At least 55 records · Page 3

Metal additively manufactured wavy fin cold-plate architecture for improved thermal-hydraulic performance

Rapid growth in artificial intelligence and data center workloads demands high-performance liquid cooling to manage increasing chip power. This study presents two metal-additive-manufactured cold plates with sinusoidal fins, constant-amplitude wavy fins and linearly variable-amplitude wavy fins and compares them against metal-additive-manufactured straight fins using experiments conducted at 1 kW heat dissipation as well as high-fidelity 3D conjugate computational fluid dynamic simulations. The cold plates were printed in AlSi10Mg material and underwent design using a Python-automated workflow prior to manufacture and testing. The experiments show that wavy fins reduce the normalized thermal resistance by 35 to 45 % at water flow rates from 1 to 4 LPM. At a fixed 20 kPa pressure drop, the variable-waviness design lowered peak surface temperature by 9 °C and thermal resistance by 51 %, while edge-channel maldistribution in the constant wavy fin design limited gains. A thermal resistance breakdown revealed that 55–63 % of the total thermal resistance in wavy designs comes from base heat conduction, 27–33 % from fin heat conduction, and 9–13 % from fin heat convection, indicating the need to address conduction bottlenecks. Parametric sweeps identify a 3 mm fin pitch as optimal, and that horizontal inlet/outlet manifolds further reduce pressure drop by 30–60 % and thermal resistance by 9–16 % relative to vertical inlet-outlet manifolds. The results yield comprehensive guidelines for fin geometry, manifold alignment, material selection and additive-manufacturing constraints to realize high-performance liquid-cooled cold plates for power-dense electronics.

3d printing↗

Roadmap on thermodynamics and thermal metamaterials

Thermal metamaterials represent a transformative paradigm in modern physics, synergizing thermodynamic principles with metamaterial engineering to master heat flow at will. As next-generation technologies demand multi-scale thermal control, this field urgently requires systematic frameworks to unify its multidisciplinary advances. Curated through a global collaboration involving over 50 specialists across 25 subdisciplines, this review primarily summarizes two decades of advancements, ranging from theoretical breakthroughs to functional implementations. The review reveals groundbreaking innovations in heat manipulation through the exploration of both classical and non-classical transport regimes, topological thermal control mechanisms, and quantum-informed phonon engineering strategies. By bridging physical insights like non-Hermitian thermal dynamics and valleytronic phonon transport with cutting-edge applications, we demonstrate paradigm-shifting capabilities: environment-adaptive thermal cloaks, AI-optimized metamaterials, and nonlinear thermal circuits enabling heat-based computation. Experimental milestones include 3D thermal null media with reconfigurable invisibility and thermal designs breaking classical conductivity limits. Here, this collaborative effort establishes an indispensable roadmap for physicists, highlighting pathways to quantum thermal management, entropy-controlled energy systems, and topological devices. As thermal metamaterials transition from laboratory marvels to technological cornerstones, this work provides the foundational lexicon and design principles for the coming era of intelligent thermal matter.

heat conduction control↗

Formation of uranium oxy-carbide and uranium carbide via conversion of polymer covered uranium dioxide by laser-based thermal processing

Conventional formation of carbonaceous uranium compounds requires bulk processing using furnace-based approaches. Here, a methodology employing polymer covered uranium dioxide and laser-based heating is explored to enable rapid, localized formation of carbonaceous uranium compounds. Specifically, heating of poly(methyl methacrylate) covered uranium dioxide powder to high temperatures using laser irradiation in argon and methane gaseous environments was investigated. Decomposition of material and reactions induced by laser irradiation were probed in situ by residual gas analysis using a benchtop mass spectrometer. In this study, to determine the effect on the resultant material phase, three different process parameters were varied: gaseous atmosphere, laser power, and laser irradiation time. Material processed under varying conditions was analyzed using powder X-ray diffraction and scanning electron microscopy. This work realized the conversion of uranium dioxide into uranium oxy-carbide(s) and uranium carbide(s) phases, at over 60 wt.%, via the polymer surface application and laser-based thermal decomposition methodology.

36 MATERIALS SCIENCE↗

Mitigation of safety and environmental challenges posed by refrigerants

The abatement of safety and environmental burden associated with low and ultra-low Global Warming Potential (GWP) refrigerants is a critical undertaking. As the industry shifts towards more environmentally friendly alternatives, mitigating the potential risks and ensuring safety standards becomes paramount. The adoption of mildly and highly flammable refrigerants contributes significantly to minimizing the greenhouse gas impact on the environment, aligning with global climate and sustainability goals. However, it is essential to address safety concerns and potential environmental implications associated with the end use of these refrigerants. A method to mitigate the safety risk in a flammable refrigerant based heating, ventilation, air-conditioning, and refrigeration (HVACR) system is the primary focus of this paper. Advent of A2L and A3 refrigerants as replacements to high GWP refrigerants requires careful handling of leak episodes to lower or eliminate the risk associated with creating flammable mixtures capable of fire/explosion hazard. Solid materials tailored to target the molecule of interest (i.e., refrigerant.) by engineering the microporous structure as well as chemically functionalizing the surface to attract and hold on to the chemical compound being removed from the gas stream was realized. Quantitative analysis reveals the adsorbent's effectiveness in reducing leak potential in the range of 40 %–100 % for various refrigerants. Strategic placement and active leak management with negative pressure offer promising avenues for capturing leaked refrigerants, enhancing overall safety.

