Real-Time Power Management for Microgrids With Dynamic Boundaries and Multiple Source Locations
Not Available
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not Available
Extreme weather events have led to long-duration outages in the distribution system (DS), necessitating novel approaches to blackstart and restore the system. Existing blackstart solutions utilize blackstart units to establish multiple microgrids (MGs), sequentially energize non-blackstart units, and restore loads. However, these approaches often result in isolated MGs. In DERs-aided blackstart, the continuous operation of these MGs is limited by the finite energy capacity of commonly used blackstart units like battery energy storage (BES)-based gridforming inverters (GFMIs). To address this issue, this article proposes a holistic blackstart and restoration framework that incorporates synchronization between dynamic MGs and the entire DS with the transmission grid (TG). To support synchronization, we leveraged virtual synchronous generator-based control for GFMIs to estimate their frequency response to load pick-up events using only initial/final quasi-steady-state points. Subsequently, a synchronization switching condition is developed to model synchronizing switches, aligning them seamlessly with a linearized branch flow problem. Finally, we designed a bottomup blackstart and restoration framework that considers the switching structure of the DS, energizing/synchronizing switches, DERs with grid-following inverters, and BES-based GFMIs with frequency security constraints. In conclusion, the proposed framework is validated in IEEE-123-bus system, considering cases with two and four GFMIs under various TG recovery instants.
Microgrids have physical, electrical, and logical (data, network, and ownership) boundaries. To power unserved customer loads during an outage, microgrids can extend the traditional operational boundaries. This can become complex when considering microgrid-to-microgrid (M2M) interactions where sensitive information such as competitive microgrid operational data is not shared. This work proposes an optimization method coordinated between microgrid controllers and distribution management systems that limits data sharing. The method involves a competitive bidding strategy that maximizes unserved load coverage while minimizing resource utilization and sensitive operational data sharing among entities. The work is validated on a two-microgrid system with photovoltaic and energy storage systems and curves of load derived from real world residential buildings datasets. Results show that the proposed method, when applied for three distinct use cases of energy storage sufficiency to cover the predefined boundary and/or the expanded boundary, can successfully select and bid the available load coverage.
Not Available
Existing generator parameterization methods, typically developed for large turbine generator units, are difficult to apply to small kW-level diesel generators in microgrid applications. Here, this article presents a model parameterization method that estimates a complete set of kW-level diesel generator parameters simultaneously using only load-step-change tests with limited measurement points. This method provides a more cost-efficient and robust approach to achieve high-fidelity modeling of diesel generators for microgrid dynamic simulation. A two-stage hybrid box-constrained Levenberg-Marquardt (H-BCLM) algorithm is developed to search the optimal parameter set given the parameter bounds. A heuristic algorithm, namely Generalized Opposition-based Learning Genetic Algorithm (GOL-GA), is applied to identify proper initial estimates at the first stage, followed by a modified Levenberg-Marquardt algorithm designed to fine tune the solution based on the first-stage result. The proposed method is validated against dynamic simulation of a diesel generator model and field measurements from a 16kW diesel generator unit.
Explore the source record for details and available documents.
Microgrids have repeatedly demonstrated the ability to provide uninterrupted service to critical end-use loads during normal outages, severe weather events, and natural disasters. While their ability to provide critical services is well documented, microgrids present a more dynamic operational environment than grid-connected distribution systems. The dynamics of a microgrid are commonly driven by the high inertia of rotating generators, which are common in many microgrids. In such high-inertia systems, the impact of end-use load dynamics are often not examined. However, with the increased penetration of inverter-based generation with little or no inertia, it is necessary to consider the impact that the dynamics of the end-use loads have on the operations of microgrids, particularly for a resiliency-based operation. These operations include, but are not limited to, switching operations, loss of generating units, and the starting of induction motors. This paper examines the importance of including dynamic models of the end-use load when evaluating the operations of low inertia microgrids, and shows that by properly representing their behavior, it is possible to cost effectively size equipment while supporting resilient operations of critical end-use loads.
Dynamic state estimation (DSE) is a generalization of differential protection that offers a reduced likelihood of misoperation, particularly in the case of devices with nonlinear characteristics such as transformers which are being energized. It is also useful in cases where distance protection performs poorly, such as transmission lines with series compensation or mutually coupled transmission lines. DSE has been previously applied to microgrid branch protection. This study investigates the use of DSE for protection of radial portions of a microgrid or distribution system. This can be a challenge in microgrids or distribution systems with distributed generation on account of lack of fault current from inverter-interfaced generation, varying fault current between grid- connected and islanded modes, the potential for normally-meshed operation and unbalanced operation due to single-phase loads. Admittance relaying has been investigated as a solution for protection of microgrids, though it has been observed to have issues with grounded-wye connected loads, and additional relaying is necessary to prevent misoperation.
