Search NASA⌕ Search

SEARCH · Search NASA

Results for “FNET/GridEye”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

32 records · Page 2

Statistical Analysis of Inter-Area Oscillations in the U.S. Eastern Interconnection: A 2017-2023 Perspective

Recent advancements and the accumulation of high-resolution, long-term phasor measurement unit (PMU) data have provided detailed insights into inter-area oscillations in power grids. This study conducts a comprehensive statistical analysis of inter-area oscillations within the United States Eastern Interconnection from 2017 to 2023. Utilizing data captured by the advanced wide-area Frequency Monitoring Network (FNET/GridEye), this investigation examines the occurrence patterns, dominant frequencies, damping ratios, and excitation mechanisms of these oscillations. Our analysis sheds light on the evolving statistical behaviors of inter-area oscillations, offering updated and critical information for grid operators and planners. The insights gained from this study can be instrumental in enhancing the operational resilience of the power network and guiding strategic developments in grid infrastructure to accommodate future challenges. Additionally, the study discusses emerging challenges associated with the modernization of the power grid, including increased renewable penetration, dynamic load variability, and cyber-physical vulnerabilities that complicate oscillation monitoring and control.

Inter-area oscillations↗

Advanced Synchrophasor-based Application for Potential Distributed Energy Resources Management: Key Technology, Challenge and Vision

With an increasing number of distributed energy resources (DERs) integrating into the power system, the power grid is becoming more complex and uncertain. Owing to most of DERs are through grid-connected converters to integrate into the power system, the intermittent nature and resource-depended characteristic of the DERs are challenging their monitoring and control. Conventional synchronized measurement devices (SMDs) may be difficult to provide qualified data for DERs management for its accuracy and reporting-rate limitation. The monitoring systems developed basing on SMDs may be insufficient for depicting detailed dynamic manifestations of power systems with a high proportion integration of DERs. This paper shares some advanced synchrophasor-based applications developed in FNET/GridEye, which have a broad prospect for assisting system operator on the control and integration of the DERs.

Wang, Weikang↗

Model-less Source Location for Forced Oscillation based on Synchrophasor and Moving Fast Fourier Transformation

Forced oscillations in power systems occur when the grid is driven by an external and periodic force. To quickly detect and locate the source of the forced oscillation is critical in terms of ensuring the reliability of an interconnected power grid. This paper explores the electromechanical wave propagation theory and the Fast Fourier Transformation to analyze the forced oscillations. It proposes a model-less, adaptive, fast, and accurate source location algorithm. The proposed algorithm is extensively evaluated through simulation data from a 70k-bus U.S. Eastern Interconnection test system and field-collected synchrophasor data from the distribution-level wide-area monitoring system, FNET/GridEye. The evaluation results demonstrate the correctness and effectiveness of the proposed model-less forced oscillation source location algorithm.

Wang, Weikang↗

Comparative Analysis of Inter-Area Oscillations in the US Eastern and Western Interconnections

This paper presents a comparative analysis of interarea oscillations in the US Eastern and Western Interconnections using frequency disturbance data collected from the advanced wide-area Frequency Monitoring Network (FNET/GridEye), enabling us to investigate and compare the oscillation characteristics of both regions. The study analyzes the statistical data from the two interconnections, including total oscillation events, average dominant frequencies, damping ratios, and maximum amplitudes. We also explore the impact of seasonal and daily variations on oscillation occurrences and the influence of different grid topologies and operational practices. The results provide insights into both interconnections' stability and control characteristics, offering valuable information for power system operators to enhance grid stability and oscillation suppression measures.

Fu, Hao [University of Tennessee, Knoxville (UTK)]↗

FNETVision: A WAMS Big Data Knowledge Discovery System

With the growing awareness of the power system stability, wide area measurement system (WAMS) has been widely studied and deployed. In WAMS, a phasor data concentrator (PDC) collects and persists the GPS-time-synchronized phasor data from hundreds of phasor measurement units (PMU). Due to the size and complexity of the modern power systems, the number of deployed PMUs has been increasing and their data size becomes increasingly large. The large data volume challenges the analysis, and the knowledge discovery of the measurement data. This paper takes the pioneering distribution level WAMS- the frequency monitoring network FNET/GridEye as an example. It develops an adaptive visualization system- FNETVision to visualize the large-volume WAMS data by interconnection. The case studies suggest, based on the FNETVision system, the system administrator can quickly dig out issues of the FNET system and accordingly pinpoint the cause of these issues.

