Forced Oscillation Grid Vulnerability Analysis and Mitigation Using Inverter-Based Resources: Texas Grid Case Study

Forced oscillation events have become a challenging problem with the increasing penetration of renewable and other inverter-based resources (IBRs), especially when the forced oscillation frequency coincides with the dominant natural oscillation frequency. A severe forced oscillation event can deteriorate power system dynamic stability, damage equipment, and limit power transfer capability. This paper proposes a two-dimension scanning forced oscillation grid vulnerability analysis method to identify areas/zones in the system that are critical to forced oscillation. These critical areas/zones can be further considered as effective actuator locations for the deployment of forced oscillation damping controllers. Additionally, active power modulation control through IBRs is also proposed to reduce the forced oscillation impact on the entire grid. The proposed methods are demonstrated through a case study on a synthetic Texas power system model. The simulation results demonstrate that the critical areas/zones of forced oscillation are related to the areas that highly participate in the natural oscillations and the proposed oscillation damping controller through IBRs can effectively reduce the forced oscillation impact in the entire system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Cyber Protection of Grid-Connected Devices Through Embedded Online Security

Cybersecurity research regarding the electric power grid has primarily been focused on protecting the communication layer of grid-connected devices against cyber-attack threats. Although many developed methods have greatly reduced the effects of a cyber-attack on the vulnerabilities of grid-connected devices, discovering new vulnerabilities is inevitable and a constant threat. As a result, the overall reliability and security of network communications with regard to grid-connected devices is a concern. Here, this paper proposes a method that further secures a system by focusing on the control and hardware layer of grid-connected devices. The device’s controller firmware will be validated and authenticated using integrated device emulation resources prior to being activated to control the grid-connected device. This verification process is performed while the controller is online and actively controlling power flows related to the device. Therefore, an attack to the system through a malicious firmware patch would be detected by the online security and rejected while safely maintaining continuous and stable control of the device. This method integrates the concepts of firmware hot-patching, digital twins, and active monitoring into an overall cybersecurity protection system.

cybersecurity↗

SIW21-95: Hybridizing Synchronous Condensers with Grid-Forming Battery Energy Storage Systems

One of the main challenges associated with deployment of high shares of inverter-based resources (IBRs) in power grid is not only reduced system inertia but also degrading system strength that may cause severe stability impacts. A minimum level of system strength is needed for the power system to remain stable under normal conditions and to return to a steady state condition following a system disturbance. Significant system strength reduction is expected in almost all planned areas for solar and wind generation deployment. Synchronous condensers (SC) have been considered as one main technology to address the system strength issues for the areas with high levels of IBRs. SCs can help improving reliability and resiliency of power system but they do not provide the full range of services needed by power systems for reliable and economic integration of high shares of inverter-coupled variable generation such as PV generation. Services related to active power controls cannot be provided by SCs due to lack of prime mover. Even for provision of reactive power SCs have certain constraints based on their thermal and stability limits. NREL has been conducting research on a hybridized concept that combines SCs with grid forming (GFM) battery energy storage systems (BESS). This super flexible AC transmission system (SuperFACTS) that combines these two technologies in a single plant under the same controller offers a unique scalable set of services to the power system at all levels (transmission, sub-transmission, distribution, islands and isolated microgrids). Depending on use cases, SuperFACTS can be controlled to provide fully dispatchable and flexible operation using energy storage component, provide a full range of existing and future ancillary and reliability services to the grid (similar or better than conventional sources), maintain adequate levels of grid strength and inertia, and provide fault current for proper operation of protection systems. Therefore, this economic and easy to commercialize solution has potential for significant impacts on certain segments of global energy sector. All types of gird services (market based, reliability and resiliency) can be provided by SuperFACTS plants. GFM BESS can act as a self-black start source for each SuperFACTS module, which in turn can act a black start resource for co-located PV and wind power plants, segments of transmission and distribution networks, for conventional power plants, etc. The issue of in-rush currents during black start is addressed by overcurrent capability of SCs. In this paper we describe the results of modeling for SuperFACTS concept.

grid forming↗

Decentralized Control of Cascaded H-Bridge Inverters for Medium-Voltage Grid Integration: Preprint

This paper introduces a fully decentralized control strategy that allows for individualized active and reactive power control of H-bridge inverters connected in series. After formulating a model of the system power flows, we outline a communications-free approach where each inverter can act on independent commands. Inverter-level feedback is accomplished locally via a measurement of current flowing through the stack. A key feature is the lack of any centralized control routines or phase-locked loop. In this framework, the reactive power control loops achieve voltage synchronization among the converters and the grid, and the active power control loops modulate the terminal voltage amplitudes that influence power delivery. Furthermore, pole placement via state feedback is used to ensure stability of voltage synchronization while also enabling tracking of bidirectional power commands. Simulations are presented to validate the proposed approach.