This white paper focuses on "advanced microgrids," but sections do, out of necessity, reference today's commercially available systems and installations in order to clearly distinguish the differences and advances. Advanced microgrids have been identified as being a necessary part of the modern electrical grid through a two DOE microgrid workshops, the National Institute of Standards and Technology, Smart Grid Interoperability Panel and other related sources. With their grid-interconnectivity advantages, advanced microgrids will improve system energy efficiency and reliability and provide enabling technologies for grid-independence to end-user sites. One popular definition that has been evolved and is used in multiple references is that a microgrid is a group of interconnected loads and distributed-energy resources within clearly defined electrical boundaries that acts as a single controllable entity with respect to the grid. A microgrid can connect and disconnect from the grid to enable it to operate in both grid-connected or island-mode. Further, an advanced microgrid can then be loosely defined as a dynamic microgrid.
Methods, systems, and computer readable mediums for protecting and controlling a microgrid with a dynamic boundary are disclosed. One method includes detecting a fault in a microgrid that includes a dynamic point-of-common-coupling (PCC), in response to determining that the microgrid is operating in a grid-connected mode, isolating the fault by tripping a microgrid side smart switch and a grid side smart switch that are located immediately adjacent to the fault, initiating the reclosing of the grid side smart switch, and initiating the reclosing for the microgrid side smart switch via resynchronization if the grid side smart switch is successfully reclosed, and in response to determining that the microgrid is operating in an islanded mode, isolating the fault by tripping a microgrid side smart switch that is located immediately adjacent to the fault, and initiating the reclosing of the microgrid side smart switch.
Here this paper presents autonomous restoration of networked microgrids using distributed energy resources (DERs), inverter-based resources (IBRs) in general, and controllable assets of intelligence without communication to achieve a extremely resilient power system restoration. The main innovation of this work lies in use of real-time smart sensing and decision making that enable autonomous recombination of islanded microgrids, which are individually black-started by local grid-forming (GFM) inverter units. The smart circuit breakers (SCBs) designed and demonstrated here play critical roles in the restoration process to achieve autonomy; the autonomous restoration scheme is not pre-engineered and may be subject to encounter overloading, live or downed segments as the boundary of the microgrids dynamically expands without prior knowledge and only with local measurement. We demonstrate autonomous microgrid restoration both in simulation of a modified IEEE 13-bus system, and in a hardware testbed comprising 24 GFM-IBRs and 6-SCBs, depicting several scenarios to evaluate their functionalities and interoperability. This work validates high potential of extremely resilient microgrid using novel approaches for inverter-based bottom-up system restoration in a communication-free paradigm.
The development of smart grid technologies has resulted in increased interdependence between power and communication systems. Many of the operations in the existing power system rely on a stable and secured communication system. For electrically weak systems and time‐critical applications, this reliance can be even greater, where a small degradation in communication performance can degrade system stability. However, despite inter‐dependencies between power and communication systems, only a few studies have investigated the impacts of communication system performance on power system dynamics. This study investigates the dependencies of power system dynamics operations on a communication system performance. First, a detailed, dynamic networked microgrid model is developed in the GridLAB‐D simulation environment, along with a representative multi‐traffic, multi‐channel, multi‐protocol communication system model, developed in the network simulator (ns‐3). Second, a hierarchical engine for large‐scale infrastructure co‐simulation framework is developed to co‐simulate microgrid dynamics, its communication system, and a microgrid control system. The impact of communication system delays on the dynamic stability of networked microgrids is evaluated for the loss of generation using three use‐cases. While the example use‐cases examine microgrid applications and the impact to resiliency, the framework can be applied to all levels of power system operations.
icrogrids can act as emergency sources to serve critical loads when utility power is unavailable. This paper proposes a resiliency-based methodology that uses microgrids to restore critical loads on distribution feeders after a major disaster. Due to limited capacity of distributed generators (DGs) within microgrids, dynamic performance of the DGs during the restoration process becomes essential. In this paper, the stability of microgrids, limits on frequency deviation, and limits on transient voltage and current of DGs are incorporated as constraints of the critical load restoration problem. The limits on the amount of generation resources within microgrids are also considered. By introducing the concepts of restoration tree and load group, restoration of critical loads is transformed into a maximum coverage problem, which is a linear integer program (LIP). The restoration paths and actions are determined for critical loads by solving the LIP. A 4-feeder, 1069-bus unbalanced test system with four microgrids is utilized to demonstrate the effectiveness of the proposed method. The method is applied to the distribution system in Pullman, WA, resulting in a strategy that uses generators on the Washington State University campus to restore service to the Hospital and City Hall in Pullman.
The proliferation of inverter-based generation and advanced sensing, controls, and communication infrastructure have facilitated accelerated deployment of microgrids. A coordinated network of microgrids can maintain reliable power delivery to critical facilities during extreme events. Low-inertia offered by the power-electronics–interfaced energy resources, however, can present significant challenges to ensuring stable operation of the microgrids. In this work, distributed small-signal stability conditions for inverter-based microgrids are developed that involve the droop-controller parameters and the network parameters (e.g. line impedances, loads). The distributed closed-form parametric stability conditions derived in this paper can be verified in a computationally efficient manner, facilitating reliable design and operations of networks of microgrids. Dynamic phasor models have been used to capture the effects of electromagnetic transients. Furthermore, numerical results are presented, along with PSCAD simulations, to validate the analytical stability conditions. Effects of design choices, such as the conductor types, and inverter sizes, on the small-signal stability of inverter-based microgrids are investigated to derive useful engineering insights.
