The National Renewable Energy Laboratory (NREL), in partnership with the Interstate Renewable Energy Council (IREC), has recently released a report which identifies a suite of best practices for producing trusted, validated hosting capacity analysis results reflecting real-world grid conditions.
The usefulness of Hosting Capacity Analysis (HCA) is dependent on users' confidence that the results accurately reflect grid conditions. This report provides the findings and recommendations from research, conducted by The National Renewable Energy Lab (NREL) and The Interstate Renewable Energy Council (IREC), into HCA data validation best practices. The goal is to provide utilities, regulators, and stakeholders best practices for HCA data validation procedures so that future HCA deployments avoid uncertainties and potential mistakes from earlier rollouts and provide useful and accurate data from the day they are published.
The usefulness of Hosting Capacity Analysis (HCA) is dependent on users' confidence that the results accurately reflect grid conditions. This report provides the findings and recommendations from research, conducted by The National Renewable Energy Lab (NREL) and The Interstate Renewable Energy Council (IREC), into HCA data validation best practices. The goal is to provide utilities, regulators, and stakeholders best practices for HCA data validation procedures so that future HCA deployments avoid uncertainties and potential mistakes from earlier rollouts and provide useful and accurate data from the day they are published. Utilities can use this report to develop or refine their HCA data validation procedures. Regulators can use the report to inform their oversight of utilities' HCA data validation practices, while stakeholders can use it to evaluate the effectiveness of utility efforts.
Calibrating distribution system models to aid in the accuracy of simulations such as hosting capacity analysis is increasingly important in the pursuit of the goal of integrating more distributed energy resources. The recent availability of smart meter data is enabling the use of machine learning tools to automatically achieve model calibration tasks. This research focuses on applying machine learning to the phase identification task, using a co‐association matrix‐based, ensemble spectral clustering approach. The proposed method leverages voltage time series from smart meters and does not require existing or accurate phase labels. This work demonstrates the success of the proposed method on both synthetic and real data, surpassing the accuracy of other phase identification research.
Electric utilities conduct planning annually to ensure their distribution system meets technical standards, policies, and regulations; addresses forecasted grid conditions; satisfies customer needs; and advances utility priorities. The plan identifies grid deficiencies, analyzes potential solutions, and prioritizes capital investments and other expenditures. About 20 U.S. states and jurisdictions require regulated utilities to file some type of distribution system plan with the public utility commission for review. Requirements for sharing distribution system data and analyses vary widely, from few specific requirements to a detailed list of information that must be provided. While utilities conduct extensive analysis to develop distribution system plans, in most jurisdictions regulators and stakeholders do not know what data are available and how the utility uses the data in planning and investing. This report aims to bridge the gap by increasing understanding of the types of data and analyses utilities employ to develop distribution system plans and how the information affects their decision-making. The report describes information that states and stakeholders can ask for related to 11 data categories: -Forecasting loads and distributed energy resources (DERs) -Scenario analysis -Worst-performing circuits -Asset management strategy -Hosting capacity analysis -Value of DERs -Grid needs assessment -Cost-effectiveness framework for investments -Distribution system investment strategy and implementation -Geotargeted programs -Non-wires alternatives procurements.
Often PV hosting capacity analysis is performed for a limited number of distribution feeders. For medium - voltage distribution feeders, previous results generally analyze less than 20 feeders, and then the results are extrapolated out to similar types of feeders. Previous hosting capacity research has often focused on determining a single value for the hosting capacity for the entire feeder, whereas this research expands previous hosting capacity work to investigate all the regions of the feeder that may allow many different hosting capacity values wit h an idea called locational hosting capacity (LHC)to determine the largest PV size that can be interconnected at different locations (buses) on the study feeders. This report discusses novel methods for analyzing PV interconnections with advanced simulati on methods. The focus is feeder and location - specific impacts of PV that determine the locational PV hosting capacity. Feeder PV impact signature are used to more precisely determine the local maximum hosting capacity of individual areas of the feeder. T he feeder signature provides improved interconnection screening with certain zones that show the risk of impact to the distribution feeder from PV interconnections.
This paper introduces a novel approach for generating solar photovoltaic (PV) plant deployment scenarios for grid integration planning. The approach guarantees consistency among scenarios of the same deployment by ensuring that higher penetration scenarios contain PV units deployed in lower penetration scenarios. It also constrains the size and spatial distribution of the PV plants and considers three placement types. A case study on a real-world distribution system proves that the precepts of scenario consistency, deployment diversity, and placement are met. The study further investigates the impact of the resulting scenarios via a stochastic hosting capacity analysis. Results indicate that the ratio between PV and load sizes, referred to as the nodal PV penetration factor (NPPF), is a key driver of the grid integration impact. By reducing the NPPF from 5 to 2, the maximum hosting capacity increased by at least 112%. The study also reveals that scenarios under random placement can lead to higher hosting capacity values.
This paper introduces a novel approach for generating solar photovoltaic (PV) plant deployment scenarios for grid integration planning. The approach guarantees consistency among scenarios of the same deployment by ensuring that higher penetration scenarios contain PV units deployed in lower penetration scenarios. It also constrains the size and spatial distribution of the PV plants and considers three placement types. A case study on a real-world distribution system proves that the precepts of scenario consistency, deployment diversity, and placement are met. The study further investigates the impact of the resulting scenarios via a stochastic hosting capacity analysis. Results indicate that the ratio between PV and load sizes, referred to as the nodal PV penetration factor (NPPF), is a key driver of the grid integration impact. By reducing the NPPF from 5 to 2, the maximum hosting capacity increased by at least 112%. The study also reveals that scenarios under random placement can lead to higher hosting capacity values.
