Search NASA⌕ Search

SEARCH · Search NASA

Results for “OPAL-RT”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Practical Start-Up Process of Multiple Grid-Tied Voltage-Sourced Inverters in Laboratory

Starting up inverter-based resources (IBRs) and integrating them into a grid are important in real-world engineering and there are many challenges to be tackled. Using a laboratory-scale hardware test bed (50 Watt and 20 V), this paper demonstrates the challenges and provides a practical start-up process that can smoothly energize two grid-tied voltage-sourced inverters (VSI) and synchronize the VSIs into a 60-Hz grid. The hardware test bed consists of two SiC VSIs and a 45-kW Chroma grid simulator to act as the grid. The inverter controls are implemented in OPAL-RT OP5600, which has the measurements sensed, control algorithms processed, and gate signals generated and sent to the VSI switches. This research focuses on examining how to energize VSIs and how to synchronize the VSIs into the grid. The best energizing approach is summarized based on comparison and analysis of the experiment results. The presented approach can prevent large transients during the start-up process.

Wang, Zhengyu↗

Reconfigurable Real-Time Power Grid Emulator for Systems With High Penetration of Renewables

Novel power system control and new utility devices need to be tested before their actual deployment to the power grid. To assist with such a testing need, real-time digital emulators such as RTDS and Opal-RT can be used to connect to the physical world and form a hardware in the loop (HIL) emulation. However, due to the limitations of today's computational resources, the accuracy and fidelity suffer from different levels of model reductions in purely digital simulations. CURENT has developed a reconfigurable electric grid hardware testbed (HTB) to overcome the limitations of digital emulators. The HTB has been used to develop measurement, control, modeling, and actuation techniques for a national grid with a high penetration of renewables. The power electronic-based system includes emulators for synchronous generators; photovoltaics with grid-interfacing inverter; wind turbines; induction motor loads, ZIP loads, power electronic loads; batteries; ac and dc transmission lines; short circuit faults and grid relay protection; and a multiterminal HVDC overlay including power electronics interfaces. The system contains real elements of power flow, measurement, communication, protection, and control that mimic what would be seen in an actual electric grid. This paper presents an overview of the HTB and several scenarios that have been run to determine control and actions needed for the future power grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Network Reduction Algorithm for Developing Distribution Feeders for Real-Time Simulators

As advanced grid-support functions (AGF) become more widely used in grid-connected photovoltaic (PV) inverters, utilities are increasingly interested in their impacts when implemented in the field. These effects can be understood by modeling feeders in real-time simulators and test PV inverters using power hardware-in-the-loop (PHIL) techniques. This paper presents a novel feeder model reduction algorithm using a ruin & reconstruct methodology that enables large feeders to be solved and operated on real-time computing platforms. Two Hawaiian Electric feeder models in Synergi Electric's load flow software were converted to reduced order models in OpenDSS, and subsequently implemented in the OPAL-RT real-time digital testing platform. Smart PV inverters were added to the realtime model with AGF responses modeled after characterizing commercially available hardware inverters. Finally, hardware inverters were tested in conjunction with the real-time model using PHIL techniques so that the effects of AGFs on the feeders could be analyzed.

14 SOLAR ENERGY↗

Microgrid Power Flow Control with Integrated Battery Management Functions

This paper presents a microgrid power flow control for islanded microgrids consisting of photovoltaic (PV) system, battery energy storage system (BESS) and diesel generator. The proposed control ensures automatic coordination among the microgrid units. To achieve the coordination, the local control of PV system and BESS are configured to regulate power flow without relying on communications. The generator is controlled as the back-up source and its connection depends on battery state of charge (SOC). A state machine with hysteresis settings is used to trigger smooth transition among operation modes. Not only does the proposed controller consider battery SOC and power limits, but also integrates three-stage charging control as battery charging mechanism, which is not considered in the existing literature. The proposed control is validated for an islanded hybrid microgrid using an OPAL-RT real-time simulator.

