Search NASA⌕ Search

SEARCH · Search NASA

Results for “microgrid transition”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Assessing Dynamic Behaviors in Converter- Dominated Power Systems via RMS and EMT Simulations: A Study of Hawaii’s NELHA Microgrid

The transition from conventional power systems to converter-based microgrids has significantly advanced sustainability, clean energy integration, and operational reliability. However, this paradigm shift introduces operational challenges due to the intermittent nature of renewable energy sources and the non-linear characteristics of power electronic loads, inducing voltage fluctuations and harmonic distortions that complicate voltage and frequency regulation. Accurate dynamic modeling is hypothesized to be critical for capturing such effects, enabling reliable simulation and control strategy development. This study introduces an innovative dynamic modeling framework for a real-world converter-based microgrid, utilizing both root mean square (RMS) and electromagnetic transient (EMT) simulation methods. The microgrid was modeled in DIgSILENT PowerFactory, with simulations calibrated against high-resolution field measurements from SEL-735 power quality meters. Results show that RMS simulations effectively characterize steady-state dynamics, while EMT simulations are essential for capturing high-frequency transients and non-linear effects from photovoltaic inverters and variable frequency drives (VFDs). This complementary approach provides a comprehensive understanding of microgrid behavior, providing critical insights for improving simulation accuracy, advancing protection schemes, and improving resilience in future low-inertia power networks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Inverter Controls for Smooth Transition Operation of Networked Microgrids

Islanding sections of a distribution grid as microgrids and networking these microgrids offer promising opportunities for improving system reliability; however, this approach may need distributed energy resources (DERs) to switch between grid-connected and islanded operation without affecting the system stability. The Thevenin impedance of the power system at the DER point of common coupling changes due to networking actions. It is critical to have smooth transitions between modes to ensure stable system operation and to avoid nuisance tripping. This paper presents the design of a grid-forming (GFM)-capable inverter control scheme to reliably operate in distribution systems with networked microgrids. Control mechanisms for smooth transitions between grid-following (GFL) and GFM inverter modes are presented. First, we test the control mechanism on a simple two-source power system through electromagnetic transient (EMT) simulations using a digital real-time simulator. Then, we add multiple such DERs to the EMT model of a real-world distribution feeder and demonstrate stable operation between mode transitions during the networking of the microgrids.

grid forming controls↗

Design Power Control Strategies of Grid-Forming Inverters for Microgrid Application: Preprint

This paper compares two control schemes in the application control layer of a non-PLL grid-forming (GFM) inverter to gain the insights and understanding of how the two schemes affect the dynamic responses of the GFM inverters and the transition operation of microgrids. Both schemes can achieve smooth microgrid transition operation and power tracking, however, the first scheme expects to exhibit more transients due to the feedforward of the inverse dynamic model of the output filter. Simulation results show that both control schemes achieve successful transition operation with smooth transients, and the second control scheme exhibits slightly better transients in the system frequency during islanding operation and the first one has slightly superior transients in the system frequency during reconnection operation. The power tracking performance in the grid-connected mode is evaluated, which shows that the first scheme has better active power tracking and the second one has better reactive power tracking. The analysis and results are useful to develop reliable control schemes for non-PLL GFM inverters because more and more inverters will work as non-PLL grid-forming sources in the future grids due to better stability and reliability.

grid-forming inverter↗

Advanced Distributed Wind Turbine Controls Series: Part 4-Wind Energy in Microgrids – Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL)

In recent years, the technical capabilities and requirements for distributed wind turbines to provide ancillary services beyond maximum energy production has increased. Ancillary services, leveraged through advanced wind turbine controls, can support grid stability, reliability, and resilience. In the context of a microgrid, wind turbines can provide ancillary services that are useful in both islanded and grid-connected modes, as demonstrated in previous parts of this report series. This report focuses on how wind turbines with advanced controls and power electronics can support the stability of the microgrid during transitions from grid-connected to island mode, and back. This report documents simulation results from a model of the National Renewable Energy Laboratory (NREL) Flatirons Campus containing NREL's 600-kilowatt Controls Advanced Research Turbine. Using this turbine, we demonstrate through desktop simulation how a wind turbine can support the voltage and frequency of a microgrid during transitions - from making planned transitions seamless to keeping all loads online during some unplanned transitions to supporting black start in the event of an open transition (blackout).

