Conservation Voltage Reduction (CVR) via Two-Timescale Control in Unbalanced Power Distribution Systems

Voltage control devices are employed in power distribution systems to reduce the power consumption by operating the system closer to the lower acceptable voltage limits; this technique is called conservation voltage reduction (CVR). The different modes of operation for system’s legacy devices (with binary control) and new devices (e.g. smart inverters with continuous control) coupled with variable photovoltaic (PV) generation results in voltage fluctuations which makes it challenging to achieve CVR objective. This paper presents a two-timescale control of feeder’s voltage control devices to achieve CVR that includes (1)a centralized controller operating in a slower time-scale to coordinate voltage control devices across the feeder and (2) local controllers operating in a faster timescale to mitigate voltage fluctuations due to PV variability. The centralized controller utilizes a three-phase optimal power flow model to obtain the decision variables for both legacy devices and smart inverters. The local controllers operate smart inverters to minimize voltage fluctuations and restore nodal voltages to their reference values by adjusting the reactive power support. The proposed approach is validated using the IEEE-123 bus (medium-size) and R3-12.47-2 (large-size) feeders. It is demonstrated that the proposed approach is effective in achieving the CVR objective for unbalanced distribution systems.

optimal control, distributed generation, fluctuati↗

Recent Advances in Precision Clock Synchronization Protocols for Power Grid Control Systems

With the advent of a new Precision Time Protocol specification, new opportunities abound for clock synchronization possibilities within power grid control systems. The third iteration of the Institute of Electrical and Electronics Engineers Standard 1588 specification provides several new features specifically aimed at complex, wide-area deployments in which situational awareness and control require precise time agreement. This paper describes the challenges faced by existing technology, introduces the new time distribution specification, and provides examples to explain how it represents a game-changing innovation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Strategy for distributed controller defence: Leveraging controller roles and control support groups to maintain or regain control in cyber-adversarial power systems

Distributed controllers play a prominent role in electric power grid operation. The coordinated failure or malfunction of these controllers is a serious threat, where the resulting mechanisms and consequences are not yet well-known and planned against. If certain controllers are maliciously compromised by an adversary, they can be manipulated to drive the system to an unsafe state. The authors present a strategy for distributed controller defence (SDCD) for improved grid tolerance under conditions of distributed controller compromise. The work of the authors’ first formalises the roles that distributed controllers play and their control support groups using controllability analysis techniques. With these formally defined roles and groups, the authors then present defence strategies for maintaining or regaining system control during such an attack. A general control response framework is presented here for the compromise or failure of distributed controllers using the remaining, operational set. The SDCD approach is successfully demonstrated with a 7-bus system and the IEEE 118-bus system for single and coordinated distributed controller compromise; the results indicate that SDCD is able to significantly reduce system stress and mitigate compromise consequences.

97 MATHEMATICS AND COMPUTING↗

Power Grid Reliability Estimation via Adaptive Importance Sampling

Electricity production currently generates approximately 25% of greenhouse gas emissions in the USA. Thus, increasing the amount of renewable energy is a key step to carbon neutrality. However, integrating a large amount of fluctuating renewable generation is a significant challenge for power grid operating and planning. Grid reliability, i.e., an ability to meet operational constraints under power fluctuations, is probably the most important of them. In this letter, we propose computationally efficient and accurate methods to estimate the probability of line overflow, i.e., reliability constraints violation, under a known distribution of renewable energy generation. To this end, we investigate an importance sampling approach, a flexible extension of Monte-Carlo methods, which adaptively changes the sampling distribution to generate more samples near the reliability boundary. The approach allows to estimate overload probability in real-time based only on a few dozens of random samples, compared to thousands required by the plain Monte-Carlo. Our study focuses on high voltage direct current power transmission grids with linear reliability constraints on power injections and line currents. Herein, we propose a novel theoretically justified physics-informed adaptive importance sampling algorithm and compare its performance to state-of-the-art methods on multiple IEEE power grid test cases.