The benefits and risks associated with Volt-Var Curve (VVC) control for management of voltages in electric feeders with distributed, roof-top photovoltaic (PV) can be defined using a stochastic hosting capacity analysis methodology. Although past work showed that a PV inverter’s reactive power can improve grid voltages for large PV installations, this study adds to the past research by evaluating the control method’s impact (both good and bad) when deployed throughout the feeder within small, distributed PV systems. The stochastic hosting capacity simulation effort iterated through hundreds of load and PV generation scenarios and various control types. The simulations also tested the impact of VVCs with tampered settings to understand the potential risks associated with a cyber-attack on all of the PV inverters scattered throughout a feeder. The simulation effort found that the VVC can have an insignificant role in managing the voltage when deployed in distributed roof-top PV inverters. This type of integration strategy will result in little to no harm when subjected to a successful cyber-attack that alters the VVC settings.
Rapid and accurate quasi-static time series (QSTS) analysis is becoming increasingly important for distribution system analysis as the complexity of the distribution system intensifies with the addition of new types, and quantities, of distributed energy resources (DER). The expanding need for hosting capacity analysis, control systems analysis, photovoltaic (PV) and DER impact analysis, and maintenance cost estimations are just a few reasons that QSTS is necessary. Historically, QSTS analysis has been prohibitively slow due to the number of computations required for a full-year analysis. Therefore, new techniques are required that allow QSTS analysis to rapidly be performed for many different use cases. This research demonstrates a novel approach to doing rapid QSTS analysis for analyzing the number of voltage regulator tap changes in a distribution system with PV components. A representative portion of a yearlong dataset is selected and QSTS analysis is performed to determine the number of tap changes, and this is used as training data for a machine learning algorithm. The machine learning algorithm is then used to predict the number of tap changes in the remaining portion of the year not analyzed directly with QSTS. The predictions from the machine learning algorithms are combined with the results of the partial year simulation for a final prediction for the entire year, with the goal of maintaining an error <10% on the full-year prediction. Five different machine learning techniques were evaluated and compared with each other; a neural network ensemble, a random forest decision tree ensemble, a boosted decision tree ensemble, support vector machines, and a convolutional neural network deep learning technique. A combination of the neural network ensemble together with the random forest produced the best results. Using 20% of the year as training data, analyzed with QSTS, the average performance of the technique resulted in ~2.5% error in the yearly tap changes, while maintaining a <10% 99.9 th percentile error bound on the results. This is a 5x speedup compared to a standard, full-length QSTS simulation. These results demonstrate the potential for applying machine learning techniques to facilitate modern distribution system analysis and further integration of distributed energy resources into the power grid.
National Laboratory of the Rockies (NLR), in collaboration with the Dubai Electricity and Water Authority (DEWA) and Infra-X, has undertaken the Energy Visualization Analysis Project. The aim of this project is to enhance analytical and 3D visualization capabilities for distribution network planning and renewable energy integration. As modern grid continues to evolve with large-scale solar PV deployment and emerging distributed energy resources (DERs), the ability to effectively analyze, visualize, and communicate complex grid behaviors has become increasingly critical. The project focuses on developing empirical use cases based on real distribution feeder data and engineering workflows, ensuring the outcomes are directly aligned with operational environment. Through time-series power flow simulations and nodal hosting capacity analysis, the study quantifies the impacts of high PV penetration on voltage and thermal limits within representative 11 kV feeders. These analyses identify specific nodes and conditions where DER integration challenges arise. Furthermore, a Battery Energy Storage System (BESS) optimization algorithm was applied to determine the optimal size and placement of storage systems that can mitigate network constraints and enhance hosting capacity. The comparative results between base-case and BESS-augmented scenarios clearly demonstrate improvements in network stability and load management efficiency. In parallel, the NLR team developed an immersive 3D visualization framework, enabling interactive exploration of grid simulations using commodity head-mounted display (HMD) systems. This framework transforms conventional 2D simulation data into spatially intuitive visual environments - allowing engineers to analyze feeder conditions, PV hosting potential, and BESS effects in real time. This report represents the first foundational phase in establishing a visualization-driven analytical ecosystem. It provides a methodological foundation for data integration, visualization architecture, and simulation-based decision support, paving the way for large-scale adoption of immersive visualization across DEWA's Smart Grid Initiative, R&D activities, and future network resilience studies.
Current distribution system planning (DSP) processes do not explicitly account for energy equity considerations, such as who is most affected by power system burdens, where those burdens are concentrated, and what investments can be made to improve baseline conditions. This paper proposes an iterative framework for advancing energy equity as an objective of the DSP process, showing how measurement strategies, or metrics (informed by conceptual foundations of energy justice), can be applied to benchmark equity performance at various stages. This methodology is applied for equity-aware distributed energy resource (DER) hosting capacity analysis and outage analysis to provide critical insights on infrastructure upgrade decisions compared to a business-as-usual (BAU) case. The analysis is performed on a taxonomy feeder representing the West Coast urban/semi-urban system with augmentation of electric vehicles (EVs) and rooftop solar photovoltaic (PV) generators. The study considers disadvantaged community (DAC) and non-disadvantaged community (NDAC) load regions to enable equity-aware simulations. The results demonstrate how equity-aware planning could reveal the limitations of the traditional DSP process as DAC regions are found to have lower DER hosting capacity and higher outage vulnerability. Overall, this work provides insights on the need to incorporate energy equity as an integral part of the DSP process.