17 WIND ENERGY↗

Design Power Control Strategies of Grid-Forming Inverters for Microgrid Application

This paper develops and compares two control schemes in the application control layer of a non-phase-locked loop (non-PLL) grid-forming (GFM) inverter to gain insight and understanding into how the two schemes affect the dynamic responses of GFM inverters and the transition operation of microgrids. The first scheme adopts power tracking based on an outer current loop in grid-connected mode and droop control in islanded mode, and the second uses droop control in both grid-connected and islanded modes. Analytical study is developed to compare the performance of these two strategies from various aspects, including fundamental differences, transition operation, power tracking, and P-Q capability with low point-of-common-coupling (PCC) voltages. Extensive simulation testing is carried out to validate the control performance of these two control strategies, and the simulation testing confirms the findings of the analytic study. Finally, the second strategy is recommended because of its superior control performance and ease of implementation. The analysis and results are useful in developing reliable control schemes for non-PLL GFM inverters because increasing numbers of inverters will work as non-PLL grid-forming sources in future grids because of their improved stability and reliability.

grid-forming↗

Distributed Control Strategy to Achieve Synchronized Operation of an Islanded MG

To seamlessly transition a microgrid (MG) from islanded to grid-connected mode, it is necessary to synchronize the magnitude, frequency, and phase of the MG voltage to the voltage of the main grid. In this paper, we present a distributed control strategy to achieve synchronized operation of an islanded MG supported by multiple controllable distributed generators (DGs). The proposed method utilizes pinning-based consensus algorithm to ensure explicit coordination between magnitude, frequency and phase angle regulation, while ensuring proportional power sharing. System frequency is regulated by all the DGs in proportion to their capacity, while a selected DG eliminates the phase and magnitude regulation errors. Controller design criteria is based on small-signal stability analysis. Here, the proposed control strategy is implemented in hardware controllers and its effectiveness is demonstrated using a real-time hardware-in-the-loop MG testbed.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A Novel Power-Hardware-in-the-Loop Interface Method for Grid-forming Inverter Systems: Preprint

Power Hardware-in-the-Loop (PHIL) simulation of grid-forming (GFM) inverter systems facilitates the testing of drastic scenarios like on-grid to off-grid transition, islanded microgrid operation without stiff grid etc. To the authors best knowledge, most of studies in literature are focused on PHIL simulation for grid-following inverter systems and only few studies are focused on GFM inverters and those are challenging and problematic especially for high-power applications. In this article, a novel PHIL simulation platform is proposed that enables interfacing of high-power GFM inverter systems. It proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface for GFM inverter. This addition of virtual GFM inverter in the PHIL interface expands the conventional Ideal Transformer Model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a 3-phase 480 V, 125 kVA GFM inverter system with proposed interfacing method. The results corroborates the fact that the proposed PHIL simulation method performs well and stable for GFM inverter system.

grid-forming inverters↗

Inverter Controls for Smooth Transition Operation and Voltage Balancing of Networked Microgrids

With increasing penetrations of distributed energy resources (DERs), researchers have extensively studied the formation and networking of microgrids to improve reliability during distribution system outages. However, these operations might require DERs in the microgrids to switch between grid-following (GFL) and grid-forming (GFM) modes of operation. A smooth transition between the operation modes should be ensured to have a stable system operation and to avoid nuisance tripping. Additionally, as we network microgrids, inverter control schemes with voltage-balancing controls are needed for unbalanced distribution networks. This paper presents the design of a GFM and GFL capable inverter control scheme for reliable operation in networked microgrids with mechanisms for 1) smooth transition between the GFL and GFM modes, and 2) negative sequence voltage control for voltage balancing. Using electromagnetic transient (EMT) simulations, the control scheme is first tested on a simple two-source power system using a digital real-time simulator. Next, a real-world distribution feeder with unbalanced loading and multiple DERs is used to demonstrate stable operation during the networking of microgrids with voltage balance support.

distributed energy resources↗

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design of an advanced energy management system for microgrid control using a state machine

A state machine is proposed as the solution for an automated microgrid energy management system (EMS) to improve transient performance during transition operations. It characterizes microgrid operation by seven states that cover all the operating modes: two for steady-state operation (grid-connected and islanded), four for transition operation (preparing for disconnection, transitioning to islanding, preparing for reconnection, and transitioning to grid-connected), and one for emergency operation (black-start operation). A unique dispatch algorithm is developed for each state to achieve the control objective, and the transition function is implemented in the state machine as control logics to transition the system from one state to the next. The feasibility and effectiveness of the developed state machine is validated by simulation in MATLAB with an example microgrid, and the test results show excellent performance of the state machine to achieve the target control objective in each state and to improve the system's transient performance during transition operation.

