A Measurement-Based Adaptive Voltage Regulation Method Considering Topology Changes

This paper proposes an online adaptive data-driven distributed energy resource (DER) dispatch optimization method for voltage control considering topology changes. By using a local sensitivity factor (LSF)-enabled voltage control, traditional DER control can be reformulated into a linear programming (LP) problem, leading to faster computation speeds. Power injection alteration and topology changes are two common operational changes in the distribution network that can affect the LSF and voltage control performance. To address this issue, a robust estimation method is developed to adjust the sensitivity matrix at each time step for the time-varying power injection changes. When topology changes occur, only the allocated predominant LSF submatrices are updated based on measurement data, allowing for a fast adaptation to the system reconfiguration. Results obtained from a real distribution feeder in Southern California demonstrate its robustness as compared to traditional volt-var control and constant LSF matrix dispatch control methods.

DERs↗

Effects of voltage control in utility interactive dispersed storage and generation systems

When a small generator is connected to the distribution system, the voltage at the point of interconnection is determined largely by the system and not the generator. The effect on the generator, on the load voltage and on the distribution system of a number of different voltage control strategies in the generator is examined. Synchronous generators with three kinds of exciter control are considered, as well as induction generators and dc/ac inverters, with and without capacitor compensation. The effect of varying input power during operation (which may be experienced by generators based on renewable resources) is explored, as well as the effect of connecting and disconnecting the generator at ten percent of its rated power. Operation with a constant slightly lagging factor is shown to have some advantages.

Kirkham, H.↗

Quantitative Trade-Off in Distributed Secondary Control for Autonomous AC Microgrids

In this paper, we propose to quantify the trade-off between voltage regulation and reactive power sharing in autonomous AC microgrids with distributed secondary control. It is known that voltage regulation and reactive power sharing in droop-controlled autonomous AC microgrids are two conflicting control objectives that present a natural trade-off between voltage regulation towards the voltage magnitude reference and reactive power sharing accuracy. This trade-off is commonly shown qualitatively without sufficient quantification. In this work, to quantify the trade-off between the two objectives, we focus on distributed secondary control and utilize regression and polynomial surface fitting to identify the requisite parameter area to satisfy the predefined error bands for voltage magnitude regulation and reactive power sharing. Extensive case studies are presented to validate the proposed method.

autonomous AC microgrids↗

Safe Deep Reinforcement Learning for Active Distribution System Model Predictive Control with EVs and DERs

The temporal and spatial mismatch between PV generation and electric vehicle (EV) charging and discharging may cause voltage violations in active distribution networks. Despite the widespread use of deep reinforcement learning (DRL) in power system optimization and control, it lacks guarantees on constraint satisfaction during both training and deployment. This paper proposes a Lagrangian-based safe DRL approach for model predictive control (MPC) of active distribution systems with large-scale integration of PVs, EVs, and energy storage systems (ESSs). A Transformer-LSTM time-series model is proposed to forecast EV charging demand, which is then formulated as a constraint to ensure charging requirements are met. Using this prediction, a Lagrangian-based safe soft actor-critic (SAC) framework is developed for real-time control in a three-phase unbalanced distribution system, enforcing voltage safety constraints while optimizing the cumulative net reward. By integrating the forecasting model with multi-period constraints, the proposed framework jointly coordinates PV systems, EV charging and discharging, and ESS scheduling within the MPC horizon. Numerical experiments on a modified IEEE 123-bus system with real-world data show that, under a high PV penetration scenario, the proposed method increases the net reward by 30.74% and reduces average voltage violations from 0.0011 p.u. to 0.0002 p.u. compared with standard SAC. Compared with the optimal power flow (OPF) approach, it achieves similar voltage security while yielding lower line losses. It also maintains real-time control capability, reducing operation latency to 53.21 ms per 15-minute control interval. The proposed method remains effective under varying PV/EV penetrations and load conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Swarm Intelligence Based Optimal Design of Local Volt/Var Control Function for Distributed Energy Resources

The increasing penetration of renewable based distributed energy resources (DERs) in distribution network (DN) leads to larger and more frequent voltage variation in distributions network (DN), thus posing challenges on voltage control. Real-time local voltage control method is a promising solution for the above issue. However, the local voltage control function needs to be customized and optimized according to real distribution system condition. In this paper, a swarm intelligence based Volt/Var control optimal design method (SO-VVC) is proposed to optimize the control function. Compared with existing approaches, the proposed method can not only represent the nonlinear behaviour of power flow but is also computation efficient. The performance of the proposed SO-VVC is demonstrated by case studies on a modified IEEE-123 bus system.