Long, Qian↗

Maximum Power Reference Tracking Algorithm for Power Curtailment of Photovoltaic Systems

This paper presents an algorithm for power curtailment of photovoltaic (PV) systems under fast solar irradiance intermittency. Based on the Perturb and Observe (P&O) technique, the method contains an adaptive gain that is compensated in real-time to account for moments of lower power availability. In addition, an accumulator is added to the calculation of the step size to reduce the overshoot caused by large irradiance swings. A testbed of a three-phase single-stage, 500 kVA PV system is developed on the OPAL-RT eMEGAsim real-time simulator. Field irradiance data and a regulation signal from PJM (RTO) are used to compare the performance of the proposed method with other techniques found in the literature. Results indicate an operation with smaller overshoot, less dc-link voltage oscillations, and improved power reference tracking capability.

Paduani, Victor↗

Challenges and Solutions for Real-Time Phasor Modeling of Large-scale Distribution Network with High PV Penetration

The conversion process of a practical large-scale feeder data from a quasi-static time series (OpenDSS) model into a real-time phasor model (ePHASORSIM in Opal-RT) is discussed in the paper. The process is implemented using an open source Python software. Previous reported implementations for the conversion process lead to several errors when applied to a larger-scale system such as the one considered here. Hence in this work, we describe the common issues in this conversion and propose a customized solution to enhance the efficiency of the conversion and reduce the complexity in the process. A quantitative validation of the enhanced conversion process is presented in this work using an actual high PV penetration feeder model that consists of 2230 buses, and using actual load and PV profile data. After a detailed analysis, this customized conversion software will be made available as an open source tool and is expected to be helpful for researchers who want to pursue a similar conversion. Solutions to various observed issues such as identifying the lines due to islanded network, representation of full impedance model of transformer/lines as sequential models, complexity in the representation of single phase buses/lines as three phase buses/lines to make it compatible with the simulator platform are discussed. Comparison of power flow and time series simulation results obtained from both OpenDSS and ePHASORsim models show very low errors, validating the accuracy of the proposed conversion process.

14 SOLAR ENERGY↗

Spatio-Temporal Deep Graph Network for Event Detection, Localization, and Classification in Cyber-Physical Electric Distribution System

This work proposes a deep graph learning framework to identify, locate, and classify power, cyber, and cyber power events at the distribution system level. The proposed algorithm jointly exploits spatial, temporal, and node-level cyber and physical data features. The developed graph neural network, together with a deep autoencoder, utilizes physical measurements from distribution level phasor measurement units and cyber data from communication network logs. The spatial structure of the synchrophasor measurements and network is incorporated through a weighted adjacency matrix. The temporal structure is incorporated by defining a spatial operation in the gated recurrent unit. This spatio-temporal learning element resides inside a power event detection, localization, and classification module that provides the degree of confidence for an event label. To accurately pinpoint the location of an event to the nearest bus equipped with a measurement unit, a combination of squared error and proximity score is utilized. Also included is a cyber event detection module that employs heteroskedasticity to analyze the significance of various cyber features during different types of attacks. Finally, a dual-bit cyber-power decision table determines the nature of the event. The proposed method is validated on two distribution systems modeled in OPAL-RT/Hypersim with limited phasor measurement units for different possible physical and cyber events. Further analyses include comparison with other state-of-the-art methods and validation in the presence of measurement noise. As a result, our method outperforms existing approaches and achieves an average detection accuracy of 97.97%, F1-score of 96.88%, precision of 96.53%, and recall of 98.57%.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Islanding Detection of Distributed Generation Using Electrical Variables in Space Vector Domain

This paper presents a new approach for islanding detection in distribution systems incorporating synchronous generator-based distributed generations. The proposed method first utilizes the dynamic equations of three electrical variables under islanding situations. The variables are: change of frequency; rate of change of frequency; and rotor angle deviation. Second, transformation of these variables is conducted in the space vector domain, which gives rise to three parameters, namely, semi-major axis, semi-minor axis, and inclination angle. Finally, exploiting these parameters, a decision boundary is established to classify grid events resulting in the formation of an island or not. The proposed method is comprehensively investigated under different operating conditions, which include excess/deficit of reactive/active power imbalance scenarios in the formed island containing different load-types (constant impedance, constant power, and constant current) with varying quality factor. A large variety of islanding and non-islanding events are generated using a practical distribution network simulated in real time on OPAL-RT digital simulation platform under the aforementioned operating conditions. A detailed evaluation of the proposed approach is conducted and it demonstrates the effectiveness of the method.