36 MATERIALS SCIENCE↗

Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Novel Power-Hardware-in-the-Loop Interface Method for Grid-Forming Inverter Systems

Power-hardware-in-the-loop (PHIL) simulations of grid-forming (GFM) inverter systems facilitate the testing of drastic scenarios, such as on-grid to off-grid transitions and islanded microgrid operations without a stiff grid. To the authors’ best knowledge, most studies in the literature focus on PHIL simulations for grid-following inverter systems. Only a few studies focus on GFM inverters, and those are challenging and problematic, especially for high-power applications. This article proposes a novel PHIL simulation platform that enables interfacing high-power GFM inverter systems. The paper proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface. This addition of a virtual GFM inverter in the PHIL interface expands the conventional ideal transformer model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a three-phase, 480-V, 125-kVA GFM inverter system with the proposed interfacing method. The results corroborate that the proposed PHIL simulation method performs well and is stable for GFM inverter systems.

droop control↗

Using Energy Storage-Based Grid Forming Inverters for Operational Reserve in Hybrid Diesel Microgrids

In remote arctic communities, where access to a bulk electrical grid interconnection is not available, the implementation of islanded microgrids has been the most viable way to produce and distribute electricity services to their inhabitants. Historically, these islanded grids have relied primarily on diesel generators or hydropower resources to supply the baseload. However, this practice can result in increased expense due to the high costs associated with fuel transportation and the significant amounts of on-site storage necessary when fuel transportation is unavailable during winter months. In order to mitigate this problem, arctic microgrids have started to transition to a hybrid-source operational mode by incorporating renewable energy sources that are inherently variable in nature, such as wind or solar. Due to their highly stochastic behavior, these hybrid-source islanded microgrids can pose potential issues related to power quality due to introduction of rapid net load fluctuations and inability of diesel generators to respond rapidly. In addition, non-firm stochastic sources can require significant idling diesel generator resources to serve as spinning reserves, which is inefficient and wasteful. This work studies the problems that may arise in the transient dynamics of a real-world hybrid diesel microgrid when subjected to a loss of wind generation. Moreover, this work proposes a transition from a diesel spinning reserve to a battery energy-storage system (BESS) operating reserve scheme. The study of the proposed transition is important in establishing the fundamental implication of transient dynamics and the potential benefits of integrating a BESS as a spinning reserve in terms of stability, frequency nadir, and transient voltage deviation. The methods to investigate and validate the transient dynamics relied on both electromagnetic simulation models of GFMIs and a commercially available GFMI in an experimental power hardware-in-the-loop setup. The simulation results showed that the proposed operating reserve scheme improves the power quality of the system in terms of voltage deviation and frequency nadir when the microgrid is subjected to a loss of wind generation scenario. Depending on the simulation cases, adding a GFMI reduced the frequency nadir between 65.3% and 86.7%. Moreover, the reductions in the voltage deviations improved between 3.6% and 23.0%. From these results it can be concluded that the integration of a GFMI can reduce the frequency nadir in a hybrid diesel microgrid, and in turn, reduce diesel consumption, which improves system reliability while reducing fuel expenses. Furthermore, the novelty of this work relies on the fact that the offline simulation results were validated using a power hardware-in-the-loop platform that incorporated a 100 kVA commercially available GFMI as the device under test.