Zhang, Zhengfa [University of Tennessee, Knoxville↗

Demonstrating the data center as a flexible grid asset using a C-HIL setup

Increasing data center demand is outpacing grid infrastructure development. Artificial intelligence workloads and hyperscale cloud growth are creating unprecedented demand for power, while traditional grid expansion faces multiyear development timelines. Verrus is developing an innovative datacenter solution for this challenge, data centers that act as active grid-supportive assets rather than passive loads. Our approach integrates a novel grid-aware power flow management system with battery energy storage systems(BESS) into a microgrid-controlled, medium-voltage power distribution architecture that delivers critical capabilities, such as: * Fast response to grid disturbances such over/ under voltage or over/ under frequency * Demand flexibility that can service requests from the utility within 10 s * Uninterrupted transition to islanded operation during grid outages * Continuous uptime assurance for compute loads while maintaining all customer service level agreements. Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), these capabilities were validated using NREL's Advanced Research on Integrated Energy Systems (ARIES) virtual emulation environment to model a 70-MW grid-interactive data center. This paper outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can provide both critical load resilience and ancillary grid support without compromising uptime requirements. Specifically, we present a digital real time simulation of a 70 MW data center integrated with a physical microgrid controller, and demonstrate the data center response in the event of a grid voltage and frequency event, utility demand response request and utility outage.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distributed Coordination of Networked Microgrids for Voltage Support in Bulk Power Grids

The increasing deployment of distributed energy resources (DERs) and microgrids (MGs) in power distribution systems has enabled the adjustment of reactive power consumption as seen at the substation, which can be used to provide voltage support for the bulk power system (BPS). Leveraging this new capability will provide greater resiliency to the power system as a whole. Here, the goal of this paper is to develop and compare three different algorithms, namely distributed optimal power flow, distributed consensus algorithm, and fully decentralized collaborative autonomy for unbalanced distribution systems for microgrid coordination. These algorithms use networked MGs to support the BPS voltage when a contingency at the bulk grid results in abnormally low voltages, which may be a precursor to voltage collapse. Our comparative analysis includes both qualitative and quantitative assessments of the three algorithms and a discussion of the trade-offs between the decentralized and distributed methods in normal and disrupted conditions. Each algorithm was evaluated on the modified IEEE 13-bus system and a real power distribution system at Chattanooga, Tennessee, that encompasses more than 4500 buses. Each algorithms excels differently and may be suited for different scenarios depending on the condition, operations, and priorities of the power and communication systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling Framework for Data Center

This chapter highlights the critical need for advanced modeling of data centers due to their rapidly increasing energy consumption and impact on grid reliability. Driven by the demand for AI applications, data centers are projected to consume a significant portion of US energy by 2028, putting stress on an already challenged power grid. The chapter emphasizes the importance of "fast" time-scale models to understand the dynamic interactions between data centers and the grid, especially given the rapid power fluctuations of AI workloads. It outlines a modeling framework that includes both offline and real-time EMT domain simulations, detailing the necessary representations for various components like utility interfaces, transformers, IT loads, UPS, cooling loads, Battery Energy Storage Systems (BESS), generators, protection systems, and higher-level control systems. While standard simulation tools like PSCAD offer basic models, custom development is often required to accurately capture the unique and fast-changing behaviors of modern data centers. The chapter also discusses key metrics and test cases for validating these models, focusing on transient load responses, protection relay coordination, and demand flexibility. Finally, it addresses the challenges of modeling large-scale data centers, such as computational complexity and the trade-off between model fidelity and practicality, suggesting hybrid modeling approaches as a solution. The overarching goal is to create a robust framework that helps assess data center impacts on grid stability, identify vulnerabilities, and inform the development of standards for reliable integration of these large loads into the bulk power system.

