Search NASA⌕ Search

SEARCH · Search NASA

Results for “power grid simulation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 469 records · Page 26

How a Large-Scale Deployment of Grid-Forming Inverters May Impact Inter-Area Oscillation Modes: An Investigation in the US Western Interconnection

This report describes work performed to evaluate the impact of high grid-forming (GFM) inverter penetration on the inter-area oscillation mode characteristics of the Western Interconnection. Using simulations, this work analyzes how: a) replacing fossil-fuel-based synchronous generators by GFM inverters will impact properties of the North-South mode, and b) replacing the Colstrip power plant by grid-following (GFL) and GFM inverters will change the characteristics of the Montana mode. Results obtained indicate that high penetration of GFM inverters will significantly alter inter-area oscillation characteristics in interconnections. Low frequency oscillations in the 0.11 Hz range will be predominantly driven by remaining synchronous machines, and hence their relative distribution in the interconnection will impact mode characteristics and observability.

20 FOSSIL-FUELED POWER PLANTS↗

Sequence Impedance Modeling of Grid-Forming Converters: Preprint

Grid-forming control of inverter-based resources (IBRs) has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents sequence impedance modeling of grid-forming inverters to evaluate its small-signal stability properties. Droop based grid-forming control with full consideration of the multiloop structure is studied, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Evaluation of Adaptive Volt-VAR to Mitigate PV Impacts [Slides]

Distributed generation (DG) sources like photovoltaic (PV) systems with advanced inverters are able to perform grid-support functions, like autonomous Volt-VAR that attempts to mitigate voltage issues by injecting or consuming reactive power. However, the Volt-VAR function operates with VAR priority, meaning real power may be curtailed to provide additional reactive power support. Since some locations on the grid may be more prone to higher voltages than others, PV systems installed at those locations may be forced to curtail more power, adversely impacting the value of that PV system. Adaptive Volt-VAR (AVV) could be implemented as an alternative, whereby the Volt-VAR reference voltage changes over time, but this functionality has not been well-explored in the literature. In this work, the potential benefits and grid impacts of AVV were investigated using yearlong quasi-static time-series (QSTS) simulations. After testing a variety of allowable AVV settings, we found that even with aggressive settings AVV resulted in <0.01% real power curtailment and significantly reduced the reactive power support required from the PV inverter compared to conventional Volt-VAR but did not provide much mitigation for extreme voltage conditions. The reactive power support provided by AVV was injected to oppose large deviations in voltage (in either direction), indicating that it could be useful for other applications like reducing voltage flicker or minimizing interactions with other voltage regulating devices.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Introducing the 9500 Node Distribution Test System to Support Advanced Power Applications: An Operations-Focused Approach

The 9500 Node Test System is a representative section of distribution power system model developed as a part of the GridAPPS-D™ project, an effort funded by DOE as a part of the Grid Modernization Lab Consortium (GMLC) program. The test system was developed to fulfill a growing need to represent the rapidly evolving state of electric distribution systems by combining elements of legacy infrastructure systems, modern feeder topologies, and an anticipated future with smart grid technologies. It also provides a network model capable of supporting the simulation of operational scenarios such as the ones in a utility distribution control center. This test system allows the evaluation of the performance of advanced power applications in real-time, such as one that simulates the operations of an Advanced Distribution Management Systems (ADMS), Distributed Energy Resource Management Systems (DERMS), etc. in a Distribution control center. This model is an extension of the widely used IEEE 8500 Node Test Feeder and is currently being validated to become an IEEE test case to help increase adoption and widespread usage among both academia and industry. It is a full-size model representative of a section of a utility’s distribution system with multiple feeders fed from different substations. The model includes multiple distribution circuits, a sub-transmission system, multiple substations, behind the meter customer rooftop photovoltaics (PV), and multiple utility-scale distributed energy resources. To enable accurate simulations of operational scenarios, the 9500 Node Test System is designed to support procedure-based operations, with the ability to realistically demonstrate switching operations, feeder reconfiguration, adjustment of volt-var control equipment, dispatch of distributed generation, and response to planned and unplanned outages. The 9500 Node Test System includes three radial distribution feeders with 12.3 MVA of average load, consisting of both medium voltage and low voltage equipment each supplied by a different distribution substation. The three distribution feeders are connected to each other through Normally-Open switches which can be closed when needed to simulate restoration scenarios due to a fault. One feeder represents today’s grid with low penetration of customer-side renewables. The second represents a potential future grid with microgrids and 100% renewable penetration. The third has no customer generation resources, a district steam plant, and a utility-scale solar farm. The three diverse circuits were created to allow the simulation of both today’s situation as well as potential future scenarios. All three feeders have customers connected by low-voltage secondary triplex lines. This test system meets all requirements outlined in the report for creating a simulation environment that would enable discussion between key technical stakeholders as well as having the potential to accelerate operational application development and their subsequent testing and integration. The new model is a possible representation of what we believe the distribution grid may look like in the future: a high penetration of renewables, reconfigurable radial and mesh topology, numerous DERs, islanded microgrids, and significantly increased data and measurement density. The system supports both the solution of existing and newer algorithms but also enables the evaluation of applications in a realistic operational environment defined by task oriented procedural steps that represent the interaction between the control center operator and field personnel.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Seamless Transition of Critical Infrastructures using Droop Controlled Grid-forming Inverters