Hernandez-Alvidrez, Javier↗

Net-Zero Carbon Microgrids

The microgrid concept has been effective in creating aggregations of distributed energy resources—generation, storage and loads—for resiliency, in the form of energy security. The success of microgrids in bringing energy security to a wide range of customers—from individual residences to commercial and industrial installations to military bases—has been exemplified during power disruptions and extended outages due to extreme weather events, cybersecurity attacks, and equipment failures. Now microgrids have an opportunity to meet the challenges of climate change and contribute to a carbon-free power delivery system. The transition to net-zero starts within microgrids themselves. In fact, today’s microgrids are largely dominated by generators using fossil fuels, natural gas and diesel, with high greenhouse gas emissions. In short, the transition to net-zero means replacing fossil fueled generators with renewable generation in microgrids. This transition is extended by including new dispatchable generation technologies that are 100% carbon-free and that offer additional advantage of a more-dependable and sustainable source of energy and power. Basically, the decarbonization of microgrids requires three elements: 1) maximizing generation from renewable energy resources, 2) management of storage and flexible loads to balance the variability and intermittency of renewable energy resources, and 3) introducing new clean power sources, including hydrogen-based generation and small modular reactors. This report affirms a need for specific focus by governmental agencies at national, regional, and local levels to establish technology, policy, and investment in this area. The intention of the Net-Zero Microgrid (NZM) Program is to inform these constituencies with cross-cutting research and tools for the reduction of GHG in microgrids – to net-zero in the near term eventually to zero in the longer term. The NZM Program is committed to achieving decarbonization for resiliency and for providing clean energy at the local or distribution level, from remote communities to underserved communities, and large industrial and military facilities. The NZM Planning and Design Platform is a core tool to be developed as an early deliverable of the NZM Program because only a fully integrated microgrid-design approach will ensure maximum carbon reduction in energy production.

13 HYDRO ENERGY↗

An overview of the operation architectures and energy management system for multiple microgrid clusters

The emerging novel energy infrastructures, such as energy communities, smart building-based microgrids, electric vehicles enabled mobile energy storage units raise the requirements for a more interconnective and interoperable energy system. It leads to a transition from simple and isolated microgrids to relatively large-scale and complex interconnected microgrid systems named multi-microgrid clusters. In order to efficiently, optimally, and flexibly control multi-microgrid clusters, cross-disciplinary technologies such as power electronics, control theory, optimization algorithms, information and communication technologies, cyber-physical, and big-data analysis are needed. This paper introduces an overview of the relevant aspects for multi-microgrids, including the outstanding features, architectures, typical applications, existing control mechanisms, as well as the challenges.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid to Microgrid Synchronization with Grid-Forming Inverters: Challenges and Solution

Research on network microgrids has primarily focused on control and optimization. However, application aspects such as microgrid-to-microgrid synchronization have not been fully addressed in existing literature. This paper first addresses the challenges of networking microgrids with grid-forming inverter in droop control. Then, it proposes a pre-synchronization algorithm to improves the synchronization speed and transient stability. To improve the speed, the phase difference between adjacent microgrids is minimized. Transients such as inrush current and oscillations are effectively mitigated by increasing the virtual impedance during interconnection. The proposed strategy allows smooth transitions when reconfiguration of the microgrids is needed. The applicability of this strategy to today’s microgrid systems is demonstrated through a validation in a 480V three-phase network microgrid testbed with commercial-grade inverters, protective devices, and switchgear.

Ferrari Maglia, Max↗

A generic microgrid controller: Concept, testing, and insights

Microgrids have garnered attention in recent years as a way to increase the reliability of the grid, increase the reliability of electricity service to customers, adapt to an increasing percentage of intermittent renewable generation, and serve both customer critical loads and the needs of adjacent communities in the case of emergencies such as natural disasters. One barrier to microgrids is the historic cost and lack of standardization associated with microgrid controllers. To reduce this cost and address standardization, specifications for a Generic Microgrid Controller (GMC) were developed with the goal to facilitate the design and ease of adaptation of microgrid controllers to various microgrids of different sizes and with different resources. A GMC must address two core functions, Transition and Dispatch, as well as several optional higher level functions such as economic dispatch, and renewable and load forecasting. The GMC specifications were demonstrated and evaluated using a commercial simulation platform for two different microgrids, a 20MW-Class community microgrid and a 10MW-Class medical center microgrid. For each microgrid, the GMC was tested in hardware-in-the-loop (HIL) using an OPAL-RT real-time digital simulator, and the two core functions were assessed. The results established that (1) the GMC is successful in seamlessly transitioning the microgrids to and from an islanded mode, (2) a load/generation mismatch at the time of separation depends on the microgrid configuration and must be lower than a specific value determined by simulation testing, and (3) the GMC Dispatch Function response is acceptable in maintaining, in the islanded mode, 60Hz for a range of load changes.

24 POWER TRANSMISSION AND DISTRIBUTION↗