power system faults↗

Artificial Intelligence/Machine Learning Technology in Power System Applications

The primary purpose of this report is to provide an overview of the advancement in artificial intelligence and machine learning (AI/ML) technologies and their applications in power systems. It offers a foundation for understanding the transformative role of AI/ML in power systems and aims to stimulate further research and development in this area. This report begins with a historical perspective of AI/ML technologies, then explores their advancement to today’s prominence. The document highlights key contributors to the success of AI/ML technologies, including increased computational power, greater data availability, innovative algorithms, and advanced tools. It further introduces various AI/ML techniques, including supervised, unsupervised and reinforcement learning, graph neural networks, and generative AI. It also emphasizes the critical importance of ensuring the safety, security, and trustworthiness of these AI/ML techniques within this sector. The report reviews the recent representative advancements in various power system applications enhanced by AI/ML techniques, underscoring key developments and their transformative impact as evidenced by numerous studies. It also explores both the opportunities and challenges associated with the application of AI/ML technologies to improve power system applications. While the report extensively covers AI/ML applications in power systems, focusing primarily on the technical and operational aspects, it may not thoroughly explore the sociopolitical, economic, and broader regulatory implications of AI/ML integration in power systems. AI/ML techniques hold significant potential for enhancing power system applications; however, they are not omnipotent. It is crucial to acknowledge their limitations and understand that they may not be able to address all challenges in the power system domain. Various factors must be considered that influence the implementation, adoption, and effectiveness of AI/ML solutions, including but not limited to safety, security, transparency, and trustworthiness. Additionally, the incorporation of advanced human–machine interfaces is essential, as it enables humans to validate the effectiveness of AI/ML solutions while remaining actively engaged, fostering trust in AI/ML deployment. Finally, the report summarizes AI/ML research activities supported by the Department of Energy (DOE) Office of Electricity (OE) through the Advanced Grid Modeling (AGM) program. The work aligns with the interests and mission of DOE-OE AGM, with the report serving as a resource for identifying existing progress and for pinpointing future applications within AI/ML that need further exploration and support.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control of Low-Inertia Power Systems

Electric power systems are undergoing an unprecedented transition from fossil fuel–based power plants to low-inertia systems that rely predominantly on power electronics and renewable energy resources. This article reviews the resulting control challenges and modeling fallacies, at both the device and system level, and focuses on novel aspects or classical concepts that need to be revised in light of the transition to low-inertia systems. To this end, we survey the literature on modeling of low-inertia systems, review research on the control of grid-connected power converters, and discuss the frequency dynamics of low-inertia systems. Moreover, we discuss system-level services from a control perspective. Overall, we conclude that the system-theoretic mindset is essential to bridge different research communities and understand the complex interactions of power electronics, electric machines, and their controls in large-scale low-inertia power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Stability and control of power systems with high penetrations of inverter-based resources: An accessible review of current knowledge and open questions

As power system renewable energy penetrations increase, the ways in which key renewable technologies such as wind and solar photovoltaics (PV) differ from thermal generators become more apparent. Many studies have examined the variability and uncertainty of such generators and described how generation and load can be balanced for a wide variety of annual energy penetrations, at timescales from seconds to years. Another important characteristic of these resources is asynchronicity, the result of using inverters to interface the prime energy source with the power system as opposed to synchronous generators. Unlike synchronous generators, whose frequency of alternating current (AC) injection is physically coupled to the rotation of the machine itself, inverter based asynchronous generators do not share the same physical coupling with the generated frequency. These subtle differences impact the operations of power systems developed around the characteristics of synchronous generators. In this paper we review current knowledge and open research questions concerning the interplay between asynchronous inverter-based resources (IBRs) and cycle- to second-scale power system dynamics, with a focus on how stability and control may be impacted or need to be achieved differently when there are high instantaneous penetrations of IBRs across an interconnection. This work does not seek to provide a comprehensive review of the latest developments, but is instead intended to be accessible to any reader with an engineering background and an interest in power systems and renewable energy. As such, the paper includes basic material on power electronics, control schemes for IBRs, and power system stability; and uses this background material to describe potential impacts of IBRs on power system stability, operational challenges associated with large amounts of distributed IBR generation, and modern power system simulation trends driven by IBR characteristics.

14 SOLAR ENERGY↗

Apparatus and system for controlling power to an air conditioning compressor for a vehicle

A climate control system for vehicles includes an internal combustion engine that may be coupled to selectively power a first motor generator, and an air conditioning compressor that may be selectively powered by one or both of the first motor generator and a second motor generator, or by the internal combustion engine. The system may include a rechargeable battery, and a vehicle controller having a vehicle state circuit structured to determine a vehicle operating condition value and a state-of-charge value of the rechargeable battery, and a coupling determination circuit structured to provide an internal combustion engine-first motor generator coupling command in response to the vehicle operating condition value and the state-of-charge value. In response to the internal combustion engine-first motor generator coupling command being provided as coupled, the internal combustion engine may power the first motor generator.