F-measure↗

Data-Driven Cyber-Attack Detection for PV Farms via Time-Frequency Domain Features

The internetworking of grid-connected power electronics converters (PECs) in photovoltaic (PV) farms has inevitably expanded the cyber-attack surfaces. Here this paper presents a comprehensive study on cyber-attack detection and diagnosis for PEC-enabled PV farms via single waveform sensor to distinguish between normal conditions, open-circuit faults, short-circuit faults, and cyber-attacks. To our knowledge, this has not been attempted before. Firstly, we propose frequency-domain magnitude-based residuals to identify short-circuit faults and a time-domain mean current vector-based feature to distinguish open-circuit faults from other threats. These features can fully reflect the specific physical characteristics of PV farms during threat duration. Secondly, unlike micro phasor measurement units (µPMU) and raw electric waveform-based methods, the proposed innovative features can address novel cyber-attacks that are excluded from the training process. Thirdly, an online hardware-in-the-loop (HIL) testbed using the OPAL-RT real-time digital simulator has verified the effectiveness. The monitoring system runs in real-time while using HIL as an operational solar farm and a National Instruments (NI) data acquisition card as the electric waveform sensor at the point of coupling.

42 ENGINEERING↗

GHOST (Grid Hardware Open Source Testbed) [SWR-18-32]

The software was developed for the purpose of Microgrid Controller Procurement where multiple Microgrid Controller vendors were competing to prove the best performance. Each microgrid controller was connected to Real-Time Simulator (Opal-RT) where the Real-Time model of microgrid was simulated. Microgrid controllers were able to control most of the assets in the model. To be able to fairly compare controller's performance each controller was evaluated using exactly the same model, with the same initial conditions and exactly the same test sequence. The microgrid evaluation test sequence lasted 100 minutes and consist of various grid disturbances to which a microgrid controller must respond. The microgrid and power system will experience multiple types of disturbances while performing dispatch functions. Many functions are tested in grid-connected and islanded modes such as unexpended failures of generators, energy storage trip events, and large load fluctuations. The test sequence focuses on fault scenarios that cause the highest short-circuit fault current contribution; force a swing bus or generator capable of being a swing bus offline; cause the most reconfigurations; and cause conflicting objectives for the microgrid controller. During the test sequence execution multiple datapoints are being recorded and stored. During data postprocessing key performance parameters are extracted allowing quantitative comparison of performance on multiple aspects including: resiliency, fuel utilization, grid interconnection, ancillary services and power quality and eventually after summing all key performance parameters by comparing the overall result. To be able to perform such testing multiple tools had to be developed included in this repository including: - Real time model of microgrid (Urban-Banshee, Remote-smaller model) - Test sequence configuration tools - Test execution real-time scripts - Post processing scripts - Human Machine Interface software

Koralewicz, Przemyslaw↗

Bulb-style Kaplan Turbine - Run-of-the-river (ror) Hydro Governor And Turbine Model

This software package includes hydro governor and turbine models developed in Simulink (Mathworks Inc.) and RSCAD (RTDS Technologies) for low-head bulb-style Kaplan turbine hydropower plants. The model developed in Simulink has been designed and tuned to match the governor-turbine response for a real-world hydropower unit owned by Idaho Falls Power (IFP). The Simulink and RSCAD models enable real-time testing in a hardware-in-the-loop (HIL) implementation using OPAL-RT and RTDS digital real-time simulators, respectively. An automatic initialization for dynamic simulation has also been integrated to each model in both Simulink and RSCAD. The RSCAD initialization involves a novel python-based interfacing for automatic modification of the initial conditions in the model. The parameters of these models can be tuned to match other hydropower plants in this class.

