Search NASA⌕ Search

SEARCH · Search NASA

Results for “medium voltage distribution system”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

A Medium-/Low-Voltage Joint State Estimator Through Linear Uncertainty Propagation

Traditionally, distribution system state estimations (DSSE) are challenged by the lack of measurements at both primary and secondary sides of the system. The widely available cable television (CATV) voltage sensors installed in low-voltage (LV) networks bring opportunities to achieve higher quality DSSE covering a broader area of the distribution network. This study proposes a medium-/low-voltage (MV/LV) joint distribution system state estimation approach using the untapped CATV measurements. It aims at addressing the need for system situational awareness at the grid edge while improving the estimation accuracy at both the primary and secondary sides compared to its disjointed counterpart. Linearized measurement functions and boundary condition uncertainty propagation rules are derived to ensure the computational efficiency and accuracy of the joint state estimator. Numerical experiments are conducted on an IEEE test feeder to demonstrate the efficacy of the proposed method and the value of CATV measurements.

joint state estimation↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids

Increasing penetration levels of inverter based distributed energy resources (DERs) impact the legacy distribution system protection. Inverter based DERs provide approximately 1.2-2 pu fault current. In systems with high penetration of inverter based DERs, it is difficult for over-current based protection schemes to differentiate between normal loading conditions and a fault. Directional, distance, and adaptive forms of protection schemes are also affected by low fault currents. This paper analyzes fault generated traveling wave (TW) based high-frequency signatures in the distribution system. In order to simulate such signatures, frequency-dependent distributed parameter line modeling approach is used in this research work to represent distribution lines and underground cables. Modified IEEE 13-bus medium voltage test system is modeled in electromagnetic transient simulation tool and multiple transient scenarios are simulated in this test system. The results are analyzed to understand the high-frequency signatures that can be used to detect and locate faults under high penetration of DERs.

41 EE - Solar Energy Technologies Office (EE-4S)↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids

Increasing penetration levels of inverter based distributed energy resources (DERs) impact the legacy distribution system protection. Inverter based DERs provide approximately 1.2-2 pu fault current. In systems with high penetration of inverter based DERs, it is difficult for over-current based protection schemes to differentiate between normal loading conditions and a fault. Directional, distance, and adaptive forms of protection schemes are also affected by low fault currents. This paper analyzes fault generated traveling wave (TW) based high-frequency signatures in the distribution system. In order to simulate such signatures, frequency-dependent distributed parameter line modeling approach is used in this research work to represent distribution lines and underground cables. Modified IEEE 13-bus medium voltage test system is modeled in electromagnetic transient simulation tool and multiple transient scenarios are simulated in this test system. The results are analyzed to understand the high-frequency signatures that can be used to detect and locate faults under high penetration of DERs.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Megawatt-Class, High-Voltage SiC Power Electronics Converters for Advanced Manufacturing with Grid Support Services

DE-EE0009135 aimed to push the 10kV SiC MOSFET based power electronics to 3-phase 13.8kV 10MW to be used as a Megawatt Class Medium-Voltage Power Conditioning Systems – PCS – to enable “Resilient Distribution through Grid-dispatching and Uninterrupted Quality Power to Manufacturing Facilities” during transitory grid disturbances. As a stretch to those goals, Eaton added the load power peak shaving opportunity.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Study on Conversion from an Existing Alternating Current Medium-Voltage Line to a Direct Current Line: A Case of Load or Source Expansion

Simultaneous increase of power generation through renewable systems and load due owing to the rapid growth in electrified road transportation systems, leads to new challenges in the design, operation, and protection of distribution-level electrical power systems. This paper addresses challenges related to the integration of new sources or loads to a distribution grid through long alternating current lines. The International Council on Large Electric Systems medium-voltage benchmark model developed for North America was used for simulation studies. Use cases were developed to illuminate the issues related to long alternating current lines and the usefulness of medium-voltage direct current lines in a distribution network.

