Power Flow Models of Grid-Forming Inverters in Unbalanced Distribution Grids

Load unbalance in electric distribution systems is unavoidable. Unbalanced load currents will lead to negative sequence (NS) voltages that may damage electric equipment. Unbalanced power flow analysis is a common tool to detect and mitigate NS voltage issues and requires accurate models of grid components. While traditional source models are available, grid-forming (GFM) inverter models are not well developed. GFM inverters implement various control strategies, which affect their power flow models. Here, in this paper, a novel GFM inverter model considering control effects is proposed. We show that for some control methods, unbalanced system loading will lead to unbalanced terminal voltages of the GFM inverters, which are modeled through an equivalent negative sequence impedance. The proposed models are initially validated using a simple test circuit. Then, they are applied in the power flow analysis on the IEEE 13-bus and 34-bus systems to demonstrate the accuracy improvement over the state-of-the-art. Using time-domain simulations as benchmarks, we show that the proposed models reduce the calculation error of negative sequence voltages by at least 25% in unbalanced distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Assessing the Technical Potential of Fast Frequency Response in Grid-Supportive Loads

Fast frequency response (FFR) is a critical tool for grid operators to manage contingency events in low-inertia systems. While large generators and loads are more commonly used, many smaller end use loads, in aggregate, can provide FFR across a large system. This work considers the technical potential of power electronics-based loads for autonomous FFR in low-inertia grids. We consider multiple factors that might influence the impact of FFR for various end use loads, with a focus on residential loads.

ENERGY PLANNING, POLICY, AND ECONOMY,POWER TRANSMI↗

Thermal-Mechanical Stress Analysis of PWR Pressure Vessel and Nozzles under Grid Load-Following Mode: Interim Report on the Effect of Cyclic Hardening Material Properties and Pre-existing Cracks on Stress Analysis Results

This report provides an update on an assessment of environmentally assisted fatigue for light water reactor components under extended service conditions. This report is a deliverable under the work package for environmentally assisted fatigue as part of DOE’s Light Water Reactor Sustainability Program. In a previous report (September 2015), we presented tensile and fatigue test data and related hardening material properties for 508 low-alloys steel base metal and other reactor metals. In this report, we present thermal-mechanical stress analysis of the reactor pressure vessel and its hot-leg and cold-leg nozzles based on estimated material properties. We also present results from thermal and thermal-mechanical stress analysis under reactor heat-up, cool-down, and grid load-following conditions. Analysis results are given with and without the presence of preexisting cracks in the reactor nozzles (axial or circumferential crack). In addition, results from validation stress analysis based on tensile and fatigue experiments are reported.

42 ENGINEERING↗

Scheduling and Control of Flexible Building Loads for Grid Services Based on a Virtual Battery Model

This paper presents a framework for modeling, scheduling, and controlling residential thermostatically controlled loads (TCLs) to provide multiple grid services, such as energy shifting, peak load reduction, and ancillary services. A modeling method is proposed to characterize the aggregate flexibility from heterogeneous TCLs using a battery-equivalent model. Based on the flexibility model, a multi-period optimal scheduling formulation is developed to best utilize the flexibility from building loads and maximize total benefits from stacked value streams. An algorithm is proposed to control individual TCLs to follow the desired power consumption in real-time. The proposed methods are illustrated and validated through simulations.

Wu, Di↗

Development of Digital Twin Predictive Model for PWR Components: Updates on Multi Times Series Temperature Prediction Using Recurrent Neural Network, DMW Fatigue Tests, System Level Thermal-Mechanical-Stress Analysis