Kumar, Mahesh Madurai↗

Barrier Function-based Reinforcement Learning for Emergency Control of Power Systems

Under voltage load shedding has been considered as a standard and effective measure to recover the voltage stability of the electric power grid under emergency and severe conditions. However, this scheme usually trips a massive amount of load which can be unnecessary and harmful to customers. Recently, deep reinforcement learning (RL) has been regarded and adopted as a promising approach that can significantly reduce the amount of load shedding. However, like most existing machine learning (ML)-based control techniques, RL control usually cannot guarantee the safety of the systems under control. In this paper, we introduce a novel safe RL method for load shedding of power systems, that can enhance the safe voltage recovery of the electric power grid after experiencing faults. Unlike standard RL method, the safe RL method integrates a Barrier function into the reward function. Consequently, the optimal control policy can render the power system to avoid the safety bounds. This method is general and can be applied to other safety-critical control problems. Numerical simulations on the 39-bus IEEE benchmark is performed to demonstrate the effectiveness of the proposed safe RL emergency control, as well as its adaptive capability to faults not seen in the training.

Vu, Thanh Long↗

Reinforcement Learning-based Output Structured Feedback for Distributed Multi-Area Power System Frequency Control

Load frequency control (LFC) is a key factor to maintain the stable frequency in multi-area power systems. As the modern power systems evolve from centralized to decentralized paradigm, LFC needs to consider the decentralized scheme that considers limited information from the information-exchange graph for the generator control of each interconnected area. This paper aims to solve a data-driven constrained LQR problem with mean-variance risk constraints and output structured feedback, and applies this framework to solve the LFC problem in multi-area power systems. By reformulating the constrained optimization problem into a minimax problem, the stochastic gradient descent max-oracle (SGDmax) algorithm with zero-order policy gradient (ZOPG) is adopted to find the optimal feedback gain from the learning, while guaranteeing the convergence. In addition, to improve the adaptation of the proposed learning method to new or varying models, we construct an emulator grid that approximates the dynamics of a physical grid and performs training based on this model. Once the feedback gain is obtained from the emulator grid, it is applied to the physical grid with a robustness test to check whether the controller from the approximated emulator applies to the actual system. Numerical tests show that the obtained feedback controller can successfully control the frequency of each area, while mitigating the uncertainty from the loads, with reliable robustness that ensures the adaptability of the obtained feedback gain to the actual physical grid.

Kwon, Kyung-bin↗

Implementation Plan for Combined Heat and Power Systems VOLTTRON Controller: Performance Monitoring and Real-Time Commissioning Algorithm Verification

Building-integrated cooling, heating, and power (CHP) systems are more efficient than conventional systems at providing local power and thermal energy, and favorable fuel prices are bound to spur their increased adoption. However, to realize the full benefit of the CHP systems, we must ensure persistence of energy efficient operations. Much of the inefficiency in the current building operations can be eliminated by use of automated performance monitoring (PM), real-time commissioning verification (CxV) and automated fault detection and diagnostic (AFDD) tools. Automation can help system operators make intelligent decisions. Remote and continuous monitoring of system conditions and performance will enable better management and integration of CHP with existing building systems. Continuous PM, real-time CxV, and AFDD could alleviate burdens for operations staff, enhance operations and maintenance (O&M), and improve reliability of building and CHP systems. To address the O&M challenges and to provide a means to maximize the rate-of-return of building-integrated CHP systems, the Building Technologies Office (BTO) within the U.S. Department of Energy’s (DOE’s) Office of Energy Efficiency and Renewable Energy (EERE) initiated a project to design, develop, and field test a VOLTTRON™-based supervisory controller and associated open-source algorithms. These algorithms will ensure real-time optimal operation of a building-integrated CHP system, support electric grid reliability, and lead to achieving the goal of clean, efficient, reliable, and affordable next-generation integrated energy system. Previous report listed the components for which PM, real-time CxV, and AFDD algorithms will be developed, how the algorithms will be tested, and the metrics that will be used to validate the algorithms and their ease of deployment. Deployment of these algorithms in the field will result in a reduction in energy consumption of between 10% and 20% (for both CHP and conventional building systems). This report builds upon the previous report by detailing the process by which PNNL will implement performance monitoring and real-time commissioning algorithms for CHP systems in conjunction with the use of the VOLTTRON CHP economic dispatch agent in host facilities.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Efficient learning of power grid voltage control strategies via model-based deep reinforcement learning