Seamless recovery of power to critical infrastructures, after grid failure, is a crucial need arising in scenarios that are increasingly becoming more frequent. Here, this article proposes a seamless transition strategy using a single and unified mode-dependent droop controlled grid-forming inverters. The control strategy achieves the following objectives: 1) regulates the output active and reactive power by the droop-controlled inverters to a desired value while operating in on-grid mode; 2) seamless transition and recovery of power injections into the load after grid failure by inverters that operates in grid-forming mode all the time; 3) requires only a single bit of information on the grid/network status for the mode transition. A framework for assessing the stability of the system and to guide the choice of parameters for controllers is developed using control-oriented modeling. A controller hardware-in-the-loop-based real-time simulation study on a test system based on the realistic electrical network of a commercial-scale medical center is conducted for initial prototyping of the control strategy. A hardware experiment is conducted with two 3 - $\phi$, 480 -V, 125 -kVA grid-forming inverters, a 3 - $\phi$, 480 -V, 270 -kVA grid simulator, a physical grid switch, and a physical load bank. The experimental data establishes the effectiveness of the always grid-forming operation and control of inverters in meeting power delivery objectives when on-grid and off-grid under various kinds of loads and scenarios while minimizing transients during transitions. Furthermore, performance comparison with existing strategies showcases the advantage of the proposed strategy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Evaluating Grid Strength under Uncertain Renewable Generation

The increasing displacement of synchronous generators with renewable resources such as wind and solar via power electronic interfaces causes a reduction in short-circuit strength and weak grid issues. The variation and uncertainty of renewable energy increase challenges for identifying weak grid conditions. This paper proposes an efficient method to analyze the impact of uncertain renewable energy on grid strength. The proposed method uses the probabilistic collocation method (PCM) to approximate the results of grid strength assessment under uncertain renewable generation, in order to reduce computational burden without compromising result accuracy when compared with traditional Monte Carlo simulation (MCS). To improve the accuracy of the approximation results, the proposed method integrates the K-means clustering technique with PCM to select the approximation samples of input variables. The efficacy of the proposed method is demonstrated by comparison with MCS on the modified IEEE 9-bus system and modified IEEE 39-bus system with multiple renewable generators.

grid strength↗

Hardware-in-the-Loop Using Electromagnetic Transient Simulation

Digital real time simulators have the capability to run electromagnetic transient simulations in real time. This capability allows users to leverage the hardware-software combination to evaluate controller performance, protection device performance, and power device performance. This has helped many field deployment projects to be successful and be cost-effective. In this talk, we will present current state-of-art, and future of real time electromagnetic transient simulation and its impacts on field deployment.

08 HYDROGEN↗

Blackstart and Fault Ride-Through Capability of DFIG-Based Wind Turbines

Grid-forming wind turbines must be able to re-energize transmission branches, motor loads, unbalanced loads, and power electronics loads following a blackout. Further, they must ride through faults that can arise during restoration. To tackle these challenges, this paper sets forth a grid-forming control strategy for wind turbines using doubly-fed induction generators (DFIGs). In particular, a special set of feedforward control loops are engineered to mitigate the impacts of restoration transients as well as symmetrical and asymmetrical faults on the regulation of DFIG rotor currents and stator voltages. This paper also leverages two-axis anti-windup regulators to bound two-axis voltage and current commands within ratings. As a result, the controller performance is demonstrated via a high-fidelity simulation model of a notional wind-dominant grid.