The long-term operation (LTO) of nuclear power plant (NPP) beyond their original design life of 40 years, can lead to more material damage associated with cyclic fatigue under thermal-mechanical loading cycles and associated long-term exposure of reactor material to the deleterious reactor-coolant environments. However, under this LTO condition the reactor components can still safely operate but may require more frequent Nondestructive Evaluation (NDE) of reactor components. Frequent NDE requirement may lead to frequent shutdown of the NPP. This in turn can lead to power outage and additional NDE-inspection-cost related economic loss. The economic loss can be minimized by reducing uncertainty in life estimation of safety-critical pressure boundary components and by implementing more digital approach such as by using upcoming digital-twin (DT) technology for predicting the structural states (e.g., time and location dependent inside/outside thickness temperature, stress, strain, plastic deformation, etc.) and associated fatigue life of a component in real time. Towards this goal Argonne National Laboratory (ANL) with the sponsorship of DOE Light Water Reactor Sustainability (LWRS) program is working on the development of a DT framework that can be used for real time environmental fatigue prediction of reactor components. The DT framework is based on limited experiment-data, Artificial-intelligence (AI) – Machine-Learning (ML) - Deep-Learning (DL) based techniques and Multiphysics-computational-mechanics such as finite element (FE) based modeling tools. Towards this overall goal, following are some of the major contributions made during the FY21: 1) Multiple 82/182 dissimilar metal weld (DMW) specimens (both solid-weld and joint-weld representing the actual reactor multi-metal nozzles) were fatigue tested. The resulting fatigue lives were compared to the NUREG-6909 based best-fit and design fatigue curves. Additionally, the results of 52/152 DMW fatigue specimens (which were recently tested at Republic of Korea under the sponsorship of International Nuclear Energy Research Initiative - INERI program) were compared to the NUREG-6909 based best-fit and design fatigue curves. From the comparison of 82/182 and 52/152 DMW test data with NUREG-6909 best-fit curve, most of the reported test data fall way away from the NUREG-6909 suggested best-fit or mean curve. The NUREG-6909 suggested best-fit curve is the best-fit curve of austenitic stainless steel and due to lack of enough data on Nickel-based welds, this is currently being used for predicting the life of Nickel-alloy-based welded components. However, the above observation may require higher scaling factor (e.g., ASME suggested factor of 20 on cycles rather than the current NUREG-6909 suggested factor of 12 on cycles) for scaling the austenitic-stainless-steel best-fit-curve for estimating the design or safe-life of a welded component. Accordingly, for example, if a DMW component experience a strain amplitude of 0.6% the PWR-water life of the component would be 52 cycles instead of 85 cycles. However, more DMW tests are required to further ascertain the above-mentioned observations. 2) A system level CAD and finite element model were developed which consists of reactor pressure vessel (RPV), part of steam generator (SG), part of pressurizer (PRZ), hot leg (HL), and surge line (SL). This is with detailed nozzle geometry and thermal-mechanical material properties of different metals to simulate realistic thermal-mechanical stress under connected system global thermal-mechanical boundary conditions. 3) Different system level heat transfer analyses were performed with estimation of relevant heat transfer coefficients. The resulting data were used in subsequent system level thermal-mechanical stress analysis and for generating spatial-temporal training and validation data for a system level digital-twin based temperature predictor. Transient heat transfer analyses were performed considering thermal boundary condition under design-basis (DB) loading and EDF (Électricité de France) data-based grid-load-following (EDF-GLF) loading cycles. 4) System level thermal-mechanical stress analysis was performed for identifying damage-prone hotspots and for future extension of the model for cyclic state prediction. From the system-level model simulation under DB loading cycle it is found that HL and the SL nozzle that connect to the HL can experience significant stress and strain and could be one of the weakest links in the overall reactor coolant system (RCS). 5) An AI/ML based DT model was developed for multi-time-series temperature prediction at any inside/outside thickness locations of PWR pressure boundary components. This is by using Recurrent-neural-network (RNN) and keras machine learning libraries. The RNN model was validated against two laboratory test-based data sets with one obtained through ANL’s in-air fatigue test system and other through PWR-water test loop. The experimentally validated DT model further validated against FE model results to predict thermal scarification related spatialtemporal temperatures at random locations of a component. The well validated DT model was then used for demonstrating spatial-temporal temperature prediction under 100+ years of reactor operation subjected to combined DB, EDF-GLF and randomized grid-load-following (RANDOMGLF) loading Cycles. The expert-elicitation DT model framework was developed assuming field/input/process measurements can be available from a few existing plant sensors and can readily be used by the NPP operators. The above temperature prediction model will feed to the next-step stress analysis model based on which the life of a component can be predicted in realtime, which is one of our future works.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Analyzing Potential Grid Impacts from Future In-Motion Roadway Wireless Power Transfer Scenarios: Preprint

This work examines the grid impact of in-motion roadway wireless power transfer through the examination of the electrification of high-capacity roadways inside a metropolitan area. The work uses data from a regional travel study and the Federal Highway Administration's Highway Performance Monitoring System to estimate the electrified roadway's hourly power use throughout a week. The data are then combined with hourly grid load estimates for the same metropolitan area to determine the overlay of traditional grid load with additional load from a future electrified roadway.