Jaldanki, Sreenivasa↗

Understanding Line Losses and Transformer Losses in Rural Isolated Distribution Systems

Rural, isolated power systems in the mainland U.S. and in states like Alaska and Hawaii are powered by assets like diesel generators. These rural, isolated power systems also cannot operate at the higher band of medium voltage (like 69kV). They are primarily in the 12 to 14 kV range to keep the cost of the distribution investments lower. Because of this mid-band medium voltage range, the line losses and distribution transformers losses consume significant diesel consumption (almost 10 percent of the peak load). This work considers one such power system powering an isolated system and presents key findings online losses, and transformer losses. Understanding and documenting the impacts is critical for these communities operating their power systems and take actions to reduce expensive diesel consumption. In this paper, we will present one such typical grid and model it in electromagnetic transients (EMT) domain. We used the tower structure, under ground cabling installation to develop high fidelity models of lines. We also used high fidelity models of distribution transformers to present the no-load losses and full load loses. We will also present technical solutions available commercially off-the-shelf to reduce these losses and reduce diesel consumption. This work will be a primer for communities to understand the technical challenges and to understand the possible solution available to solve such challenges for rural, isolated power system operators.

blackstart↗

Demonstrating the data center as a flexible grid asset using a C-HIL setup

Increasing data center demand is outpacing grid infrastructure development. Artificial intelligence workloads and hyperscale cloud growth are creating unprecedented demand for power, while traditional grid expansion faces multiyear development timelines. Verrus is developing an innovative datacenter solution for this challenge, data centers that act as active grid-supportive assets rather than passive loads. Our approach integrates a novel grid-aware power flow management system with battery energy storage systems(BESS) into a microgrid-controlled, medium-voltage power distribution architecture that delivers critical capabilities, such as: * Fast response to grid disturbances such over/ under voltage or over/ under frequency * Demand flexibility that can service requests from the utility within 10 s * Uninterrupted transition to islanded operation during grid outages * Continuous uptime assurance for compute loads while maintaining all customer service level agreements. Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), these capabilities were validated using NREL's Advanced Research on Integrated Energy Systems (ARIES) virtual emulation environment to model a 70-MW grid-interactive data center. This paper outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can provide both critical load resilience and ancillary grid support without compromising uptime requirements. Specifically, we present a digital real time simulation of a 70 MW data center integrated with a physical microgrid controller, and demonstrate the data center response in the event of a grid voltage and frequency event, utility demand response request and utility outage.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Outdoor Test Bed Performance of a Power Line Sensor Using a Real-Time Event Simulator

This report summarizes the design and application of an outdoor power line sensor testbed (OPLST) with a real-time simulator and power meter to compare a potential transformer (PT) and current transformer (CT) versus an advanced line-post sensor. The OPLST was created to validate advanced medium-voltage (20/34.5 kV) outdoor power line sensors used in electrical distribution systems. Electrical utilities have installed metering and relay-protection transformers like PTs and CTs for several decades. The PTs/CTs are iron core measurement transformers based on the electromagnetic induction principle and provide reliable data in normal grid operation. However, new outdoor power line sensors (OPLS) using other technologies like voltage divider, Rogowski coil and optical principles have become available and may have favorable performance and costs compared to PTs/CTs. Therefore, the importance of testing these technologies with the PT/CT, to compare the measured phase voltage/current at different power grid scenarios is crucial to understand the performance of these new OPLS. For this study a G&W Electric Model CVS-36-O power line sensor was chosen as the OPLS to test with voltage/current signals. An OPAL-RT Technologies Model OP4510 real-time simulator and Schweitzer Engineering Laboratories Model SEL-735 power meter were installed with the 20/34.5 kV OPLST to compare the measured transient events collected from an advanced OPLS and the PT/CT. This system is installed at the Distributed Energy Communications and Control (DECC) lab, Oak Ridge National Laboratory (ORNL). The simulator generated different power grid scenarios (electrical faults, capacitor bank operation, service restoration, etc.), and its analog-output signals were connected to the voltage/current amplifiers that feed the 20/34.5 kV aerial cable loop through the PT/CT devices. Additional PT/CT devices were also wired with the medium voltage aerial cable loop to measure the phase current/voltage signals and server as references. After each test, common format for transient data exchange (COMTRADE) files were collected from the SEL-735 power meter and used to compare the performance of the OPLS with the PT/CT. The behavior of analog signals, harmonic components, total harmonic distortion and crest factors were assessed and found favorable for the G&W sensor as compared to the reference PT/CT.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Understanding Line Losses and Transformer Losses in Rural Isolated Distribution Systems: Preprint