communication-free modular converter control↗

Control, Operation, and Stability Characteristics of Grid-Forming Type III Wind Turbines: Preprint

This paper explores the control, operation, and stability characteristics of grid-forming Type III wind turbines. The paper shows that the grid-forming operation mode requires redesign of only the slower control loops for active and reactive power control, whereas the faster current control implementation can stay the same as grid-following turbines. The paper also shows that grid-forming wind turbines face higher mechanical stress than grid-following wind turbines because of the slower speed of the active power control. This stress, however, can be mitigated using advanced pitch control. The paper compares the stability characteristics of the grid-forming and grid-following operation modes of Type III turbines by comparing sequence impedance responses for both operation modes. It is found that, unlike standard Type III wind turbines, the grid-forming mode substantially reduces the risks of subsynchronous oscillations during operation with series-compensated transmission lines. Moreover, the grid-forming Type III turbines can operate stably with extremely weak grids. The findings of this paper are validated using EMT-PSCAD simulations of a 2.5-MW turbine operating in both grid-forming and grid-following modes.

49 EE - Wind and Water Power Program - Wind (EE-4W↗

Control-inspired design and power optimization of an active mechanical motion rectifier based power takeoff for wave energy converters

Ocean waves have high energy density and are persistent and predictable. Yet, converting wave energy to a useable form remains challenging. A significant hurdle is the oscillatory nature of waves resulting in the alternating loads, which necessitate the use of rectification at some stage of the energy conversion. This research effort presents a novel design of active mechanical motion rectifier (AMMR) for the power takeoff (PTO), which provides enhanced controllability and better power performance when compared to passive mechanical motion rectifiers (MMR). Inspired by transistors used in synchronous electrical rectifiers, the proposed design uses controllable electromagnetic clutches in the mechanical transmission to allow active engagement-disengagement control; thus, rectifying the oscillatory motion into a unidirectional rotation for high energy conversion efficiency and allowing the generator in unidirectional rotation to control the bidirectional wave capture structure for maximizing the power output. A semi-analytical computational approach is developed to efficiently evaluate the optimal power achieved using the proposed AMMR-based PTO and active control. It is found that the AMMR-based PTO design yields a higher optimal power than the previous passive MMR design across the wave spectrum. The influences of generator inertia and reactive power are discussed. Furthermore, the effects of control parameters on the power output and the optimal trajectories are analyzed. Wave tank tests with the AMMR prototype demonstrated the effectiveness of AMMR based PTO design and validated the numerical analysis.

16 TIDAL AND WAVE POWER↗

Isochronous Architecture-Based Voltage-Active Power Droop for Multi-Inverter Systems

This article proposes an isochronous architecture for parallel inverters with only voltage-active power droop (VP-D) control for improving active power sharing as well as plug-and-play of multi-inverter-based distributed energy resources (DERs). The isochronous framework obviates the need for an explicit regulation of the frequency while allowing for sharing of reactive power. The article shows that the detrimental effects of circulating currents between inverters can be addressed in the framework developed. The isochronous architecture is implemented by employing a GPS to disseminate clock timing signals that enable the microgrid to maintain the nominal system frequency. Small signal eigenvalue analysis of a Multi-inverter Microgrid system near the steady-state operating point is presented to evaluate the system stability. Moreover, unlike traditional droop-based methods, the isochronous strategy lends itself to analytical guarantees which are developed in the article. Furthermore, the effect of delays in receiving GPS clock signals by an inverter is experimentally characterized and an inverter isolation mechanism is proposed that disconnects inverters facing large GPS communication delays. Hardware experiments on an 1.2 kVA-prototype and controller-hardware-in-the-loop validation on the CIGRE distribution network are conducted to demonstrate the effectiveness of the proposed architecture towards active and reactive power sharing between inverters with load scenarios.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Framework for Supporting Adaptive Droop Based Power Electronic Systems

The electric grid is evolving into an electrical network composed of power electronic converters interconnected with renewable and energy storage technologies. This requires the adoption of more advanced control such as volt/var regulation, fast frequency control, and active power frequency response. This work presents a communication and control framework to support dynamically changing droop control segments that can be used for different optimization schemes. Results are presented to work in a controller hardware in the loop testbed.