30 DIRECT ENERGY CONVERSION↗

Analyzing Potential Grid Impacts from Future In-Motion Roadway Wireless Power Transfer Scenarios

This work examines the grid impact of in-motion roadway wireless power transfer through the examination of the electrification of high-capacity roadways inside a metropolitan area. The work uses data from a regional travel study and the Federal Highway Administration's Highway Performance Monitoring System to estimate the electrified roadway's hourly power use throughout a week. The data are then combined with hourly grid load estimates for the same metropolitan area to determine the overlay of traditional grid load with additional load from a future electrified roadway.

30 DIRECT ENERGY CONVERSION↗

Hardware Implementation and Market Impacts of Grid-Supportive Functions in End-Use Loads

Grid-supportive loads (GSLs) are power electronics-based end-use loads that can provide frequency response and other grid services by autonomously adjusting their output power using local grid measurements. This report provides details on GSL hardware design options and their associated costs and benefits for multiple devices, including EV chargers, refrigerators, and heat pumps. We consider mechanisms to incentivize adoption of GSLs at scale and estimate the quantity of frequency response that can be procured with GSLs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analysis of Electric Vehicle Charging Behavior Patterns with Function Principal Component Analysis Approach

This manuscript focused on analyzing electric vehicles’ (EV) charging behavior patterns with a functional data analysis (FDA) approach, with the goal of providing theoretical support to the EV infrastructure planning and regulation, as well as the power grid load management. 5-year real-world charging log data from a total of 455 charging stations in Kansas City, Missouri, was used. The focuses were placed on analyzing the daily usage occupancy variability, daily energy consumption variability, and station-level usage variability. Compared with the traditional discrete-based analysis models, the proposed FDA modeling approach had unique advantages in preserving the smooth function behavior of the data, bringing more flexibility in the modeling process with little required assumptions or background knowledge on independent variables, as well as the capability of handling time series data with different lengths or sizes. In addition to the patterns revealed in the EV charging station’s occupancy and energy consumption, the differences between EV driver’s charging time and parking time were analyzed and called for the needs for parking regulation and enforcement. The different usage patterns observed at charging stations located on different land-use types were also analyzed.

Engineering↗

Grid Services Load Shift Baseline Degradation Analysis Methodology v1

As demand flexibility becomes more common, the mix and frequency of a range of demand flexibility strategies will introduce potential biases into baselines, i.e., the time period immediately prior to a LS event may include other LS or DF events. Baseline degradation assessment provides an approach to quantify how these biases begin to compromise predictive accuracy. Heatmaps, based on each month of the year provides a granular view of a given model's predictive capability. However, for comparing multiple algorithms, separately for weekdays and weekends, aggregating results to seasons provides a simpler means of comparison while still allowing for review of variations by time of day and time of year

Fernandes, Samuel↗

Large Load Management and Grid Planning

This presentation will cover these topics, followed by a discussion and Q&A: Grid impacts of load growth of the current bulk power system, a review of recent trends and events related to large load integration, what might these new large loads look like, what are options for reducing costs and timelines of integration, and working toward a framework for identifying hot spots for efficiently interconnecting large loads.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Mitigating Data Center Impact on Grid Stability: A Coordinated Control Strategy Using Verrus StabiliGrid Architecture

Large data centers, which now represent a significant and growing share of the total U.S. grid load, can inadvertently destabilize the electrical grid when they disconnect simultaneously during brief voltage disturbances. The July 10, 2024, Eastern Interconnection incident, in which a sub-100-millisecond transmission fault triggered the cascading loss of approximately 1,500 MW of data center load, illustrates this vulnerability. While commercial battery energy storage systems (BESS) deployed in data centers provide device-level fault ride-through per IEEE 1547, they lack coordination with facility protection logic and uninterruptible power supplies (UPS), limiting their effectiveness as grid-stabilizing assets. This report presents the Verrus StabiliGrid architecture, a coordinated control framework that integrates BESS, UPS, and point-of-interconnection (POI) protection settings to enable data centers to ride through both undervoltage and overvoltage grid contingencies without disconnecting. The four-step strategy encompasses: (1) high-resolution power quality monitoring to detect the grid state during events such as undervoltage, overvoltage, underfrequency, and overfrequency; (2) POI protection settings that allow for extended ride-through and grid-connected operation during grid contingencies; (3) grid state-driven autonomous dispatch of assets to improve grid resilience by reducing power draw during undervoltage or absorbing more power during overvoltage events; and (4) coordinated post-recovery dispatch of data center assets to restore firm load to pre-contingency levels. Validated through controller-hardware-in-the-loop (C-HIL) simulations at the National Laboratory of the Rockies, results show grid import restoration to pre-fault levels within 100 milliseconds of voltage recovery. This work advances the ability of data centers to transition from passive, disturbance-sensitive loads to active participants in grid stability, a capability increasingly required by emerging NERC and ERCOT regulatory frameworks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