Here, this paper presents a refined quantum Harrow Hassidim Lloyd (HHL) algorithm for microgrid control. The first novelty of the developed method is that a mapping shift function enables the original HHL algorithm to handle general linear equations with non-singular and indefinite matrix. Second, a method of Matrix Extension for Amplifying Sampling Probabilities of Intended Solution (ME-ASPI) is proposed to design the reformulated linear algebraic equations, allowing for improved sampling efficiency of the quantum tomography in the refined HHL algorithm. Then, we applied the method to solve the model predictive control (MPC) problem in nonlinear dynamical microgrids. Specifically, with the ME-ASPI method, the refined HHL algorithm can effectively obtain the intended partial optimal control inputs for MPC. The optimization of quadratic programming problem in each time step of MPC is transformed into a linear system problem, which is addressed by the proposed quantum solver through using only partial information, with the time complexity improved from $\mathscr{O}(\mathscr{N}^{2.37286})$ classically to $\mathscr{O}(\mathscr{N}^{2} log \mathscr{N}$ x $p$ log $p)$ in quantum. Numerical examples have validated the effectiveness of the refined HHL algorithm with the proposed mapping function and the ME-ASPI method. By leveraging quantum properties, the proposed method provides a hybrid quantum–classical framework for microgrid control. This generic method can also potentially tackle many other challenges in analyzing and controlling general complex engineered systems.
In this paper we propose a co-design of the secondary frequency regulation in systems of AC microgrids and its cyber security solutions. We term the secondary frequency regulator a Micro-Automatic Generation Control (μ AGC) for highlighting its same functionality as the AGC in bulk power systems. We identify sensory challenges and cyber threats facing the μ AGC. To address the sensory challenges, we introduce a new microgrid model by exploiting the rank-one deficiency property of microgrid dynamics. This model is used to pose an optimal μ AGC control problem that is easily implemented, because it does not require fast frequency measurements. An end-to-end cyber security solution to the False Data Injection (FDI) attack detection and mitigation is developed for the proposed μ AGC. The front-end barrier of applying off-the-shelf algorithms for cyber attack detection is removed by introducing a data-driven modeling approach. Finally, we propose an observer-based corrective control for an islanded microgrid and a collaborative mitigation scheme in systems of AC microgrids. We demonstrate a collaborative role of systems of microgrids during cyber attacks. Furthermore, the performance of the proposed cyber-resilient μ AGC is tested in a system of two networked microgrids.
Enormous challenges are inherent in the operation of modern distribution grids. In particular, distribution feeders can be severely compromised under extreme conditions such as large-scale weather events (e.g., hurricanes, floods, and other types of natural disasters). To combat this problem, they turn to local energy support from distributed energy resources, such as solar and wind, marine hydrolinetic (MHK), and other types of energy. In this report, we investigate the actual characteristics of MHK resources to enhance coastal community resiliency. Two typical types of MHK resources (i.e., wave and tidal resources) illustrate the coastal resilience enhancement framework. By identifying their operational characteristics, such as target time-scales and potential power generation variations, we detail a holistic coastal community resiliency enhancement framework that integrates both optimization and control efforts. The optimization problem is formulated to significantly minimize the power outage time at the critical infrastructures in coastal communities by implementing multiple autonomous and dynamic microgrids around MHK resources. Therefore, during severe power outages caused by natural disasters (e.g., floods, hurricanes), the coastal community load profiles can be satisfied using local MHK resources in each microgrid with limited or no power support from upstream power grids.
In this report we address the challenge of designing efficient protection system for inverter- dominated microgrids. These microgrids are characterised with limited fault current capacity as a result of current-limiting protection functions of inverters. Typically, inverters limit their fault contribution in sub-cycle time frame to as low as 1.1 per unit. As a result, overcurrent protection could fail completely to detect faults in inverter-dominated microgrids. As part of this project a detailed literature survey of existing and proposed microgrid protection schemes were conducted. The survey concluded that there is a gap in the available microgrid protection methods. The only credible protection solution available in literature for low- fault inverter-dominated microgrids is the differential protection scheme which represents a robust transmission-grade protection solution but at a very high cost. Two non-overcurrent protection schemes were investigated as part of this project; impedance-based protection and transient-based protection. Impedance-based protection depends on monitoring impedance trajectories at feeder relays to detect faults. Two communication-based impedance-based protection schemes were developed. the first scheme utilizes directional elements and pilot signals to locate the fault. The second scheme depends on a Central Protection Unit that communicates with all feeder relays to locate the fault based on directional flags received from feeder relays. The later approach could potentially be adapted to protect networked microgrids and dynamic topology microgrids. Transient-based protection relies on analyzing high frequency transients to detect and locate faults. This approach is very promising but its implementation in the filed faces several challenges. For example, high frequency transients due to faults can be confused with transients due to other events such as capacitor switching. Additionally, while detecting faults by analyzing transients could be doable, locating faults based on analyzing transients is still an open question.