Wang, Weikang↗

Understanding Regional Inertia Dynamics in CAISO from Real Grid Disturbances

The shift from synchronous generators to inverter-based resources has caused power system inertia to be unevenly distributed across power grids. As a result, certain grid regions are more vulnerable to high rate-of-change of frequency (RoCoF) during disturbances. This paper presents a measurement-based framework for estimating grid inertia in CAISO (California Independent System Operator) region using real disturbance-driven frequency data from the Frequency Monitoring Network (FNET/GridEye). By analyzing confirmed disturbances from 2013 to 2024, we identify trends in regional inertia and frequency dynamics, highlighting their relationship with renewable generation and the evolving duck curve. Regional RoCoF values were up to six times higher than interconnection-wide values, coinciding with declining inertia. Recent recovery in inertia is attributed to the increased deployment of battery energy storage systems with synthetic inertia capabilities. These findings underscore the importance of regional inertia monitoring, strategic resource planning, and adaptive operational practices to ensure grid reliability amid growing renewable integration.

Dulal, Saurav [University of Tennessee, Knoxville ↗

U.S. Eastern Interconnection (EI) Electromechanical Wave Propagation and the Impact of High PV Penetration on its Speed

A power system electromechanical wave propagates from the disturbance location to the rest of system, influencing various types of protections. In addition, since more power-electronics-interfaced generation and energy storage devices are being integrated into power systems, electromechanical wave propagation speeds in the future power systems are likely to change accordingly. In this paper, GPS-synchronized measurement data from a wide-area synchrophasor measurement system FNET/GridEye are used to analyze the characteristics of electromechanical wave propagation in the U.S. Eastern Interconnection (EI) system. Afterwards, high levels of photovoltaic (PV) penetration are modeled in the EI to investigate the influences of a typical power-electronics--interfaced resource on the electromechanical wave propagation speed.

You, Shutang↗

Cyber-Attack Identification of Synchrophasor Data Via VMD and Multifusion SVM

A large amount of synchrophasor data in the wide area measurement system (WAMS) needs to be collected and transmitted to the phasor data concentrator, thereby increasing the possibility of being attacked by hackers. The attacked data are therefore hidden into the normal synchrophasor data so that the synchrophasor data based application will be affected. To remedy this problem, an identification framework is proposed to detect the data cyber-attack in WAMS utilizing variational mode decomposition (VMD) and multifusion support vector machine (MSVM). First, VMD is used to transform the attacked data into multiple modal components. Thereafter, a novel MSVM is employed to classify the deterministic features using the proposed linear combined multikernel (LCM). Further, this LCM can fuse multiple types of features, including the time, frequency, and statistical domains of the synchrophasor data. Utilizing the actual data from FNET/GridEye, different experiments are conducted under multiple attack strengths and types. The results demonstrate that the identification framework has higher precision and robustness compared with other conventional classifiers.

97 MATHEMATICS AND COMPUTING↗

Synchrophasor Data Compression Under Disturbance Conditions via Cross-Entropy-Based Singular Value Decomposition

The increasing deployment of phasor measurement units and the advances of their reporting rates are challenging the present data centers in terms of storing and analyzing large-volume data. Under power system disturbance conditions, it is difficult to retain critical information while compressing the synchrophasor data effectively. This article combines the cross entropy and the singular value decomposition, proposing a novel model to compress the synchrophasor data to an extremely small size yet keep superior accuracy. The proposed model is extensively tested and compared with the state-of-the-art algorithms using the simulated and the FNET/GridEye field-collected data. The result indicates that the proposed algorithm has superior performance in compressing the data while retaining critical information under disturbance conditions.

42 ENGINEERING↗

Timestamp Shift Detection for Synchrophasor Data Based on Similarity Analysis between Relative Phase Angle and Frequency

Timestamp Shift (TS) in synchrophasor data can lead to false operation of synchrophasor-based wide-area monitoring, protection and control applications. The letter presents a method to detect TS of synchrophasor data based on similarity analysis between its own relative phase angle and frequency. Here, a linear correlation component, caused by TS, between relative phase angle and measured frequency is discovered via theoretical derivation. Then a detection method is developed utilizing this linear component for TS diagnosis. Firstly, system phase angle is leveraged as angle reference and then relative phase angle is calculated. Secondly, the correlation coefficient between relative phase angle and frequency is calculated for similarity analysis. Thirdly, the TS is detected via threshold criterion and corresponding time error is estimated. The effectiveness of this method is validated via experiments with actual synchrophasor data in FNET/Grideye.

