Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗

Techno-Economic Assessment of Data Center Load Demand Powered by Small Modular Reactors and Distributed Energy Resources

The rapid increase in data center energy demand, driven by AI and large-scale data processing, poses significant challenges to global energy infrastructure. Data centers require substantial and reliable energy for continuous operations and high-performance computing. Current electrical grids face issues such as transmission bottlenecks and aging infrastructure, making it difficult to meet these demands. Integrating inverter-based-resources (IBRs) like solar and wind presents both opportunities and challenges due to their intermittent nature. Small Modular Reactors (SMRs) offer a promising solution with their enhanced safety, modularity, reliability, and scalability, providing consistent base load power ideal for data center operations. This study presents a comprehensive techno-economic assessment of powering data center load demand using a combination of SMRs and IBRs with grid-connected and islanded mode. This study utilized Idaho National Laboratory’s (INL) HPC data center hourly load profiles and Xendee microgrid optimization platform to conduct the analysis. In this configuration, SMRs serves as the primary base load power source, consistently providing a steady supply of electricity necessary to meet the minimum load demand of the data center with support from the IBRs. Key performance indicators such as Levelized Cost of Electricity (LCOE), Net Present Value (NPV) has been calculated to assess the economic feasibility. The findings from this research will underscore the strategic benefits of integrating SMR plant with DERs – particularly for critical infrastructure load such as data centers.

14 - SOLAR ENERGY↗

Reliability of CCGA 1152 and CCGA 1272 Interconnect Packages for Extreme Thermal Environments

Ceramic column grid array (CCGA) packages have been increasing in use based on their advantages of high interconnect density, very good thermal and electrical performance, and compatibility with standard surface-mount packaging assembly processes. CCGA packages are used in space applications such as in logics and microprocessor functions, telecommunications, flight avionics, and payload electronics. As these packages tend to have less solder joint strain relief than leaded packages, the reliability of CCGA packages is very important for short- and long-term space missions. Certain planetary satellites require operations of thermally uncontrolled hardware under extremely cold and hot temperatures with large diurnal temperature change from day to night. The planetary protection requires the hardware to be baked at +125 C for 72 hours to kill microbugs to avoid any biological contamination, especially for sample return missions. Therefore, the present CCGA package reliability research study has encompassed the temperature range of 185 to +125 C to cover various NASA deep space missions. Advanced 1152 and 1272 CCGA packaging interconnects technology test hardware objects have been subjected to ex treme temperature thermal cycles from 185 to +125 C. X-ray inspections of CCGA packages have been made before thermal cycling. No anomalous behavior and process problems were observed in the x-ray images. The change in resistance of the daisy-chained CCGA interconnects was measured as a function of increasing number of thermal cycles. Electrical continuity measurements of daisy chains have shown no anomalies, even until 596 thermal cycles. Optical inspections of hardware have shown a significant fatigue for CCGA 1152 packages over CCGA 1272 packages. No catastrophic failures have been observed yet in the results. Process qualification and assembly are required to optimize the CCGA assembly processes. Optical inspections of CCGA boards have been made after 258 and 596 thermal cycles. Corner columns have started showing significant fatigue per optical inspection results.

Ramesham, Rajeshuni↗

Grid Sphere Electrodes used for Current Collection at the Positive Pole of Electrodynamic Tethers

The generation of either electrical power or propulsive thrust with an electrodynamic tether system necessarily depends on driving a return current through the system's ambient space plasma environment. An electrical connection is, therefore, required between the plasma and each end of the tether. The voltage required to drive current through the system is derived either from the orbital motion of the conducting tether through the magnetic field of the Earth, or from a high-voltage power supply that taps into an external energy source (e.g., the sun). In either case, one end of the tether will receive a positive bias. This positive bias, between the tether and the ambient plasma, allows electrons to be collected effectively with a simple, passive electrode. Passive electrode contactors offer several important advantages, including simplification of the upper end-body design and operations, minimization of system mass, and an increase of system reliability and robustness. A preliminary analysis of an inflatable Grid-Sphere end-body concept is presented that is interesting because of the potential for collecting arbitrarily large currents independent of tether length, while the device has the physical characteristics of a high area-to-mass ratio, a low drag coefficient, and simplicity. In particular, we will discuss the physics of current collection by a biased Grid-Sphere and the present state-of-the-art of materials, attainable area-to-mass ratios, and deployment techniques.