25 ENERGY STORAGE↗

A bi-level advanced control framework for large-scale control of buildings with system-level impact

Increased electricity consumption combined with new forms of generation is testing the reliability of our grid infrastructure. This work describes a method to improve the reliability of the grid through large-scale advanced building control. This paper develops a bi-level distributed control framework to shift the load of 153 buildings to achieve a system-level objective of tracking a power reference signal. This bi-level control is based on the previously-developed ANPV-MPC, a predictive controller that uses a Bayesian neural network to generate an accurate control model and adapt to changing conditions over time. By shifting the building electricity demand to better match the available power, the grid system supplying the buildings is more reliable as evidenced by the analysis of node voltages across an IEEE 13-bus distribution system. The proposed bi-level control framework tracks the system-level power reference with enough accuracy to regulate node voltages across the IEEE 13-bus distribution system within ANSI limits of ±5%. Additionally, the adaptive nature of ANPV-MPC allows each building across the system to adapt to changing conditions, further amplifying the system-level reliability.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Data-Driven Voltage Regulation of Distribution Grid Using Nonlinear Autoregressive Model with Exogenous Inputs (NARX)

This article proposes data-driven control via a nonlinear autoregressive model with exogenous inputs (NARX) for real-time voltage regulation of a modified feeder using reactive power sources. Traditional voltage control strategies rely on rule-based heuristics or optimization techniques, which often require detailed system models and extensive computational resources. The NARX-based controller learns system dynamics from historical data and predicts optimal reactive power dispatch in real-time for voltage correction. The proposed approach is evaluated on a power system feeder model under varying load and network conditions. Simulation results demonstrate that the NARX-based controller achieves improved voltage regulation, offering higher adaptability to system fluctuations. This study highlights the potential of data-driven control for enhancing the reliability of power distribution networks.

Donge, Vrushabh [ORNL] (ORCID:0000000306062803)↗

Physics-Informed Graph Neural Networks for Collaborative Dynamic Reconfiguration and Voltage Regulation in Unbalanced Distribution Systems

Network reconfiguration has long been employed as a strategic approach to minimize power distribution system losses and effectively regulate voltage levels. Tap-changing voltage regulators are also critical for controlling bus voltages, especially in accommodating the increasing integration of distributed energy resources (DERs) with intermittent outputs. This paper introduces novel methodologies to address the challenges of dynamic reconfiguration and optimal tap setting in unbalanced three-phase distribution systems. We propose an approximated mixed-integer quadratically constrained program (MIQCP) to model dynamic reconfiguration, along with a pioneering formulation for voltage regulator (VR) tap-setting based on Special Ordered Set type 1 (SOS1). To mitigate computational complexity, we propose a physics-informed spatial-temporal graph convolutional network (STGCN) with an integrated link classifier. The proposed approach enables efficient solution generation by fixing specific variables in the MIQCP instance and solving the simplified sub-MIP using an MIP solver. Numerical studies demonstrate the superior prediction accuracy of our STGCN model compared to baseline neural network models, resulting in reduced DER curtailment and voltage deviation with shorter computation time.

dynamic reconfiguration↗

Optimization-Based Dynamic Voltage Support of Microgrids Using Energy Storage Systems

A microgrid network is characterized by a high R/X ratio, making the voltage more sensitive to active power changes compared to bulk power systems, where the voltage is regulated primarily by reactive power. Due to its sensitivity, voltage control approaches for microgrids should also consider the active power input coupling, making it very different from conventional power systems. Additionally, as the energy costs associated with active and reactive powers are different and the operational conditions of microgrids connected to active distribution systems vary over time, the ideal controller to provide voltage support must be flexible enough to handle these technical and operational constraints. This paper proposes a model predictive control approach to provide dynamic voltage support using energy storage systems. This approach uses a simplified predictive model of the system to solve the model predictive control problem. By proper selection of model predictive control weighting parameters, the quality of service provided can be adjusted to achieve the desired performance. A simulation study in MATLAB/Simulink validates the proposed approach for the Cordova, Alaska microgrid. Results show that the performance of the voltage support can be adjusted depending on the choice of weight and constraints of the controller.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Sensitivity-based voltage constraints for optimal power flow in low-voltage distribution feeders