17 WIND ENERGY↗

Spatial Impacts of Electric Vehicle Charging on Power Grid Stability: A Downtown Atlanta Case Study

The rapid increase in electric vehicle (EV) charging demand poses a potential risk to power grid stability, particularly as the spatial distribution of this demand remains underexplored. Existing research often focuses on technical optimization models while overlooking the geographic and human dynamics that affect energy consumption. This study addresses this gap by incorporating mobility data to estimate both building energy use and EV charging demand while also considering geographic factors for a better understanding of grid load. Using agent-based simulations and the Open-Source Distribution System Simulator, the study evaluates the effect of various EV penetration scenarios on grid voltage and unbalance. The results show that, although voltage remains within acceptable limits at lower EV penetration rates, significant voltage drop and unbalance occur as EV penetration exceeds 40%, particularly in residential areas with high charging demand. This study offers a framework for integrating spatial analysis and mobility data in power network simulations, providing insights for future EV infrastructure planning.

Pan, Melrose [ORNL] (ORCID:000000031627448X)↗

Decentralized Distribution System Restoration with Grid-Forming/Following Inverter-Based Resources

The high penetration of distributed energy resources (DERs) in active distribution systems has posed challenges to the centralized distribution system restoration (DSR) strategies in current practice. On the other hand, the advancement in smart inverter technologies enables the bottom-up restoration capability. This paper is motivated to develop a 3-layered hierarchical framework for decentralized DSR, based on the grid-forming (GFM) and grid-following (GFL) grid-edge inverters. The first layer presents the tertiary control, which determines the load pickup schedule and generation dispatch of DERs, using the alternating direction method of the multipliers algorithm. The second layer consists of two control functions: GFM control, which regulates voltage and frequency, establishing a stable grid for GFL inverters to follow; and GFL control, which regulates the real and reactive power. In the third layer, the primary control is proposed to regulate the inverter voltage and current, which is developed based on the virtual oscillator control (VOC). Furthermore, the developed framework is tested in the modified IEEE 13-node test feeder. Two scenarios of grid-connected and islanded operating modes are designed, and simulation results demonstrate the effectiveness of decentralized DSR strategies for controlling grid-edge inverters to enhance the distribution system resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

ARIES: Advanced Research on Integrated Energy Systems Research Plan

The Advanced Research on Integrated Energy Systems (ARIES) platform is one of the most powerful research environments anywhere for addressing the speed and scale of change on power systems. This research plan details ARIES capabilities, current and upcoming, and how they relate to objectives for advanced energy systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Large-Amplitude Motion Platform: A New Ocean Simulator Can Help Technologies Succeed

Offshore renewable energy technologies - like wave energy devices, wind turbines, floating solar panels, and hybrid systems - can help decarbonize our power grids as well as offshore activities like international shipping and seafood farming. But it's not always easy to build technologies hearty enough to operate in a powerful ocean environment. And subjecting promising prototypes to real ocean waves can be an expensive, time-consuming, and risky way to get these technologies ready for the high seas. Now, with the National Renewable Energy Laboratory's (NREL's) new testing platform, called the large-amplitude motion platform (or LAMP for short), our experts can replicate powerful ocean waves in a low-risk laboratory setting. The LAMP, coupled with NREL's diverse array of testing instrumentation, can help technology developers rapidly hone their prototypes before embarking on a potentially costly and time-consuming ocean trial.

marine energy↗

IMoFi - Intelligent Model Fidelity: Physics-Based Data-Driven Grid Modeling to Accelerate Accurate PV Integration (Final Report)

This report summarizes the work performed under a project funded by U.S. DOE Solar Energy Technologies Office (SETO) to use grid edge measurements to calibrate distribution system models for improved planning and grid integration of solar PV. Several physics-based data-driven algorithms are developed to identify inaccuracies in models and to bring increased visibility into distribution system planning. This includes phase identification, secondary system topology and parameter estimation, meter-to-transformer pairing, medium-voltage reconfiguration detection, determination of regulator and capacitor settings, PV system detection, PV parameter and setting estimation, PV dynamic models, and improved load modeling. Each of the algorithms is tested using simulation data and demonstrated on real feeders with our utility partners. The final algorithms demonstrate the potential for future planning and operations of the electric power grid to be more automated and data-driven, with more granularity, higher accuracy, and more comprehensive visibility into the system.