Alam, SMShafiul↗

Outdoor Test Bed Performance of a Power Line Sensor Using a Real-Time Event Simulator

This report summarizes the design and application of an outdoor power line sensor testbed (OPLST) with a real-time simulator and power meter to compare a potential transformer (PT) and current transformer (CT) versus an advanced line-post sensor. The OPLST was created to validate advanced medium-voltage (20/34.5 kV) outdoor power line sensors used in electrical distribution systems. Electrical utilities have installed metering and relay-protection transformers like PTs and CTs for several decades. The PTs/CTs are iron core measurement transformers based on the electromagnetic induction principle and provide reliable data in normal grid operation. However, new outdoor power line sensors (OPLS) using other technologies like voltage divider, Rogowski coil and optical principles have become available and may have favorable performance and costs compared to PTs/CTs. Therefore, the importance of testing these technologies with the PT/CT, to compare the measured phase voltage/current at different power grid scenarios is crucial to understand the performance of these new OPLS. For this study a G&W Electric Model CVS-36-O power line sensor was chosen as the OPLS to test with voltage/current signals. An OPAL-RT Technologies Model OP4510 real-time simulator and Schweitzer Engineering Laboratories Model SEL-735 power meter were installed with the 20/34.5 kV OPLST to compare the measured transient events collected from an advanced OPLS and the PT/CT. This system is installed at the Distributed Energy Communications and Control (DECC) lab, Oak Ridge National Laboratory (ORNL). The simulator generated different power grid scenarios (electrical faults, capacitor bank operation, service restoration, etc.), and its analog-output signals were connected to the voltage/current amplifiers that feed the 20/34.5 kV aerial cable loop through the PT/CT devices. Additional PT/CT devices were also wired with the medium voltage aerial cable loop to measure the phase current/voltage signals and server as references. After each test, common format for transient data exchange (COMTRADE) files were collected from the SEL-735 power meter and used to compare the performance of the OPLS with the PT/CT. The behavior of analog signals, harmonic components, total harmonic distortion and crest factors were assessed and found favorable for the G&W sensor as compared to the reference PT/CT.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimal Reconfiguaration and Resilient Control Framework for Real-Time Photopholtaic Dispatch to Manage Critical Infrastructure (ReDis-PV)

The consortium is conducting cutting-edge collaborative research that will allow advancing solar energy’s role in strengthening the resilience of the U.S. electricity grid. The U.S Department of Energy Solar Technologies Office (SETO) has awarded 4.6 million to Professor Sukumar Kamalasadan (The University of North Carolina at Charlotte) for the project “Optimal Reconfiguration and Resilient Control Framework for Real-Time Photovoltaic Dispatch to Manage Critical Infrastructure (ReDis-PV)”. The project developed a grid management tool that detects cyber and physical threats and forms dynamic clusters to manage photovoltaic and energy optimally. The project collaborating team includes the University of North Carolina at Charlotte, Clemson University, New Mexico State University, Florida International University, Argonne National Laboratory, Idaho National Laboratory, OPAL-RT Corporation, and Duke Energy.

14 SOLAR ENERGY↗

Self-Aware Local Autonomous and Semi-Cooperative Control for Cross-Layered Resilience (SLAC3R)

The objective of this work is to develop and demonstrate novel, adaptive, lightweight algorithms that enable the decision-making agents in a large cyber-physical network to act both autonomously and in collaborative harmony to enforce assured resilience across spatiotemporal layers, even under unforeseen adversarial scenarios (e.g., high- impact-low-probability events). Towards this end, the proposed solution will serve as minimally invasive add-on layers that bridge the existing (faster, reactive) local myopic controls and (slower, predictive) centralized optimization. Importantly, the proposed algorithms will enable the multi-agent network to autonomously and collaboratively enforce resilient operation under no or limited communication environment typical of severe cyber- physical adversarial events. The expected outcome of this effort is a suite of prototype, open-source, software algorithms for safety-aware local autonomous and semi-cooperative control (SLAC3R), demonstrated on networked microgrids (via RD2C/Thrust-1 OPAL-RT testbed).