Here this article proposes a model-based deep reinforcement learning (DRL) method to design emergency control strategies for short-term voltage stability problems in power systems. Recent advances show promising results for model-free DRL-based methods in power systems control problems. But in power systems applications, these model-free methods have certain issues related to training time (clock time) and sample efficiency; both are critical for making state-of-the-art DRL algorithms practically applicable. DRL-agent learns an optimal policy via a trial-and-error method while interacting with the real-world environment. It is also desirable to minimize the direct interaction of the DRL agent with the real-world power grid due to its safety-critical nature. Additionally, the state-of-the-art DRL-based policies are mostly trained using a physics-based grid simulator where dynamic simulation is computationally intensive, lowering the training efficiency. We propose a novel model-based DRL framework where a deep neural network (DNN)-based dynamic surrogate model (SM), instead of a real-world power grid or physics-based simulation, is utilized within the policy learning framework, making the process faster and more sample efficient. However, having stable training in model-based DRL is challenging because of the complex system dynamics of large-scale power systems. We addressed these issues by incorporating imitation learning to have a warm start in policy learning, reward-shaping, and multi-step loss in surrogate model training. Finally, we achieved 97.5% reduction in samples and 87.7% reduction in training time for an application to the IEEE 300-bus test system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Framework for Analysis and Quantification of Wide-Area Control Resilience for Power Systems

Wide-area control helps damp the inter-area oscillations in modern power systems. However, compared to traditional local control, it is more vulnerable to cyber attacks due to its dependence on remote real-time-communicated measurements. In this paper, a formal mathematical framework for analyzing resilience of various wide-area controllers under adversarial scenarios is proposed. A novel resilience index based on the $\H_2$ norm of the post-attack closed-loop system is defined. Computation of such an index is, in general, challenging due to the combinatorial nature of the attack profiles and the bilinear nature of the problem. To address these difficulties, a gradient-based path-following-like solution is developed in this paper to solve a relaxed version of the original non-convex problem. Case studies on IEEE 39-bus system are performed to demonstrate the usage of the proposed framework.

Marinovici, Laurentiu D.↗

Optimal mitigation and control over power system dynamics for stochastic grid resilience

Optimal mitigation planning for highly disruptive contingencies to a transmission-level power system requires optimization with dynamic power system constraints, due to the key role of dynamics in system stability to major perturbations. We formulate a generalized disjunctive program to determine optimal grid component hardening choices for protecting against major failures, with differential algebraic constraints representing system dynamics (specifically, differential equations representing generator and load behavior and algebraic equations representing instantaneous power balance over the transmission system). We optionally allow stochastic optimal pre-positioning across all considered failure scenarios, and optimal emergency control within each scenario. This novel formulation allows, for the first time, analyzing the resilience interdependencies of mitigation planning, preventive control, and emergency control. Using all three strategies in concert is particularly effective at maintaining robust power system operation under severe contingencies, as we demonstrate on the western system coordinating council 9-bus test system using synthetic multi-device outage scenarios.

30 DIRECT ENERGY CONVERSION↗

Discovery of Signatures, Anomalies, and Precursors in Synchrophasor Data with Matrix Profile and Deep Recurrent Neural Networks (Final Project Report)

The widespread deployment of phasor measurement unit (PMU) across the U.S. together with the burgeoning machine learning technology made it possible to develop data-driven PMU data analytics to improve grid security and reliability in a more insightful and effective manner. Although PMU applications have been explored for over a decade, the representative PMU usage is limited to the bulk power system monitoring mainly due to the data integrity issues associated with PMUs (typically missing, fragmented, and wrongly amplified data). To forge a breakthrough on this stalemate and embrace PMUs for power system control and protection as well, we applied various advanced machine learning and big data analysis technology to the power system event detection and classification as the first step toward the power system control and protection pertaining to grid security enhancement.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distribution power system fault control apparatus and method

A method includes detecting a fault in a grid coupled to a distribution power network, the distribution power network comprising a distribution feeder, a plurality of distributed energy resources (DERs) coupled to the distribution feeder and a reference point of applicability (RPA) associated with the plurality of DERs, and in response to detecting the fault, determining an error voltage at the RPA, converting the error voltage into an error signal, broadcasting the error signal to the plurality of DERs, and based on the error signal, reducing the error voltage at the RPA by injecting a plurality of currents from the plurality of DERs to the distribution feeder.