Rural, isolated power systems in the mainland U.S. and in states like Alaska and Hawaii are powered by assets like diesel generators. These rural, isolated power systems also cannot operate at the higher band of medium voltage (like 69kV). They are primarily in the 12 to 14 kV range to keep the cost of the distribution investments lower. Because of this mid-band medium voltage range, the line losses and distribution transformers losses consume significant diesel consumption (almost 10 percent of the peak load). This work considers one such power system powering an isolated system and presents key findings online losses, and transformer losses. Understanding and documenting the impacts is critical for these communities operating their power systems and take actions to reduce expensive diesel consumption. In this paper, we will present one such typical grid and model it in electromagnetic transients (EMT) domain. We used the tower structure, under ground cabling installation to develop high fidelity models of lines. We also used high fidelity models of distribution transformers to present the no-load losses and full load loses. We will also present technical solutions available commercially off-the-shelf to reduce these losses and reduce diesel consumption. This work will be a primer for communities to understand the technical challenges and to understand the possible solution available to solve such challenges for rural, isolated power system operators.

blackstart↗

Smart-DS: Synthetic Models for Advanced, Realistic Testing: Distribution Systems and Scenarios

The explosion of new ideas for distributed energy resources and advanced distribution grid algorithms faces a critical challenge: how can one effectively develop and evaluate these breakthrough technologies without an adequate set of power systems network, load, and resource data to test against? Today's open test systems, particularly for distribution systems, are tiny and incomplete; and though with enough effort, obtaining utility data under NDA can overcome scale challenges, the results can't be openly shared, preventing fair comparison. The Smart-DS project-led by NREL in partnership with MIT, Universidad Pontificia Comillas, CYME, and EDD-is working to overcome this gap by generating multiple large-scale, open, synthetic, distribution systems that are realistic but not real. These datasets go beyond a single medium voltage feeder (~1000 customers) to cover entire metropolitan areas and their surrounds with up to hundreds of feeders and millions of customers, complete with low voltage customer connections and high voltage sub-transmission. This scale allows adequate testing and analysis of not just local controls and advanced DERs, but also multiple substation interactions, optimized switching, full-scale distribution-OPF, and more. To accompany these datasets, the project is also building a rich set of scenario generation tools that can be used for distribution and transmission systems alike. This includes automated, spatially aware access to world-class, high-resolution solar, wind, and weather data: forward looking generation mixes: and highly configurable DER, load, climate, outage, control-scheme, and other scenarios. We will also highlight DiTTo, an exciting open-source, multi-way distribution dataset transformation tool for many-to-many format translation with scenario, merge/split, and many other manipulation capabilities.

DERs↗

Enabling Extreme Fast Charging with Energy Storage Final Report

The objective of this project was to develop and demonstrate an extreme fast charging (XFC) station with three 350 kW charging ports that operate at a combined power exceeding 1 MW and mitigate the grid impact by employing smart charging algorithms, using an energy storage system, and connecting directly to a medium-voltage (15 kV-class three-phase) distribution feeder. This final report describes the team's achievements in all aspects of the technology development.