42 ENGINEERING↗

Iso-cost-performance of thermal energy storage

As thermal energy storage (TES) systems gain increasing recognition as next-generation energy storage solutions, evaluating their techno-economic performance is crucial. This perspective analyzes the cost-performance of latent heat-based TES systems and introduces the concept of iso-cost-performance—maintaining a constant cost per unit energy ($\$$/kWh) despite material degradation. Using an empirical degradation model, we show that after 1200 thermal cycles, the thermal conductivity and volumetric energy density of a paraffin-based phase change material (PCM) decreased by 36.0% and 26.1%, respectively, resulting in a 31.2% reduction in the figure of merit (FOM) and, consequently, the system cost-performance. However, by introducing thermally conductive additives to enhance effective thermal conductivity, the TES system can recover its initial FOM, achieving iso-cost-performance operation. This framework quantitatively demonstrates how degradation-mitigation strategies—such as improving thermal conductivity—can offset material degradations and maintain long-term cost-effectiveness. Beyond PCM-based TES, the proposed FOM-based approach provides a generalized pathway for cost-performance optimization across various TES technologies.

25 ENERGY STORAGE↗

Numerical Simulation Studies of Ultrasonic De-Icing for Heating, Ventilation, Air Conditioning, and Refrigeration Structures

Ice accumulation on heating, ventilation, air conditioning, and refrigeration (HVACR) structures presents significant operational challenges. These challenges include reduced efficiency, increased energy consumption, and potential damage to equipment. Traditional de-icing methods, such as chemical treatments, mechanical scraping, or heating-based techniques, are often labor-intensive, costly, and environmentally harmful. Here, this study uniquely investigates ultrasonic de-icing as an energy-efficient alternative for HVACR applications, focusing on the specific structural geometries found in these systems. A comprehensive numerical simulation framework was developed using finite element analysis to explore ultrasonic wave propagation across four distinct HVACR structures. Key parameters such as ultrasonic frequency, power levels, and the number and placement of actuators were examined for their impact on ice detachment efficiency. Results from simulations on a plate structure reveal that ultrasonic excitation can propagate effectively across large areas (at least 150 × 150 mm), enhancing the de-icing coverage. Lower frequency (e.g., 30 to 45 kHz) excitation results in greater displacement, improving de-icing performance, while increased actuator numbers with the same total power input also enhance effectiveness. Two actuators seem sufficient for the de-icing of a 300 × 300 mm plate. For tube-and-fin structures, specific high-power ultrasonic frequencies selectively excite the fin plates, demonstrating efficient ice removal when actuated on the tube. However, optimal performance requires careful design of actuator placement and vibration modes to accommodate the irregular shapes of these structures.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

BlueCRAB Multiphysics in Support of the U.S.NRC

This presentation provides an overview of the nonLWR modeling and simulation project at INL. It includes a discussion of the various reference plant models developed since 2019 and a more detailed view at results from a monolith-based heat pipe cooled micro reactor.

21 - SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLAN↗

Testing of a 40-kWth Counterflow Particle-Supercritical Carbon Dioxide Narrow-Channel, Fluidized Bed Heat Exchanger

Particle-based primary heat exchangers (HXs) must deliver sCO2 fluid temperatures above 700°C to couple particle-based concentrating solar receivers and thermal energy storage (TES) sub-systems with efficient sCO2 power cycles. Particle-sCO2 HX designs have struggled to meet DOE cost targets (≤ $150/kWth) due to the amount of expensive nickel alloys necessary for manufacturing full-scale, particle-sCO2 HXs. Our team has demonstrated that mild bubbling fluidization of falling particles in a counterflow narrow-channel fluidized bed can reduce required HX surface area and thus, costs by increasing particle-wall heat transfer coefficients hT,w > 800 W m-2 K-1. This paper reports on the fabrication and testing of a stainless steel, particle-sCO2 HX with 12 fluidized-bed channels approximately 10.5 mm deep spaced between diffusion-bonded, micro-channel sCO2 plates. The HX with a core length of ≈0.56 m is fed with CARBOBEAD HSP particles through a short, fluidized freeboard zone just above the core. Testing to date in the National Solar Thermal Test Facility (NSTTF) at Sandia National Laboratories has shown that parallel bed fluidization maintains uniform particle inventory across the instrumented channels. Heat transfer thermal duty between the particle and sCO2 flows exceeds 30 kWth with sCO2 inlet temperatures of 200ºC and particle inlet temperatures up to 440ºC and mass flow rates of 0.2 kg s-1 fluidized by counterflowing gas flow rates of 0.005 kg s-1. Tests at higher particle and sCO2 inlet temperatures (600ºC and 400ºC respectively) are targeted to achieve > 40 kWth with model-predicted overall heat transfer coefficients U > 400 W m-2 K-1.