14 SOLAR ENERGY↗

IMoFi (Intelligent Model Fidelity): Physics-Based Data-Driven Grid Modeling to Accelerate Accurate PV Integration Updated Accomplishments

This report summarizes the work performed under a project funded by U.S. DOE Solar Energy Technologies Office (SETO), including some updates from the previous report SAND2022-0215, to use grid edge measurements to calibrate distribution system models for improved planning and grid integration of solar PV. Several physics-based data-driven algorithms are developed to identify inaccuracies in models and to bring increased visibility into distribution system planning. This includes phase identification, secondary system topology and parameter estimation, meter-to-transformer pairing, medium-voltage reconfiguration detection, determination of regulator and capacitor settings, PV system detection, PV parameter and setting estimation, PV dynamic models, and improved load modeling. Each of the algorithms is tested using simulation data and demonstrated on real feeders with our utility partners. The final algorithms demonstrate the potential for future planning and operations of the electric power grid to be more automated and data-driven, with more granularity, higher accuracy, and more comprehensive visibility into the system.

14 SOLAR ENERGY↗

Developing a PSCAD Model of the Reduced 240-Bus WECC Test System: Preprint

Fast-acting controls of inverter-based resources (IBR) introduce unprecedented dynamics to bulk power systems and island power grids, especially the high-frequency dynamics ranging from $>5$ Hz to hundreds of Hz. These oscillatory stability problems cannot be captured by the phasor domain simulations, e.g., in PSS/E, Powerworld and TSAT, due to insufficient modeling. Instead, they should be studied by electromagnetic transient (EMT) simulations by using proper EMT dynamic models. This paper develops and validates the PSCAD model of the reduced 240-bus Western Electricity Coordinating Council (WECC) test system. The PSCAD model will be released to the public, which can be used by both academia and power industry practitioners for studying the fast dynamic problems without any Critical Energy/Electric Infrastructure Information (CEII).

240-bus WECC test system↗

Adventures in Computational Grids

Sometimes one supercomputer is not enough. Or your local supercomputers are busy, or not configured for your job. Or you don't have any supercomputers. You might be trying to simulate worldwide weather changes in real time, requiring more compute power than you could get from any one machine. Or you might be collecting microbiological samples on an island, and need to examine them with a special microscope located on the other side of the continent. These are the times when you need a computational grid.

Walatka, Pamela P.↗

Magnetohydrodynamic Turbulence and Reconnection in the Magnetotail

We have used a global MHD simulation with high spatial resolution to investigate the origin and properties of turbulence in the plasma sheet. In this simulation we imposed a steady southward IMF with a magnitude of 5 nT at the upstream simulation boundary for more than three hours followed by ninety minutes of northward IMF of the same magnitude. The solar wind number density was 20 cm-3, the thermal pressure was 20 pPa, and the velocity was 500 km/s in the x direction. The moderately high dynamic pressure confined the magnetotail to the high-grid resolution region. Even for these nominal solar wind parameters and steady driving the plasma sheet became turbulent. The power spectral densities and probability distribution functions computed from the simulations were comparable to those obtained from spacecraft observations. The largest scale vortices were associated with reconnection outflows and, in the southward IMF case, with the diversion of high speed flows in the near-Earth region. Both time and space domain analyses revealed that there were three scales present, the large scale of the driving processes, the intermediate inertial scale and the dissipative scale.

El-Alaoui, Mostafa↗

A Station-hybrid HVDC System Structure and Control Strategies for Cross-seam Power Transmission

Cross-seam high voltage DC (HVDC) transmission in the United States can provide an efficient and flexible bulk power delivery highway between the interconnections. Recent studies have shown significant economic benefits of cross-seam HVDC transmission systems by taking the advantages of load diversity, frequency response, renewable energy diversity, and energy arbitrage in the different interconnections. This paper introduces a station-hybrid system scheme for cross-seam interconnections. Here, the proposed station-hybrid system combines the advantages of line commutated converter (LCC) and voltage source converter (VSC) technologies, thus enabling reliable and flexible bidirectional power flows across the interconnections. Control strategies of the station-hybrid system are investigated with a focus on power flow reversal control under normal operation conditions and grid support control under emergency conditions. The feasibility and effectiveness of the proposed station-hybrid system and corresponding control strategies are verified by simulations in PSCAD/EMTDC.

Station-hybrid system↗