Stone, N. H.↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. GFM inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generators) and follow the change in the load demand; however, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help grid operators better manage their inverter-based resources (IBRs) to improve operation efficiency and reliability; therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and synchronous generators) to output the target power in both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters.

dispatching↗

Decoupling Power Quality Issues in Grid-Microgrid Network Using Microgrid Building Blocks

Microgrids are evolving as promising options to enhance reliability of the connected transmission and distribution systems. Traditional design and deployment of microgrids require significant engineering analysis. However, Microgrid Building Blocks (MBB), consisting of modular blocks that integrate seamlessly to form effective microgrids, are promising technologies to enable faster and broader adoption of microgrids. Back-to-Back converter placed at the point of common coupling of microgrid is an integral part of MBB. This paper presents applications of MBB to decouple power quality issues in grid-microgrid network serving power quality sensitive critical loads such as data centers, new grid-edge technologies such as vehicle-to-grid generation, and emergency condition loads such as electric vehicle charging loads during evacuation prior disaster events. Simulation results show that MBB effectively decouple the power quality issues across networks and allow network with low power quality to transfer high-power quality power to connected networks during emergency conditions.

Acharya, Samrat S. [BATTELLE (PACIFIC NW LAB)]↗

Residential Vehicle-to-Home Backup Power Capabilities: Key Findings from a ComEd Beneficial Electrification R&D Pilot

This report summarizes key findings from a collaborative technical study of residential, non-grid-tied vehicle-to-home (V2H) backup power systems in Commonwealth Edison’s (ComEd’s) service territory. The work integrates (1) a feeder-level technoeconomic analysis (TEA) using historical outage-event data and simulated electric-vehicle (EV) driving/charging profiles to estimate potential reliability and customer interruption-cost impacts under V2H and vehicle-to-grid (V2G) adoption scenarios; (2) controlled laboratory performance testing of a representative V2H backup ecosystem to characterize transfer-to-backup behavior, sustained power delivery, efficiency trends, and repeatable reliability limitations; and (3) a cybersecurity assessment aligned with NIST Cybersecurity Framework (CSF) 2.0 and ISO/SAE 21434 to evaluate interface-level risk drivers and identify program-relevant mitigations. Results indicate that V2H can provide measurable resilience value, but outcomes are strongly context dependent on outage patterns and the share of events that are “V2H-applicable.” Typical transfer-to-backup behavior clustered on the order of minutes, but rare long-delay edge cases were observed (including an event approaching 30 minutes) and should be treated as a reliability risk. High-power testing showed that peak-rated output is not necessarily continuously deliverable; stable operation may require operation below nameplate ratings and attention to thermal and installation constraints. The cybersecurity assessment highlights a broad attack surface spanning commissioning, home networks, embedded services, and cloud/OTA pathways, motivating minimum controls for secure onboarding, signed updates, patch cadence, and coordinated vulnerability response for any scaled deployment.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantification of Uncertainty and Risk Sensitivity for Safety of Emerging Operations

The growing need to develop and deploy small unmanned aerial vehicles (sUAVs) for various applications in the airspace necessitates reliable tools to accurately predict the flight trajectories of the sUAVs. The knowledge of the predicted trajectories help decision makers anticipate potential conflict, assess the risk, and take appropriate risk mitigation actions. In addition, uncertainties in vehicle models, weather, and controller action further highlights the need for reliable prediction tools. In this project, the application of mixed sparse grid-based quadrature and generalized polynomial chaos(gPC) expansion method for uncertainty quantification and collision assessment in air traffic consisting of fixed-wing small unmanned aerial vehicles (sUAV) was studied. From the results obtained, it can be concluded that this provides a reliable framework to carry out quantitative conflict assessment in an unmanned air traffic, which when employed, can improve the functionalities of the unmanned traffic management system. It was observed that the results from the gPC expansion framework developed in the project can be utilized to conduct rapid probabilistic collision assessment for near real-time unmanned traffic management in the airspace. From the vehicle models, position updates, and wind-field data, a priori gPC based 3-σcon-fidence ellipses can provide estimates of potential conflict at some future instants. The computational costs scaled linearly when the uncertain inputs were fewer. Further, the largest allowable distribution of para-metric uncertainties that leads to the smallest risk of collision in traffic of small unmanned aerial vehicles could be calculated. The time of closest approach between two sUAVs can be established paving way for development of proactive mitigation strategies. The separation between the sUAVs was found to be most significantly affected by uncertainties in the maximum available thrusts, zero-lift drag coefficients, and wing planform areas of the sUAVs. The study of uncertain wind-fields indicated that a heterogeneous traffic mix resulted in an increased probability of conflict. Increased measurement update rate reduced the uncertain-ties in the trajectories of the vehicles, further reducing the probability of conflict but rapid updates of all vehicles in the airspace poses a stringent communication limitation. The gPC framework also provided the means to analyze vehicle impact (crash region) due to loss of control resulting from actuator failure in sUAS traffic, essentially to predict impact and crash zones for representative vehicles. The predicted regions when compared with non-participant density, provides a means to develop an early mitigation strategy, should the sUAV detect an imminent actuator failure.

