Search NASA⌕ Search

SEARCH · Search NASA

Results for “Ride-Through Capabilities”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

23 records · Page 2

IEEE 1547-2018 Based Interoperable PV Inverter with Advanced Grid-Support Functions

Grid integration of photovoltaic (PV) inverters has been increasing in the past decade. As a result of the uncertainties introduced with high penetrations of PV, better monitoring and control of the PV inverters becomes crucial for improving overall system stability. This paper focuses on the communications capability of the inverter controller and on enabling interoperability. Multiple standards are available to enable interoperability in PV inverters. In this paper, an interoperable controller, enabled by Distributed Network Protocol 3 (DNP3) communications protocols, is developed for a grid-connected, three-phase PV inverter. The DNP3 server for the PV inverter is programmed on the real-time layer of the field-programmable gate array (FPGA)-based inverter controller. Set points for advanced inverter control functions, such as volt/VAr curves, ride-through curves, are sent from a DNP3 client, a simulated distribution management system application, to the PV inverter through DNP3. This communications capability of the inverter controller is validated using a controller-hardware-in-the-loop experimental setup. The code developed to achieve the interoperability is available in the public domain through open-source software licensing. This interoperability will enable smoother grid integration of smart PV inverters with advanced grid-support functions as well as allow better monitoring and control of PV inverters for grid stability.

14 SOLAR ENERGY↗

Background Information on the Protection Requirements in IEEE Std 1547-2018

As the DER penetration level has risen significantly in recent times, parameter settings and configuration of installed DERs are having direct impact on local electric distribution utilities as well as bulk power systems during normal and abnormal grid conditions. On the other hand, all grid-connected DERs in the United States of America must conform to the interconnection requirements prescribed in the IEEE Std 1547-2018. Because of these reasons, it is crucial to understand the expected DER performance during abnormal grid conditions considering the requirements of the IEEE Std 1547-2018. The aim of this document is twofold: (1) to summarize requirements in IEEE Std 1547-2018 having direct implications in distribution network protection, and (2) to provide the reader with knowledge and information that will be required for users to apply the requirements specified. Since the focus of this document is on distribution network protection in the presence of DERs, it is assumed that the readers have basic understanding of distribution network protection as well as working principles of DERs. This document starts with a brief introduction on protection systems for distribution network followed by a discussion on the impact of DER on the protection systems. Current practices to provide network protection in the presence of DER is briefly discussed. The document then explores the DER performance requirements in IEEE Std. 1547-2018; especially on those related to distribution network protection. Section 6.1 in IEEE Std. 1547-2018 provides an overview of capabilities and control requirements for DER under abnormal operating conditions. This section also introduces abnormal operating performance categories I, II, III. The DER response to various types of faults and grid conditions such as short-circuit faults and open phase conditions are discussed in section 6.2 in the standard while requirements for coordination with the Area EPS reclosing scheme are provided in section 6.3. Section 6.4 in the IEEE Std 1547-2018 specifies requirements for mandatory voltage tripping and ride-through requirements during low and high voltage disturbances and section 6.5 specifies similar requirements for low and high frequency disturbances. IEEE Std. 1547 requires that the conformance of the DERs to IEEE Std 1547-2018 requirements should be verified in accordance with IEEE Std. 1547. 1. There are several parameters and settings of DERs that need to be properly selected for reliable operation during abnormal grid condition while applying the requirements of IEEE Std 1547-2018. Key decisions for proper selections of parameter and settings are: 1. Determination of required DER abnormal operating performance category, 2. Determination of DER response (shall trip) to abnormal voltages and 3. Determination of DER response (shall trip) to abnormal frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Mitigating Data Center Impact on Grid Stability: A Coordinated Control Strategy Using Verrus StabiliGrid Architecture

Large data centers, which now represent a significant and growing share of the total U.S. grid load, can inadvertently destabilize the electrical grid when they disconnect simultaneously during brief voltage disturbances. The July 10, 2024, Eastern Interconnection incident, in which a sub-100-millisecond transmission fault triggered the cascading loss of approximately 1,500 MW of data center load, illustrates this vulnerability. While commercial battery energy storage systems (BESS) deployed in data centers provide device-level fault ride-through per IEEE 1547, they lack coordination with facility protection logic and uninterruptible power supplies (UPS), limiting their effectiveness as grid-stabilizing assets. This report presents the Verrus StabiliGrid architecture, a coordinated control framework that integrates BESS, UPS, and point-of-interconnection (POI) protection settings to enable data centers to ride through both undervoltage and overvoltage grid contingencies without disconnecting. The four-step strategy encompasses: (1) high-resolution power quality monitoring to detect the grid state during events such as undervoltage, overvoltage, underfrequency, and overfrequency; (2) POI protection settings that allow for extended ride-through and grid-connected operation during grid contingencies; (3) grid state-driven autonomous dispatch of assets to improve grid resilience by reducing power draw during undervoltage or absorbing more power during overvoltage events; and (4) coordinated post-recovery dispatch of data center assets to restore firm load to pre-contingency levels. Validated through controller-hardware-in-the-loop (C-HIL) simulations at the National Laboratory of the Rockies, results show grid import restoration to pre-fault levels within 100 milliseconds of voltage recovery. This work advances the ability of data centers to transition from passive, disturbance-sensitive loads to active participants in grid stability, a capability increasingly required by emerging NERC and ERCOT regulatory frameworks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

