At least 37 records · Page 2

Control and Simulation of a Grid-Forming Inverter for Hybrid PV-Battery Plants in Power System Black Start

Power system restoration is an important part of system planning. Power utilities are required to maintain black start capable generators that can energize the transmission system and provide cranking power to non-blackstart capable generators. Traditionally, hydro and diesel units are used as black start capable generators. With the increased penetration of bulk size solar farms, inverter based generation can play an important role in faster and parallel black start thus ensuring system can be brought back into service without the conventional delays that can be expected with limited black start generators. Inverter-based photovoltaic (PV) power plants have advantages that are suitable for black start. This paper proposes the modeling, control, and simulation of a grid-forming inverter-based PV-battery power plant that can be used as a black start unit. The inverter control includes both primary and secondary control loops to imitate the control of a conventional synchronous machine. The proposed approach is verified using a test system modified from the IEEE 9-bus system in the time-domain electromagnetic transient simulation tool PSCAD. The simulation results shows voltage and frequency stability during a multi-step black-start and network energization process.

Nguyen, Quan H.↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Safe Deep Reinforcement Learning for Robust Frequency and Voltage-Constrained Networked Microgrid Restoration

Here, this paper proposes a safe soft actor-critic reinforcement learning (RL) algorithm–based controller for networked microgrid restoration. It formulates the post black-start start as a finite-horizon constrained Markov decision process. The RL agent co-optimizes real and reactive power set-points for both grid-forming and grid-following inverters under explicit voltage and frequency constraints, while enforcing proper power sharing via the Mean Active Power Sharing Index (MPSI) and Mean Reactive Power Sharing Index (MQSI). Numerical results obtained on the IEEE 123-bus distribution system show that the proposed method achieves a mean voltage build-up time of 0.01 s without breaching the 5% sharing-violation budget under various load scenarios, considering MPSI and MQSI indices. These findings demonstrate that the proposed method yields fast and safe black-start schedules without resorting to heuristic penalties.

Selim, Alaa [Dartmouth College, Hanover, NH (Unite↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters: Preprint

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Time Disciplined Non-PLL Active Synchronization for Grid Forming Inverters

Two major issues facing grid-forming inverters are synchronism and phase reference inaccuracies. Prior literature has addressed these problems with solutions such as disciplining the phase reference using GPS and active synchronization modes but these methods have not yet been integrated together. This paper serves to unite solutions and develop a means for an inverter to remain synchronized and grid-forming without phase reference inaccuracies through a novel time-disciplined active synchronization phase reference. Further, this work expands upon prior literature on active synchronization to include black-start capabilities. Finally, the time disciplined phase reference is evaluated in Simulink as a grid-forming inverter capable of any synchronization circumstance and assessed by key metrics from modern standards.

blackstart↗

Autonomous Restoration of Networked Microgrids Using Communication-Free Smart Sensing and Protection Units

Here this paper presents autonomous restoration of networked microgrids using distributed energy resources (DERs), inverter-based resources (IBRs) in general, and controllable assets of intelligence without communication to achieve a extremely resilient power system restoration. The main innovation of this work lies in use of real-time smart sensing and decision making that enable autonomous recombination of islanded microgrids, which are individually black-started by local grid-forming (GFM) inverter units. The smart circuit breakers (SCBs) designed and demonstrated here play critical roles in the restoration process to achieve autonomy; the autonomous restoration scheme is not pre-engineered and may be subject to encounter overloading, live or downed segments as the boundary of the microgrids dynamically expands without prior knowledge and only with local measurement. We demonstrate autonomous microgrid restoration both in simulation of a modified IEEE 13-bus system, and in a hardware testbed comprising 24 GFM-IBRs and 6-SCBs, depicting several scenarios to evaluate their functionalities and interoperability. This work validates high potential of extremely resilient microgrid using novel approaches for inverter-based bottom-up system restoration in a communication-free paradigm.

24 POWER TRANSMISSION AND DISTRIBUTION↗

SOLAr Critical Infrastructure Energization (SOLACE): Leveraging Distributed Energy Resources to Provide Local Power

This document is a technical report based on a large-scale DOE-funded project conducted between 2019 and 2022. The project, called SOLAr Critical infrastructure Energization (SOLACE), is aimed at leveraging distributed energy resources (DERs) to provide local power to communities, feeders, or other regions. The project included a particular focus on high-value critical loads such as municipal water supply, telecommunication hubs, and disaster shelters. The key developments of the project were: (1) A comprehensive pre-event power system analysis methodology that identifies and characterizes the viable local power options. (2) A DMS-based example control system for activating and operating the local power solution during a time of crisis. (3) Grid-forming inverter technology to enable isolated local power operation and black-starting. (4) Cyber-security considerations for isolated systems when wider-area communication may be offline. This report describes the overall process that identifies and assesses the viable DER-based local power solutions for a given facility, region, or community. The report documents the process, including the key analysis steps, tools required, data requirements, and recommended pass/fail criteria for each step. It also provides a sample implementation of this process through a test case. Finally, it provides details of how a viable pre-event plan can be selected and activated at go-time when an event has occurred.