Starke, Michael↗

Analysis of Transformer Magnetizing Reactance Using Describing Function in Direct Power Control of Back-to-Back Modular Multilevel Converter with Advanced Grid Support

This paper presents a Port Controlled Hamiltonian based direct power control architecture for a back-to-back modular multilevel converter system connecting two ac sources at different frequencies. The system features advanced grid support functionalities based on IEEE 1547-2018, implemented on the inverter side. The rectifier side controller ensures reference following for active and/or reactive powers and maintains the commanded dc bus voltage. The inverter side controller ensures power command following for active and reactive powers.The proposed control architecture is designed to suppress second harmonic oscillations in powers during unbalanced grid voltage sags by dynamically adjusting the currents on each ac side. This also ensures effective elimination of any second harmonic oscillations in the equivalent dc bus voltage. Validation is performed on an OPAL-RT real-time platform with case studies on unbalanced and balanced sags, demonstrating the controller's effectiveness during real time implementation. A reduced-scale laboratory prototype further verifies these case studies, with experimental results for balanced sags due to grid simulator limitations. The results confirm the robustness and efficiency of the proposed control strategy in ensuring stable and reliable operation under various grid conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feedback and Oscillations: Constructing Feedback Systems for Root Cause Analysis of Oscillations in Power Grids

Dynamic phenomena linked to inverter-based resources (IBRs) have gained global attention. Several IBR-induced dynamics have caused bulk power system-connected wind or solar power plants to trip, and some have even led to widespread outages. In addition, many oscillations have been observed involving IBR power plants. In 2023, the IEEE Power & Energy Society (PES) IBR Subsynchronous Oscillations (SSO) task force published a journal article, “Real-World Subsynchronous Oscillation Events in Power Grids With High Penetrations of Inverter-Based Resources,” in which 19 IBR oscillation events were examined for their causation. Earlier in 2020, another PES task force article, “Definition and Classification of Power System Stability-Revisited & Extended,” authored by prominent academics, introduced converter-driven stability as a new category of stability. The international power grid industry community also took action by publishing the CIGRE Green Book, Power System Dynamic Modelling and Analysis in Evolving Networks (led by Babak Badrzadeh and Zia Emin) in 2024. In August 2024, the Energy Systems Integration Group (ESIG) released a practical guide led by Nick Miller, “Diagnosis and Mitigation of Observed Oscillations in IBR-Dominant Power System: A Practical Guide.” The goal of the guide is to assist practicing engineers in making initial judgments and conducting detailed analyses about oscillations. Finally, when addressing the classification of stability and oscillations, the guide emphasizes a causality-based taxonomy for grouping, such as voltage control-induced oscillations, synchronization-induced oscillations, and frequency or active power control-induced oscillations.

Fan, Lingling [Univ. of South Florida, Tampa, FL (↗

Preliminary Gap Analysis of Existing IEEE 1547 and IEEE 2800 Standards Towards GFM Technology

This document describes the tests that are conducted on generic grid-forming (GFM) distributed energy resource (DER) and inverter-based resource (IBR) models to check if the performance of the model aligns respectively with the IEEE Std 1547 TM -2018 and IEEE Std 2800 TM -2022 requirements. For the IEEE Std 1547 TM -2018 requirements, specifically the tests related to volt-var requirements and frequency droop requirements are conducted. For the IEEE Std 2800 TM -2022 requirements, specifically the tests conducted are related to reactive- power-voltage control requirements, active-power-frequency response requirements, voltage disturbance ride through requirements and phase jump ride through requirements. This is an initial draft/document. There are many more tests still yet to be done to further verify if the existing standards have a gap or inadvertent barrier to GFM technology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Load Shedding for Voltage Regulation With Probabilistic Agent Compliance

With the increased observability and controllability of distribution systems, the share of behind-the-meter systems is trending upwards rapidly. As a consequence, the impact of human behaviors on system performance can no longer be ignored and should be reflected in the energy management system models. In this paper, we discuss the problem of distribution system voltage control by active power curtailment where the agent compliance of the load curtailment signal is probabilistic. We discuss the modeling of the optimal voltage control problem with probabilistic agent compliance as a chance-constrained optimization problem, its tractable safe approximation using convex restriction, and a scenario-based mixed-integer reformulation as well as the associated solution method based on augmented Lagrangian method. The numerical simulation on IEEE test system validates the effectiveness of the proposed approach in obtaining high-quality feasible load curtailment signal with low computational cost, which makes it a viable tool for real time decision making.

augmented Lagrangian method↗

Yaw-Augmented Control for Wind Farm Power Tracking: Preprint

This paper presents an inner-outer control loop structure which uses wake steering (yaw control) to augment pitch control for wind farms to track a power reference signal. The outer-loop yaw controller employs a recently proposed dynamic yaw model with a time-varying graph structure that accounts for dynamic changes in the farm wake interactions due to the yaw action of upstream turbines. The wake interactions within the model include the physics of the streamwise and lateral wake evolution, which collectively determine its impact on downstream turbines. The inner-loop employs a compensation scheme to account for the slow timescale effects of the yaw control actions within the faster timescale pitch control. The controller is applied to track two power trajectories (typical of secondary frequency regulation signals) using a large eddy simulation wind farm plant. The results demonstrate that the additional control authority from yaw provides some added benefit in reducing the required turbine derates needed for wind farms to track transient power increases in the proposed setting. However, the benefit decreases and pitch control alone is sufficient when the turbines are derated beyond a certain level. These findings suggest that augmenting pitch control with yaw may provide financial incentives in terms of allowing wind farms to maximize power supply to the bulk power market while still providing regulation services. Further work is needed analyze the costs versus benefits of the additional control complexity versus bandwidth in augmenting pitch control with wake steering offers in these applications.