EMT data generation

The integration of inverter-based resources (IBRs) in power systems is accelerating, bringing with it significant benefits such as reduced greenhouse gas emissions, improved grid resilience, and increased energy independence. Despite these advantages, the widespread adoption of IBRs introduces several challenges, including issues related to grid stability, increased operational complexity, and the need for updated regulatory frameworks. To address these challenges, IEEE released Standard 2800 in 2022, which sets forth the necessary interconnection capabilities and performance criteria for IBRs connected to transmission and sub-transmission systems. This standard outlines the performance requirements to ensure the reliable integration of IBRs into the bulk power system. Furthermore, in 2023, the North American Electric Reliability Corporation (NERC) published a reliability guideline for electromagnetic transient (EMT) modeling of BPS-connected IBRs. This guideline provides recommendations for developing EMT model requirements, performing model quality checks, and implementing verification practices specifically for EMT models representing BPS-connected inverter-based resources in reliability studies conducted by transmission planners and planning coordinators. These standards and guidelines have a profound impact on EMT studies for transmission networks, influencing system stability analyses, grid recovery and resynchronization processes, fault ride-through evaluations, protection and coordination strategies, advanced control methodologies, and the inclusion of IBRs in transient models of transmission networks. As a result, the generation of EMT data is crucial for conducting various transient-based studies to understand the impact of IBRs. EMT data generation use cases serve as the basis for scenarios in event detection and identification use cases, providing comprehensive details about EMT data generation for transmission grids with inverter-based resources. These use cases supply sufficient training and validation datasets for subsequent EMT analysis algorithms.

Xia, Qianxue↗

Research Roadmap on Grid-Forming Inverters

This research roadmap is intended to fill the knowledge gap by providing a system view of grid-forming inverter-based resource controls and their impact on grid stability, which we believe is central to meeting some of the challenges to operating the future North American electric power system. This includes the roles and requirements of grid-forming inverter-based resources—including solar photovoltaics, wind generators, and energy storage. For this roadmap, we focus on a specific family of grid-forming inverter control approaches that do not rely on an external voltage source (i.e., no phase-locked loop) and that can share load without explicit communications. Although the roadmap is focused narrowly on system challenges for grid-forming controls and power system stability, including interactions with protection, we hope it serves as a foundational element for future system-of-systems roadmapping needed in a broader grid modernization effort with increasing deployments of inverter-based resources. The roadmap first introduces formal definitions for the grid stability topics and then describes the differences between grid-forming and traditional grid-following control approaches for inverter-based resources. The core of the roadmap consists of a review of current research and an outline of research needs related to five grid-forming inverter topics: frequency control, voltage control, system protection, fault ride-through and voltage recovery, and modeling and simulation. The review both delineates contemporary advances and highlights open research questions that must be addressed to enable the widespread adoption of inverter-based resources across the grid. Feedback from industry on these research questions is incorporated, including discussions during the Workshop on Grid-forming Inverters for Low-inertia Power Systems. The workshop included industry presentations and discussion of ongoing research, technology gaps, and piloting needs. This roadmap concludes by offering a multiyear perspective on the gradual field validation of grid-forming inverters. This perspective recognizes that the scale and scope of the types of power systems that inverters will be called on to provide grid-forming services will and should begin modestly. Specifically, this roadmap recognizes that inverter controls today are predominantly grid-following and that future power systems will involve a mix of inverter-based resources with both grid-following and grid-forming control capabilities. Growth over time will depend on how well grid-forming inverters perform and what advantages they bring as penetration levels (instantaneous and average) of inverter-based resources increases. This recognition, in turn, establishes a natural sequence of priorities for the research questions that must be addressed. Following this multiyear perspective, the roadmap offers short descriptions of two specific near-term research priorities: the review of regulatory and technical standards and the development of advanced modeling techniques. These priorities are foundational. We recommend immediate pursuit of them in parallel with and in direct support of the research outlined by our multiyear perspective.

24 POWER TRANSMISSION AND DISTRIBUTION↗