivalent-circuit models↗

Digital Filter Design for Point-on-Wave Sensors: Highlighting Frequency Response Limitations and Enhancing Grid Simulation Accuracy

Data is proving to be the backbone of today's and, more importantly, tomorrow's grid. As the system changes and introduces fast-acting devices like power electronics, overall observability tends to decrease from the utility point-of-view. This can be mitigated by adding more high-fidelity sensors onto the grid, although this incurs a cost. These sensors are never ideal, and each have unique frequency responses that may influence the data produced. This may, in turn, impact the protection and control of the power grid. This paper presents a methodology of representing these point-on-wave sensors digitally by estimating digital-filter representations of them, thereby introducing means of improving the sensor models used in electromagnetic-transient (EMT) simulations. This may help with identifying potential high-frequency, sensor-induced distortions, and system resonance compensation. Three commercial-grade medium-voltage point-on-wave sensors are utilized in a lab environment to obtain experimental frequency responses with a frequency sweep, and it is shown that both Infinite Impulse Response (IIR) and Finite Impulse Response (FIR) filter representations may approximate these responses with varying degrees of accuracy, though each has their own strengths and weaknesses. It is found that, in general, FIR estimation better approximates these sensors than IIR estimation does.

Wilson, Aaron [ORNL] (ORCID:0000000327331697)↗

Multiterminal High-Voltage dc Systems with Series-Parallel Valve Group-Based High-Voltage dc Substations

To transfer large amount of power over long distances, multiterminal direct current (MTdc) system based on bipole high-voltage direct current (HVdc) technology is a viable option. However, such system results in large dc transmission loss. The same can be reduced by increasing the dc voltage level. This paper introduces a new MTdc system architecture comprising of series (for increasing dc voltage level) and parallel (for increasing dc current capability) connected HVdc converters. The new architecture is compared with the bipole MTdc architecture in terms of equipment needed and dc transmission loss. The control modifications needed for the MTdc system are identified and the performance of the developed control is verified through electromagnetic transient (EMT) simulations.

Jaldanki, Sreenivasa↗

Testbed Demonstration of a Microgrid Building Block Prototype

With the adoption of ambitious climate action goals, the penetration level of distributed energy resources (DERs) is rapidly increasing. Microgrids are an efficient way to integrate these DERs, facilitating their operation and control. Additionally, microgrids enhance the overall resilience of the distribution system by serving critical loads both within and outside their boundaries. However, the need for substantial customized engineering leads to a high cost of development, installation and maintenance of microgrids. To address this challenge, Microgrid Building Blocks (MBB) are proposed to reduce the deployment cost of microgrids through modular, standardized design and implementation. This work presents a testbed demonstrating the integrated power conversion, control, and communication functionalities of an MBB. The testbed is formed by a real-time electromagnetic transient (EMT) simulation combined with a hardware and software prototype of MBB. The use cases supported by the MBB testbed are enumerated. The islanded operation, voltage regulation, and optimal dispatch capabilities of an MBB-based microgrid controller are validated through a case study.

Somda, Baza [Virginia Tech]↗

Assessing the Feasibility of Bordered Block Diagonal Reordering in Power System Matrices using Fully Convolutional Network

In electromagnetic transient (EMT) simulations for power systems and inverter-based resources (IBRs), the arrangement of states within the system's linear equations, represented by matrix A in Ax=b, is critical. The state ordering in matrix A can highlight distinct characteristics of the system's graph, and identifying an optimal state ordering is crucial for efficient computation. The choice of state ordering, however, is dependent on the solver used, as each solver may perform optimally with different matrix patterns. With a wide array of matrix reordering algorithms available, selecting the most suitable one becomes challenging without insights into the matrix's ideal configuration. To address this, the paper proposes a fully convolutional network (FCN) to evaluate the reordering potential of the A matrix into a bordered block diagonal (BBD) pattern, which is commonly observed in power system and IBR modeling. The FCN's assessment aims to streamline the solver's operation, which in turn could substantially reduce the computational time required to find a solution.

Xia, Qianxue↗

Transient Stability Analysis of Direct Droop-Controlled Grid-Forming Inverter with Current Clipping as Current Limiting Control

This paper investigates the transient stability of the direct droop-controlled grid-forming (GFM) inverter which employs the current clipping-based approach for overcurrent limitation. An equivalent circuit model of the direct-droop GFM inverter with current clipping is developed for this purpose. It is shown that during overcurrent conditions, the GFM inverter with current clipping acts as a voltage source with a virtual resistance behind the inverter filters. To compute the parameters of this virtual resistance an analytical expression is given in the paper. Then utilizing the developed circuit, a criteria to exit current limiting during post-fault conditions is given. The developed analytical approaches are then validated through electromagnetic transient (EMT) simulation results in PSCAD software and finally concluding remarks are drawn.

Mohiuddin, Sheik Mohammad↗

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.