14 SOLAR ENERGY↗

Intelligent, grid-friendly, modular extreme fast charging system with solid-state DC protection

The development of electric vehicle (EV) charging infrastructure is crucial for the widespread adoption of electric transportation. However, implementing such infrastructure is a complex task that requires consideration of factors such as space limitations, adherence to industry standards, grid capacity, and other technical and policy issues. This project seeks to create a framework for the efficient design of compact medium voltage (MV) extreme fast charging (XFC) stations for EVs. The station design involves the use of a solid-state transformer (SST) that connects to the MV distribution network, delivering power to a shared DC bus. This innovative approach eliminates the need for a step-down transformer to provide low-voltage service by connecting directly to the MV distribution network. Eliminating the low-frequency transformer not only reduces the system footprint and losses but also eliminates inrush currents during grid black-start. Additionally, placing power electronics directly on the distribution system allows for high-bandwidth filtering and power factor correction. The inclusion of a shared DC bus enables multiple charging dispensers and DC storage/generation units to connect, forming a DC microgrid. This setup facilitates power sharing with minimal conversion stages. The project showcases a DC distribution network protected by intelligent solid-state (SS) DC circuit breakers (DCCB) capable of isolating the smallest section of the faulted circuit much faster than existing mechanical solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

Final Technical Report of a Feasibility Investigation of a Hydropower Flexibility Upgrade Kit

The project studied the feasibility of a concept for a flexibility upgrade kit called h-Dynamyk to improve the flexibility of U.S. hydropower plants and assessed its potential impact on the U.S. hydropower industry. This concept addresses the growing need for grid flexibility amid rising renewable energy adoption, such as wind and solar, which often introduce intermittency. The upgrade kit is intended to address challenges posed by aging turbine designs in meeting modern grid demands for flexibility services like frequency response, voltage control, spinning reserve, and black-start capabilities. Key features of the h-Dynamyk kit include siphon turbine assemblies, medium-voltage variable frequency drives (VFDs), and smart controls integrated with plant systems to optimize operations and extend equipment life. This nine-month discovery project successfully achieved its objectives by defining a baseline design and performance metrics for the h-Dynamyk flexibility upgrade kit, analyzing this baseline, and incorporating lessons learned from this analysis into a modified set of metrics and recommendations for future design and testing, which were further guided by field site studies.

13 HYDRO ENERGY↗

Regional Power System Black Start with Run-of-river Hydropower Plant and Battery Energy Storage

Battery energy storage systems (BESSs) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various critical services to the power grid. This paper presents the real-world experience of using a megawatt-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to restore a regional power system. To demonstrate this, we carry out power-hardware-in-the-loop experiments integrating an actual GFL- or GFM-controlled BESS and a load bank. Both the simulation and experimental results presented in this paper show the different roles of GFL- or GFM-controlled BESS in power system black starts. The results provide further insight for system operators on how GFL- or GFM-controlled BESS can enhance grid stability and how an ROR hydropower plant can be converted into a black-start-capable unit with the support of a small-capacity BESS. The results show that an ROR hydropower plant combined with a BESS has the potential of becoming one of enabling elements to perform bottom-up black-start schemes as opposed to conventional bottom-down method, thus enhancing the system resiliency and robustness.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Generic characterization of electrical test benches for AC- and HVDC-connected wind power plants

The electrical test and assessment of wind turbines go hand in hand with standards and network connection requirements. In this paper, the generic structure of advanced electrical test benches, including grid emulator or controllable grid interface, wind torque emulator, and device under test, is proposed to harmonize state-of-the-art test sites. On the other hand, modern wind turbines are under development towards new features, concerning grid-forming, black-start, and frequency support capabilities as well as harmonic stability and control interaction considerations, to secure the robustness and stability of renewable-energy-based power systems. Therefore, it is necessary to develop new and revised test standards and methodologies to address the new features of wind turbines. This paper proposes a generic test structure within two main groups, including open-loop and closed-loop tests. The open-loop tests include the IEC 61400-21-1 standard tests as well as the additional proposed test options for the new capabilities of wind turbines, which replicate grid connection compliance tests using open-loop references for the grid emulator. In addition, the closed-loop tests evaluate the device under test as part of a virtual wind power plant and perform real-time simulations considering the grid dynamics. The closed-loop tests concern grid connection topologies consisting of AC and HVDC, as well as different electrical characteristics, including impedance, short-circuit ratio, inertia, and background harmonics. The proposed tests can be implemented using available advanced test benches by adjusting their control systems. The characteristics of a real power system can be emulated by a grid emulator coupled with real-time digital simulator systems through a high-bandwidth power-hardware-in-the-loop interface.