24 POWER TRANSMISSION AND DISTRIBUTION↗

SiC-Based 5-kV Universal Modular Soft-Switching Solid-State Transformer (M-S4T) for Medium-Voltage DC Microgrids and Distribution Grids

Medium-voltage DC (MVDC) grids are attractive for electric aircraft and ship power systems, battery energy storage system (BESS), fast charging electric vehicle (EV), etc. Such EV or BESS applications need isolated bidirectional MVDC to LVDC or LVAC converters. However, the existing Si-based solutions cannot fulfill the requirements of a high-efficiency and robust converter for MVDC grids. This paper presents a 5 kV SiC-based universal modular solid-state transformer (SST). This universal current-source SST can interface either a LVAC or LVDC grid with a MVDC grid in single-stage power conversion, while the conventional dual active bridge (DAB) converter needs an additional inverter. The proposed SST module using 3.3 kV SiC MOSFETs and diodes is bidirectional and can serve as a building block in series or parallel for higher-voltage higher-power systems. The topology of each module is based on the soft-switching solid-state transformer (S4T) with reduced conduction loss, which features reduced EMI through controlled dv/dt, and high efficiency with full-range ZVS for main devices and ZCS for auxiliary devices. Operation principle of the modular S4T (M-S4T), capacitor voltage balancing control between the cascaded modules, design of components including a medium-voltage (MV) medium-frequency transformer (MFT) to realize a 50 kVA 5 kV DC to 600 V DC or 480 V AC M-S4T are presented. Importantly, the MV MFT prototype achieves very low leakage inductance (0.13%) and 15 kV insulation with coaxial cables and nanocrystalline cores. Here, the proposed universal modular SST is compared against the DAB solution and verified with DC-DC and DC-AC simulation and 4 kV experimental results. Significantly, the MV experimental results of a modular DC transformer with each module at MVDC are rarely covered in the literature and reported for the first time.

14 SOLAR ENERGY↗

Conservation Voltage Reduction (CVR) via Two-Timescale Control in Unbalanced Power Distribution Systems

Voltage control devices are employed in power distribution systems to reduce the power consumption by operating the system closer to the lower acceptable voltage limits; this technique is called conservation voltage reduction (CVR). The different modes of operation for system’s legacy devices (with binary control) and new devices (e.g. smart inverters with continuous control) coupled with variable photovoltaic (PV) generation results in voltage fluctuations which makes it challenging to achieve CVR objective. This paper presents a two-timescale control of feeder’s voltage control devices to achieve CVR that includes (1)a centralized controller operating in a slower time-scale to coordinate voltage control devices across the feeder and (2) local controllers operating in a faster timescale to mitigate voltage fluctuations due to PV variability. The centralized controller utilizes a three-phase optimal power flow model to obtain the decision variables for both legacy devices and smart inverters. The local controllers operate smart inverters to minimize voltage fluctuations and restore nodal voltages to their reference values by adjusting the reactive power support. The proposed approach is validated using the IEEE-123 bus (medium-size) and R3-12.47-2 (large-size) feeders. It is demonstrated that the proposed approach is effective in achieving the CVR objective for unbalanced distribution systems.

optimal control, distributed generation, fluctuati↗

Segmented Energy Routing for a Modular AC/DC Hybrid System

This article presents a modular ac/dc system with both distributed and centralized power ports for energy router (ER) applications. In each module of the described system, photovoltaic (PV) power generation units, battery-type energy storage (ES) units, and critical loads are connected to the cascaded H-bridge (CHB)-organized medium-voltage (MV) dc links, with fully distributed low-voltage (LV) dc power ports. Copies of modules share the centralized load bus and interact with an MV ac grid in parallel. Hybrid power port (HPO) assigns flexibility to the system but makes energy routings a necessity for stable operation. In this article, a segmented energy management strategy for the HPO-ER is proposed. In terms of the grid-side power transferring, the system ratings are intentionally designed to match significant power imbalance. Focally, a segmented energy management strategy is proposed to realize fully autonomous energy routing involving MV ac grid, distributed PV generations, distributed battery storages, and LV load. The system is proven to be stable using the derived impedance-based model considering the interaction between power blocks. The feasibility of the topology and control strategy is also verified through software simulation, laboratorial hardware prototype experiment, and hardware-in-the-loop (HIL) emulation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Introducing the 9500 Node Distribution Test System to Support Advanced Power Applications: An Operations-Focused Approach