active power control↗

Overvoltage Prevention and Curtailment Reduction Using Adaptive Droop-Based Supplementary Control in Smart Inverters

Recent developments in the renewable energy sector have seen an unprecedented growth in residential photovoltaic (PV) installations. However, high PV penetration levels often lead to overvoltage problems in low-voltage (LV) distribution feeders. Smart inverter control such as active power curtailment (APC)-based overvoltage control can be implemented to overcome these challenges. The APC technique utilizes a constant droop-based approach which curtails power rigidly, which can lead to significant energy curtailment in the LV distribution feeders. In this paper, different variations of the APC technique with linear, quadratic, and exponential droops have been analyzed from the point-of-view of energy curtailment for a LV distribution network in North America. Further, a combinatorial approach using various droop-based APC methods in conjunction with adaptive dynamic programming (ADP) as a supplementary control scheme has also been proposed. The proposed approach minimizes energy curtailment in the LV distribution network by adjusting the droop gains. Simulation results depict that ADP in conjunction with exponential droop reduces the energy curtailment to approximately 50% compared to using the standard linear droop.

42 ENGINEERING↗

A Two-Stage Approach for PV Inverter Engagement in Power Factor Correction and Voltage Regulation

The rapid integration of distributed energy resources, like solar photovoltaics (PVs), can lead to overvolt-age challenges due to reverse power flow and a noticeable decrease in power factor at the substation interface. While existing literature extensively explores utilizing smart inverter capabilities for reactive power flexibility using a volt-var curve (VVC), obtaining time-varying operating points of such curves in real-time is challenging due to computational demands and communication requirements. Similarly, employing optimization-based approaches for reactive power control and active voltage regulation in large-scale distribution feeders is difficult due to the complexity of the problem and the challenges in effectively engaging customer-owned resources. This paper proposes a two-stage strategy to harness smart inverters for reactive power support. The first stage formulates short-term planning by optimally designing VVCs (on a daily or hourly basis) for large-scale solar PVs based on projected system needs and communicating optimal curves to smart inverters in advance. Subsequently, the second stage employs a transactive-based method to involve customer-owned PVs for reactive power support, effectively enhancing overall system performance and addressing real-time demands. In conclusion, the efficacy of this approach will be demonstrated using real-world distribution circuits provided by Vermont Electric Power Company (VELCO) and Vermont Electric Cooperative (VEC).

Poudel, Shiva [Pacific Northwest National Laborato↗

Angle Droop Design for Grid-Forming Inverters Considering Impacts of Virtual Impedance Control

Grid-forming inverters (GFMs) based on active power-frequency droop control and reactive power-voltage droop control have been developed in recent years, which can generate voltage and frequency references for islanded power systems or microgrids to improve system-wide synchronization and power-sharing capability. It is known that the control delays in GFMs may cause system harmonic instability. To eliminate this issue, virtual impedance techniques are normally adopted. This paper gives a comprehensive examination of the impacts of virtual impedance control block Z v in GFMs on system stability. It is revealed that although Z v is effective in eliminating system harmonic stability, it may ruin system synchronization stability as a side effect. To compensate for the negative impacts caused by Z v , an active power-angle control block is added into the conventional droop control. Design criteria are also proposed accordingly to ensure system stability over the entire frequency range. Simulations and experimental testing are conducted to validate the analysis and the proposed design guidelines. It can be concluded that the Z v control-caused grid-synchronization instability issues can be eliminated with an appropriate active power-angle droop design.

Kong, Le↗

Impacts of Voltage-Based Grid Support Functions on Energy Production of PV Customers

This paper presents the impact of inverter grid- support functions (GSFs) on photovoltaic (PV) customer energy production on a real distribution feeder in Oahu, HI. These autonomous GSFs based on local voltage measurements are good alternatives to increase PV hosting capacity. However, these functions can result in PV energy curtailment to the customer, and this study addresses the concerns about the impact of inverter GSFs through detailed quasi-static time series (QSTS) simulations. It proposes four metrics: maximum and average GSF curtailment, average increased generation and average net generation change, to assess the impact of a given control on PV systems located on customer sites. It was found that curtailment of PV production is negligible for customers where peak voltage is within ANSI C84.1 range. A reliable relationship between curtailment and peak customer voltage is demonstrated, suggesting that peak voltage could be used as an indicator of customer curtailment.

24 POWER TRANSMISSION AND DISTRIBUTION↗