CRADA Number NFE-24-10110 with Qubit Engineering Inc. (CRADA Final Report)

Over the past year, the Qubit Engineering team has pushed the frontiers of power‑grid optimization, working in close collaboration with Oak Ridge National Laboratory (ORNL) and the Tennessee Valley Authority (TVA). Their progress is reflected in three newly submitted conference papers, “Unified Relational GNN Architecture for AC Optimal Power Flow Calculations in Electric Grids,” “Graph‑Based Attention Mechanisms for Solving the AC Optimal Power Flow Problem in Electrical‑Power Networks,” and “Enhanced Power‑Grid Maintenance Planning and Quantum‑Inspired Combinatorial Prospects.” These publications showcase state‑of‑the‑art graph‑neural‑network methods for AC‑OPF and novel quantum‑inspired heuristics for maintenance scheduling. Beyond the academic results, the Qubit team has converted the research into two production‑grade tools built on TVA data: Neuro‑Grid, an AI‑driven power‑flow simulator that provides instant, interactive full‑grid load‑flow visualizations, and Quanta‑Grid, a quantum‑inspired maintenance‑scheduling engine to support logistics optimization for power utilities. Together, these advances demonstrate how Qubit’s partnership with ORNL and TVA is delivering practical, physics‑grounded analytics for next‑generation grid management.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Learning-Based Load Control to Support Resilient Networked Microgrid Operations

Microgrids have proven to be an effective option for increasing the resiliency of critical end-use loads during extreme events. Building on past operational experiences, some microgrid operators are examining the potential to network microgrids to further improve resiliency. However, the frequency deviations experienced on isolated microgrids during transient events, such as switching operations, step increases in load, and loss of generation, are significantly larger than those typically seen on bulk transmission systems. The larger frequency deviations can cause a loss of inverter-connected assets, resulting in a loss of power to critical end-use loads. This paper presents a method of mitigating the impact of transient events by engaging end-use loads using Grid-Friendly Appliance TM (GFA) controllers. An online, i.e., real-time, device-level algorithm is presented, which adjusts individual GFA controller frequency set-points based on the operational characteristics of each end-use load, and on the changing grid dynamic characteristics. The presented method improves the dynamic stability of the networked microgrid operations while minimizing the interruptions to end-use loads. The presented work is validated with dynamic simulations using a modified version of the IEEE 123-node test system with three microgrids, using the GridLAB-D TM simulation environment.

Radhakrishnan, Nikitha↗

Electrical Load Modeling and Simulation

Electricity consumer demand response and load control are playing an increasingly important role in the development of a smart grid. Smart grid load management technologies such as Grid FriendlyTM controls and real-time pricing are making their way into the conventional model of grid planning and operations. However, the behavior of load both affects, and is affected by load control strategies that are designed to support electric grid planning and operations. This chapter discussed the natural behavior of electric loads, how it interacts with various load control and demand response strategies, what the consequences are for new grid operation concepts and the computing issues these new technologies raise.

Demand Response↗

Grid oscillators

Loading a two-dimensional grid with active devices offers a means of combining the power of solid-state oscillators in the microwave and millimeter-wave range. The grid structure allows a large number of negative resistance devices to be combined. This approach is attractive because the active devices do not require an external locking signal, and the combining is done in free space. In addition, the loaded grid is a planar structure amenable to monolithic integration. Measurements on a 25-MESFET grid at 9.7 GHz show power-combining and frequency-locking without an external locking signal, with an ERP of 37 W. Experimental far-field patterns agree with theoretical results obtained using reciprocity.

Popovic, Zorana B.↗