97 MATHEMATICS AND COMPUTING↗

Comparative and Cost Analysis of a Novel Predictive Power Ramp Rate Control Method: A Case Study in a PV Power Plant in Puerto Rico

One of the most important aspects that need to be addressed to increase solar energy penetration is the power ramp-rate control. In weak grids such as the one found in Puerto Rico, it is important to smooth power fluctuations caused by the intermittence of passing clouds. In this work, a novel power ramp-rate control strategy is proposed. Additionally, a comparison with some of the most common power ramp-rate control methods is performed using a proposed model and real solar radiation data from the Coto Laurel photovoltaic power plant located in Ponce, Puerto Rico. The proposed model was validated using one-year real data from Coto Laurel. The power ramp-rate control methods were compared in real-time simulations using the OP5700 from Opal-RT Technologies considering power ramp rate fluctuations, power ramp-rate violations, fluctuations in the state-of-charge, among other indicators. Moreover, the proposed power ramp-rate control strategy, called predictive dynamic smoothing was explained and compared. Results indicate that the predictive dynamic smoothing produced a considerably reduced Levelized Cost of Storage compared to other power ramp-rate control methods and provided a higher lifetime expectancy for lithium batteries.

36 MATERIALS SCIENCE↗

NREL's Advanced Distribution Management System (ADMS) Test Bed

NREL's advanced distribution management system (ADMS) test bed is a vendor-neutral resource for evaluating existing and future ADMS functionalities in a realistic laboratory setting. The test bed uses Opal-RT's ePHASORsim and eMEGAsim products interfaced with an OpenDSS power system simulation through the HELICS cosimulation platform developed by multiple DOE laboratories; and with power and controller hardware. NREL will present an overview of the test bed and the technologies included within it, and also some examples of how the test bed has been used to address industry challenges.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of Blockchain Delay on Grid-Tied Solar Inverter Performance: Preprint

This paper investigates the impact of the delay resulting from a blockchain, a promising security measure, for a hierarchical control system of inverters connected to the grid. The blockchain communication network is designed at the secondary control layer for resilience against cyberattacks. To represent the latency in the communication channel, a model is developed based on the complexity of the blockchain framework. Taking this model into account, this work evaluates the plant’s performance subject to communication delays, introduced by the blockchain, among the hierarchical control agents. In addition, this article considers an optimal model-based control strategy that performs the system’s internal control loop. The work shows that the blockchain’s delay size influences the convergence of the power supplied by the inverter to the reference at the point of common coupling. In the results section, real-time simulations on OPAL-RT are performed to test the resilience of two parallel inverters with increasing blockchain complexity.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Networked HIL Simulation System for Modeling Large-scale Power Systems

This paper presents a network hardware-in-the-loop (HIL) simulation system for modeling large-scale power systems. Researchers have developed many HIL test systems for power systems in recent years. Those test systems can model both microsecond-level dynamic responses of power electronic systems and millisecond-level transients of transmission and distribution grids. By integrating individual HIL test systems into a network of HIL test systems, we can create large-scale power grid digital twins with flexible structures at required modeling resolution that fits for a wide range of system operating conditions. This will not only significantly reduce the need for field tests when developing new technologies but also greatly shorten the model development cycle. In this paper, we present a networked OPAL-RT based HIL test system for developing transmission-distribution coordinative Volt-VAR regulation technologies as an example to illustrate system setups, communication requirements among different HIL test systems, and connection mechanisms. Impacts of communication delays, information exchange cycles, and computing delays are illustrated. Simulation results show that the performance of a networked HIL test system is satisfactory.