97 MATHEMATICS AND COMPUTING↗

Impact of GPS Signal Loss and Its Mitigation in Power System Synchronized Measurement Devices

With the aid of global positioning system (GPS), synchronized measurement devices (SMDs) are increasingly deployed across power systems to monitor the status of electric grids by providing accurate measurement data along with unified time stamps. Unfortunately, GPS receivers tend to lose signal lock when certain uncontrollable and unpredictable factors arise. In order to investigate the presence of GPS signal loss (GSL) issues on measurement devices, analysis is performed on historical data from both phasor data concentrators and FNET/GridEye servers. Meanwhile, the impact of GSL on field measurement accuracy has not been previously explored in depth. Through analysis and experimental tests, this paper discovers angle drift caused by GSL, which consequently leads to the total vector error exceeding the IEEE standard C37.118.1-2011. Furthermore, a compensation method is proposed to rectify the angle drift and laboratory experiments demonstrate that the proposed method does effectively reduce angle drift and mitigate the impact of GSL in SMDs.

47 OTHER INSTRUMENTATION↗

Multi-View Convolutional Neural Network for Data Spoofing Cyber-Attack Detection in Distribution Synchrophasors

Security of Distribution Synchrophasors Data (DSD) is of paramount importance as the data is used for critical smart grid applications including situational awareness, advanced protection, and dynamic control. Unfortunately, the DSD are attractive targets for malicious attackers aiming to damage grid. Data spoofing is a new class of deceiving attack, where the DSD of one Phasor Measurement Units (PMUs) is tampered by other PMUs thereby spoiling measurement based applications. In order to address this issue, a source authentication based data spoofing attack detection method is proposed using Multi-view Convolutional Neural Network (MCNN). First, common components embedded in raw frequency measurements from DSD are removed by Savitzky-Golay (SG) filter. Second, fast S transform (FST) is utilized to extract representative spatial fingerprints via time frequency analysis. Third, the spatial fingerprint is fed to MCNN, which combines dilated and standard convolutions for automatic feather extraction and source identification. Finally, according to the output of MCNN, spoofing attack detection is performed via threshold criterion. Extensive experiments with actual DSD from multiple locations in FNET/Grideye are conducted to verify the effectiveness of the proposed method.

97 MATHEMATICS AND COMPUTING↗

Detection of Synchrophasor False Data Injection Attack using Feature Interactive Network

The synchrophasor data recorded by Phasor Measurement Units (PMUs) plays an increasingly critical role in the regulation and situational awareness of power systems. However, the widely installed PMUs are vulnerable to multiple malicious attacks from cyber hackers during data transmission and storage. To address this problem, a Modified Ensemble Empirical Mode Decomposition (MEEMD) is proposed first to extract the intrinsic mode functions of each Synchrophasor Data Attacks (SDA). The frequency-based adaptive screening criterion embedded in MEEMD is used to eliminate the false intrinsic mode functions. Next, a Multivariate Convolutional Neural Network (MCNN) is proposed to identify multiple SDA by utilizing the extracted intrinsic mode functions and original SDA as input vectors. A fusion block as the main structure of MCNN is also leveraged to increase the diversity of features and compress the model parameters. Integrating MEEMD and MCNN, a framework with automatic feature extraction and multi-source information fusion capability, referred to as Feature Interactive Network (FIN), is proposed to detect multiple SDA. Based on the proposed FIN framework, six types of SDA are explored for the first time using actual synchrophasor data in FNET/Grideye that was collected from different locations in the U.S. Eastern Interconnection. Finally, a large quantity of experiments with different attack strengths are used to evaluate the adaptability and classification performance of the proposed FIN.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dynamic Model Validation with Governor Deadband on the Eastern Interconnection

This report documents the efforts to perform dynamic model validation on the Eastern Interconnection (EI) by modeling governor deadband. An on-peak EI dynamic model is modified to represent governor deadband characteristics. Simulation results are compared with synchrophasor measurements collected by the Frequency Monitoring Network (FNET/GridEye). The comparison shows that by modeling governor deadband the simulated frequency response can closely align with the actual system response.

dynamic↗