The 9500 Node Test System is a representative section of distribution power system model developed as a part of the GridAPPS-D™ project, an effort funded by DOE as a part of the Grid Modernization Lab Consortium (GMLC) program. The test system was developed to fulfill a growing need to represent the rapidly evolving state of electric distribution systems by combining elements of legacy infrastructure systems, modern feeder topologies, and an anticipated future with smart grid technologies. It also provides a network model capable of supporting the simulation of operational scenarios such as the ones in a utility distribution control center. This test system allows the evaluation of the performance of advanced power applications in real-time, such as one that simulates the operations of an Advanced Distribution Management Systems (ADMS), Distributed Energy Resource Management Systems (DERMS), etc. in a Distribution control center. This model is an extension of the widely used IEEE 8500 Node Test Feeder and is currently being validated to become an IEEE test case to help increase adoption and widespread usage among both academia and industry. It is a full-size model representative of a section of a utility’s distribution system with multiple feeders fed from different substations. The model includes multiple distribution circuits, a sub-transmission system, multiple substations, behind the meter customer rooftop photovoltaics (PV), and multiple utility-scale distributed energy resources. To enable accurate simulations of operational scenarios, the 9500 Node Test System is designed to support procedure-based operations, with the ability to realistically demonstrate switching operations, feeder reconfiguration, adjustment of volt-var control equipment, dispatch of distributed generation, and response to planned and unplanned outages. The 9500 Node Test System includes three radial distribution feeders with 12.3 MVA of average load, consisting of both medium voltage and low voltage equipment each supplied by a different distribution substation. The three distribution feeders are connected to each other through Normally-Open switches which can be closed when needed to simulate restoration scenarios due to a fault. One feeder represents today’s grid with low penetration of customer-side renewables. The second represents a potential future grid with microgrids and 100% renewable penetration. The third has no customer generation resources, a district steam plant, and a utility-scale solar farm. The three diverse circuits were created to allow the simulation of both today’s situation as well as potential future scenarios. All three feeders have customers connected by low-voltage secondary triplex lines. This test system meets all requirements outlined in the report for creating a simulation environment that would enable discussion between key technical stakeholders as well as having the potential to accelerate operational application development and their subsequent testing and integration. The new model is a possible representation of what we believe the distribution grid may look like in the future: a high penetration of renewables, reconfigurable radial and mesh topology, numerous DERs, islanded microgrids, and significantly increased data and measurement density. The system supports both the solution of existing and newer algorithms but also enables the evaluation of applications in a realistic operational environment defined by task oriented procedural steps that represent the interaction between the control center operator and field personnel.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Sensors with Intelligent Measurement Platform for Monitoring and Control in Distribution Circuits

This paper presents a medium-voltage intelligent measurement platform that provides post-processing of raw measurements received from commercially-available voltage/current sensors to enhance accuracy and bandwidth of the monitoring system. Furthermore, this platform integrates into a Data Distribution Service (DDS) messaging bus for distributed control and interoperability. The authors present the design, specifications, and major components included in the platform, and argue for applications and use cases that most benefit from this new approach. A laboratory testbed has been created to demonstrate the functionality, for which test results are presented for selected test cases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

IMoFi - Intelligent Model Fidelity: Physics-Based Data-Driven Grid Modeling to Accelerate Accurate PV Integration (Final Report)

This report summarizes the work performed under a project funded by U.S. DOE Solar Energy Technologies Office (SETO) to use grid edge measurements to calibrate distribution system models for improved planning and grid integration of solar PV. Several physics-based data-driven algorithms are developed to identify inaccuracies in models and to bring increased visibility into distribution system planning. This includes phase identification, secondary system topology and parameter estimation, meter-to-transformer pairing, medium-voltage reconfiguration detection, determination of regulator and capacitor settings, PV system detection, PV parameter and setting estimation, PV dynamic models, and improved load modeling. Each of the algorithms is tested using simulation data and demonstrated on real feeders with our utility partners. The final algorithms demonstrate the potential for future planning and operations of the electric power grid to be more automated and data-driven, with more granularity, higher accuracy, and more comprehensive visibility into the system.

14 SOLAR ENERGY↗