The optimal power flow (OPF) problem for distribution systems can include network details down to the low-voltage (LV) points of interconnection of individual customers. This paper addresses the implementation of voltage magnitude constraints, and sets forth a practicable approach for capturing the effects on voltage from the switching behavior of loads (e.g., heat pumps, air conditioners, water heaters, or pool pumps) and from the variability of renewable generation (e.g., rooftop solar). The proposed method adjusts the OPF voltage constraints based on forecasts of load and generation upper and lower bounds, in conjunction with sensitivity factors derived from the power flow equations. An illustrative OPF formulation is also provided, which incorporates transformer models that include core loss. We demonstrate that accurate modeling of these LV network components is critical to avoid voltage violations at customer points of interconnection. Furthermore, the ideas are validated through numerical case studies on a realistic distribution feeder.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Photovoltaic concentrator pointing dynamics and plasma interaction study

The objectives of this experiment are to use the Space Technology Experiments Platform (STEP) system to demonstrate the viability of concentrator photovoltaic arrays by: (1) configuring a deployable mast on the STEP pallet with concentrator mass models and some active photovoltaic modules; (2) measuring the array pointing dynamics under normal rotation as well as disturbance conditions; (3) performing an array plasma interaction experiment to determine the steady-state plasma losses under various voltage conditions; and (4) providing active distributed control of the support truss to determine the improvement in dynamic response. Experiment approach and test control and instrumentation are described.

Stern, T. G.↗

Cyberattack Detection and Mitigation on Central Volt‐VAr Using Circuit Law and Machine Learning

ABSTRACT In a distribution grid, voltage is maintained within a nominal range through a Volt‐VAr function that controls capacitor banks, reactive power of distributed energy resources (DER), and on‐load tap changers (OLTC). Availability of communications helps with the implementation of central Volt‐VAr control; however, it also opens the system to cyberattacks, causing voltage disturbances. Previous work has shown the adverse impacts of false data injection (FDI) on the central Volt‐VAr control; however, very few works have studied methods to detect and mitigate FDI on Volt‐VAr control. This paper addresses gaps in the detection and mitigation of FDI on the measurement packets of a central Volt‐VAr control. This work uses a two‐stage algorithm for cyberattack detection since the accuracy of a single‐stage machine learning (ML)–based detection method decreases while dealing with unseen data. The first stage is based on the verification of measurements against circuit laws, and the second stage utilizes a tree search algorithm and an ML method to detect the falsified data. This paper compares long short‐term memory (LSTM) and bidirectional LSTM (BiLSTM) as the employed ML algorithms. Finally, the mitigation algorithm replaces the falsified data with the estimated output of the ML algorithm. The effectiveness of the proposed method is tested for several cases using the IEEE 13‐bus test system in PSCAD software.

Beikbabaei, Milad [Bradley Department of Electrica↗

Scheduler Modeling of Distributed Energy Resources for Providing Ancillary Services

Distribution energy resources (DERs) have been integral components of modern power systems, and their capability to provide grid services has been widely studied. To promote the deployment of these resources in providing grid services in real-world utility operations, this paper proposes a day-ahead scheduler model for a distribution system connected DER plant. A certain amount of generation capacity of this DER plant is reserved for frequency services, and some ancillary services for the distribution system-including peak load reduction, voltage regulation, and power factor control-are integrated into the model. The model is tested on a real-world distribution system. From the simulation results, the energy and reserve schedule of the solar photovoltaic (PV) unit and battery energy storage system (BESS) can be determined, and voltage and power factor are well maintained. Additionally, in order to demonstrate the specific characteristics of the co-located and hybrid operation modes for the PV and BESS, these two modes are analyzed both theoretically and through real-time simulation. Simulation results show that most of PV's variability is transferred to the net power in the co-located mode, whereas it is transferred to the BESS in the hybrid mode. This proposed scheduler model and the comparison of co-located and hybrid modes can provide practical guidance for the applications of DER plant in the real-world utility.

14 SOLAR ENERGY↗

Electro-Optical High-Voltage Sensors

Electro-optical sensors for measuring high voltages developed for use in automatically controlled power-distribution systems. Sensors connected to optoelectronic interrogating equipment by optical fibers. Because sensitive material and optical fibers are all dielectric, no problem in electrically isolating interrogating circuitry from high voltage, and no need for voltage dividers. Sensor signals transmitted along fibers immune to electromagnetic noise at radio and lower frequencies.

Gottsche, Allan↗