Rajnish Bhusal↗

Grid Modernization of Cooperatives and Municipal Utilities via Breakthrough System Monitoring, Control and Optimization (CRADA Final Report)

This project aims at developing and demonstrating successful implementation of breakthrough approaches in real-time data visualization as well as real-time distributed DER control and optimization to provide ample benefits to both utilities and end users. The National Renewable Energy Laboratory (NREL), Holy Cross Energy (HCE), National Rural Electric Cooperative Association (NRECA) and Survalent are collaborating to enable Cooperative and Municipal utilities to fully leverage DERs as part of their strategies for providing safe, reliable, and affordable electric services to their customers and help meet DOE Grid modernization goal of achieving at least 10% active devices to provide grid flexibility by 2035. This project will use novel real-time control algorithms and approaches for distributed control recently developed under DOE-funded projects, using the date from the Survalent’s basic SCADA engine, GIS and AMI engines deployed at HCE combined with NRECA’s globally-used MultiSpeak(R) software interoperability specification for seamless and real-time communications between electric utility enterprise software to embrace DER as part of their strategies for providing safe, reliable and affordable electric service to their customers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transformation of two and three-dimensional regions by elliptic systems

During this contract period, our work has focused on improvements to elliptic grid generation methods. There are two principle objectives in this project. One objective is to make the elliptic methods more reliable and efficient, and the other is to construct a modular code that can be incorporated into the National Grid Project (NGP), or any other grid generation code. Progress has been made in meeting both of these objectives. The two objectives are actually complementary. As the code development for the NGP progresses, we see many areas where improvements in algorithms can be made.

Mastin, C. Wayne↗

Rapid Monitoring and Defense Approach for Resilience Improvement of Grid Cyber Security

Cyber-physical systems and electric utilities significantly depend on the reliability and efficiency of information and operational technology. However, false data injection attacks based on synchrophasor measurement data pose a serious threat to the safe and reliable operation of modern power systems. Here, to mitigate this problem, a rapid monitoring and defense approach is proposed to defend against cyber attacks. Initially, the Time and Frequency based Convolutional neural Network (TFCN) is proposed to detect different types of attacks. Within the TFCN, the advances are that both time and frequency domain information can be fused without extra spectrum analysis methods, and can save detection time to speed the calculation efficiency using the developed time-frequency block. Next, a comprehensive defense strategy is developed for multiple cyber attacks to ensure the stability and resilience of the power system according to the feedback detection results. The advances of this strategy are that different control strategies can be automatically selected to recover the stability to the greatest extent according to the detected attacks. To verify the effectiveness of the proposed approach, the high-speed frequency measurements collected from the wide-area monitoring system are used. The results demonstrate that the cyber attack detection performance can reach 95.57% accuracy, outperforming both traditional and some advanced neural networks. Importantly, the defense strategy is conducted and verified in a modified IEEE 39 bus system as well, which illustrates profound performance in faster stability restoration.

Comprehensive defense strategy↗

Grid Integration of Renewable Energy and Energy Storage

Grid integration of renewable energy and energy storage requires forward-looking planning process, and increased emphasizes on reliability, resilience, and equity. Power-electronics based energy generation including solar, wind, distributed energy resources (DERs), and various types of grid-tied energy storage and emerging loads, are reshaping grid operator's understanding on interconnection level performance and responses. This paper will present the ongoing work at PNNL related to power electronics R&D, energy modeling and analysis, and a wide spectrum of grid stability studies and technologies in support of grid integration of renewable energy and energy storage.