17 WIND ENERGY↗

Interconnection and Interoperability Requirements of Hydrogen Assets to Enable Grid Integration

Traditionally, the inverters used for distributed energy resources (DERs) including solar, energy storage and hydrogen fuel cells are grid following assets. Grid following assets track real power and reactive power setpoints decided by either a local autonomous controller or a remote controller like a microgrid controller. In the past five years, multiple challenges have increased the need for grid forming inverters that can interface to a wide variety of energy resources. These grid forming inverters are becoming critical assets for power systems to enable the replacement of existing rotational machines and provide grid services such as grid resiliency services and black-start. Hydrogen assets (fuel cells) have the potential to successfully replace rotating machines and act as voltage and frequency master by leveraging the long-duration and seasonal energy storage capabilities of hydrogen technologies. This poster presents the progress made in budget period 1 of the proposed work. We will leverage an existing ARIES platform experimental setup to run power-hardware-in-the-loop and controller-hardware-in-the-loop experiments with grid forming fuel cell inverters to develop and document the standardization requirements.

electrolyzer↗

Large-Signal Stability Improvement of Parallel Grid-Forming Inverter-Driven Black Start: Preprint

With the rapid increase of inverter-based resources in modern grids, advanced grid-forming (GFM) inverter capa- bilities, such as system restoration and operation under faults, are urgently needed to realize power electronics-dominant grids at scale. One such capability is inverter-driven black start using GFM inverters. This paper analyzes the ability of two recently proposed advanced GFM controls to help GFM inverters sustain system-wide, off-nominal conditions and remain synchronized until they can overcome the momentary overloading as more GFMs join the process without generator sequence coordination or communications and finally stabilize the grid. Through an extensive set of 1,200 full-order electromagnetic transient simu- lations, we evaluate the black-start process while employing the various GFM inverter controls. The results show that the GFM current limiter and primary control have a significant impact on the stability of the system during dynamic operating conditions and thus impact the success of inverter-driven system restoration.

current limit↗

Parallel Grid-Forming Inverter-Driven Black Start: Power-Hardware-in-the-Loop Validation: Preprint

With power systems encountering increasing deployment levels of inverter-based resources (IBRs), system restoration using grid-forming (GFM) IBRs has gained attention. Engineered to establish grid voltages in the absence of a stiff grid, black-start-capable GFM IBRs are expected to enhance power system resilience by playing a critical role in bottom-up system restoration. This paper experimentally studies the feasibility of the novel approach through power-hardware-in-the-loop (PHIL) testing and validation with a commercial GFM inverter. The PHIL test setup demonstrates an inverter-driven black start of a 5-MW unbalanced distribution feeder where two GFM inverters collectively black start the feeder: one is a commercial hardware GFM inverter interacting through the PHIL interface, and the other is a software GFM emulated by a real-time simulation with full electromagnetic transient (EMT) models. Both GFM inverters are equipped with negative-sequence voltage control to suppress the voltage imbalance resulting from the unbalanced loading, allowing us to study the dynamic interactions between the GFMs with their control parameters unknown. To evaluate the dynamic behavior of the GFM inverters under the entire black-start process, the EMT model of the distribution system details the transformer and motor dynamics to emulate their inrush and startup behaviors. It abstracts conventional grid-connected inverter dynamics, i.e., grid-following inverters. Oscilloscope measurements of the hardware GFM inverter are also presented for critical steps. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Techno-Economic Analysis of a Nuclear Reactor System coupled with a Liquid Metal Battery

There is a need for nuclear reactor systems to become more dynamic as defossilization and renewable energy sources continue to reshape the energy grid. One option to meet these changing demands is to pair the reactor with an energy storage system. This work details a technoeconomic analysis and sensitivity analysis of a high temperature gas cooled microreactor, supercritical carbon dioxide power cycle, and liquid metal battery. Dynamic modeling has shown that these three systems compliment each other to provide load following and black-start capabilities to the grid. Current cost estimates for installing the systems yield a competitive levelized cost of electricity and levelized cost of storage, indicating that such a combined system may be economically viable as technological advances lead to them being technically feasible.

25 ENERGY STORAGE↗

Microgrid Black Start Challenges: The Role of Grid-Forming Inverters

Grid-forming (GFM) inverters are becoming increasingly important for future power systems, particularly in establishing and restarting microgrids after blackouts. The use of GFM inverters enables microgrids to operate independently of utility power and provide key advantages over synchronous generators in black start scenarios, including rapid startup and stable voltage and frequency support for critical loads. However, inverter-driven black start introduces unique challenges and operational considerations. This article examines key challenges and solutions, emphasizing inverter design, control strategies, and microgrid system requirements. Drawing on analysis, simulation, and experimental results, this article highlights the central role of GFM inverters in ensuring reliable and resilient microgrid operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.