Power Electronics, grid integration of renewable e↗

A resource adequacy assessment of correlated wide-area outages in the power grid

As the power grid is undergoing rapid transformations, numerous questions are emerging about its vulnerability to wide-area extreme events (WAEE), which could influence its operations. Relatively few analyses have been conducted to date regarding the impact of correlated outages during WAEEs on the grid’s ability to balance resources with demand. This study addresses this gap by conducting a resource adequacy analysis for a hurricane-inspired WAEE on a 2035 synthetic power grid system for the United States. A sensitivity analysis was also conducted to characterize the relative impact of weather on unserved energy. Our results indicate that although the magnitude and duration of the shortfalls vary depending on weather conditions, persistent shortfalls are observed in some regions. Initial explorations indicate a strong correlation between transmission-constrained regions and regions with persistent shortfalls. Future work could generate empirically-grounded representations for generator outages as well as conduct causal analyses of these shortfalls to improve understanding of drivers as well as possible mitigation strategies. Continued exploration of extreme weather impacts on the grid is important to develop more robust understanding of the reliability and resilience of our power systems, especially as they undergo rapid transformations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Data-Driven Approach for High-Impedance Fault Localization in Distribution Systems

Accurate and quick identification of high-impedance faults (HIFs) is critical for the reliable operation of distribution systems. Unlike other faults in power grids, HIFs are very difficult to detect by conventional overcurrent relays due to the low fault current. Although HIFs can be affected by various factors, the voltage-current characteristics can substantially imply how the system responds to the disturbance and thus provides opportunities to effectively localize HIFs. In this work, we propose a data-driven approach for the identification of HIF events. To tackle the nonlinearity of the voltage-current trajectory, first, we formulate optimization problems to approximate the trajectory with piecewise functions. Then we collect the function features of all segments as inputs and use the support vector machine approach to efficiently identify HIFs at different locations. Numerical studies on the IEEE 123-node test feeder demonstrate the validity and accuracy of the proposed approach for real-time HIF identification.

explainable artificial intelligence↗

Networked Microgrid Ownership, Data, and Control Implications: Challenges and Open Questions

Microgrid deployments increasingly favor the potential to form networks for greater benefits to resilience, reliability, and energy sovereignty. Both independent and networked micro-grids predominantly have a single-entity-ownership and control, where the associations from ownership to data requirements to control functions to microgrid objectives is linear. The emerging model, however, is cyclical, with bidirectional causal impacts between each of the 4 pillars: there are more complex mixed ownership models across the physical, electrical, data, communications, protection, and control boundaries that impact the data requirements for meeting control functions that help realize the use-cases or objectives. This paper is the first to delineate the pillars for effective ownership and controllability of both independent as well as networked microgrids through the cyclical model, and present barriers to the adoption of such a model.

Sundararajan, Aditya↗

Foreword: Special Section on Multiphysics Aspects of Power Electronics Packaging - Power Die, Power Module, and Converter Level - Part 1

Power electronics are increasingly being used to condition electricity for a wide array of applications, such as transportation (on land, air, and water), data centers, radio frequency, directed energy, wind, solar, and grid-tied applications. To increase power density, performance, efficiency, and reliability and reduce cost, innovations and developments are needed in the multiphysics packaging of power electronics at a die, module, and converter level. This includes fundamental research and development related to emerging high-voltage, high-temperature, and high-switching-frequency power electronics; packaging materials; thermal materials and interfaces; fluid-based thermal management technologies; reliability; condition monitoring; and prognostics. To address these important aspects, this Special Section on Multiphysics Aspects of Power Electronics Packaging includes several articles to be published in two parts. More details are given below on the articles included in the first part.

condition monitoring↗

An Orifice Pulse Tube Cooler for CMOS Computer Cooling

The subject orifice pulse tube cooler employs dual opposed compressor pistons, clearance seals, moving coil linear motors, and flexible bearings cooling capacity is 100 watts at 200 K. A matrix of optimizations explored load temperatures and cooling capacities of 50 K, 100 K, 200 K, 1 watt, 10 watts, and 100 watts. The optimization process resulted in a design with zero second entrance flow and a non-resonant pulse tube. Topics include performance results, mechanical design, and development problems and solutions. The development seeks to use orifice pulse tube mechanical simplicity to achieve a computer cooler with acceptable efficiency, low materials cost, low labor cost, long life, high reliability, low vibration, operation at the standard 60 Hz U.S. grid frequency, and control through simple drive and control electronics.

Riggle, P.↗