14 SOLAR ENERGY↗

A Gaussian Process-Based extended Goldak heat source model for finite element simulation of laser powder bed fusion additive manufacturing process

In this study, laser powder bed fusion (L-PBF) additive manufacturing (AM) is a key enabling technology to manufacture highly complex and integrated metallic structures. In L-PBF AM process, the melting of the metal powders and the layers underneath can be governed by either “conduction mode” or “keyhole mode”, with the keyhole mode reportedly leading to porosity and decreased strength and ductility by many studies. In part scale simulations, finite element (FE) model is often used to study the temperature distribution during printing and to predict the residual stress, where a volumetric heat flux with a Gaussian or a double ellipsoidal (Goldak) distribution is often applied as the laser heat source. However, the above heat source models can only capture the melt pool shape in the conduction mode, and fail to capture the transition to keyhole melting mode when the process parameters change. To overcome this inaccuracy, an extended Goldak heat source model is proposed by introducing a laser penetration term as a function of laser parameters obtained from a Gaussian-Process (GP) model. The model is validated by “2D pad” AlSi10Mg L-PBF experiments under a wide range of laser power, scan speed, and laser focus offset, and the results show the model successfully captures the measured melt pool shape in all conditions.

36 MATERIALS SCIENCE↗

Deep learning–based digital twins for heat pumps

Heat pumps are effective cooling and heating appliances to save energy in buildings. However, traditional heat pump models are challenging to integrate with building demands in a co-simulation environment because of the nonlinear thermodynamics of refrigerants. Developing digital twin representatives for heat pumps capable of faster calculations with good accuracy is desirable. This study aimed to establish a generic deep learning–based digital twin for heat pumps with a large amount of high-fidelity data. Two refrigerants for two different heat pumps were considered: an air source heat pump with refrigerant R-410A, an air source heat pump with refrigerant CO 2 , a water source heat pump with refrigerant R-410A, and a water source heat pump with refrigerant CO 2 . Furthermore, results showed that the deep learning (long short-term memory) models effectively represented these four heat pumps as a digital twin: (a) accuracy for training and testing showed smaller than 0.02 for heating electricity and heating demands, and (b) the digital twins showed good consistency with original data for heating electricity and heating demands (root mean square errors of less than 0.12 W and 0.19 W, respectively). Therefore, deep learning–based heat pump models can be used in the co-simulation of building mechanical systems.

Air source heat pump↗

Leveraging metal hydrides for strategic thermal energy control

Attributes of Sensible Heat Materials • Typically based on highly abundant and lowcost materials • Store thermal energy based on the heat capacity (or specific heat) of the material • Duration of thermal energy storage depends on how well the system is insulated • Has the lowest thermal energy storage density • Can be pumped as a fluid Attributes of Latent Heat Materials • Also based on highly abundant materials, but typically cost slightly more than sensible heat materials • Store thermal energy based on the heat of the phase change (i.e., heat of fusion) and the specific heat of the material • Duration of thermal energy storage depends on how well the system is insulated • Has a higher thermal energy storage density than sensible heat materials, but cannot be pumped as a fluid

WARD, PATRICK↗

Geothermal Heat Pump Case Study: Marine Corps Logistics Base-Albany

Geothermal heat pumps can be great alternatives to air conditioners and furnaces, and require less electricity to run. This case study focuses on Marine Corps Logistics Base-Albany and is part of a series: https://www.energy.gov/eere/geothermal/geothermal-heat-pump-case-studies.

case study↗

Refractory-based thermal energy storage for industrial process heat: one-dimensional modeling, control, and optimization

The variable and weather-dependent output of wind and solar power plants present a substantial challenge for planning and operating electricity-systems, particularly in the absence of cost-effective and dispatchable energy storage technologies. This study investigates a high-temperature, electrically heated, refractory-based thermal energy storage (RTES) system that stores electrical energy as sensible heat in dense ceramic bricks over the 950–1800 °C range. The stored heat can be discharged as a controlled hot-gas stream for industrial heating, fuel substitution in high-temperature processes, or electricity generation. The main novelty is a comprehensive modelling, control, mapping, and optimization framework that integrates one-dimensional transient gas–solid heat transfer, fan-assisted discharge, bypass-flow regulation, reheating logic, fan-power evaluation, insulation-loss assessment, and genetic-algorithm-based design optimization. The model uses feedback from outlet temperature and delivered power to regulate discharge, while a two-stage genetic algorithm optimizes brick-channel geometry, gas-flow operation, and multilayer insulation thicknesses. Storage capacities below 50 MWh and discharge powers of 5–30 MW are analyzed to evaluate hold time, thermal delivery, fan-power penalty, heat loss, state-of-charge evolution, and indicative capital cost. Results demonstrate that optimized and well-insulated refractory-based thermal energy storage units can provide stable, efficient, and repeatable heat delivery over multiple discharge cycles. The generated performance and cost maps support modular refractory thermal energy storage as a practical option for large-scale integration of wind and solar generation and for high-temperature industrial process heat.

25 ENERGY STORAGE↗

Benefits of Dual Fuel Heat Pump Grid-responsive Control: A Model-based Control Optimization Approach Using Building and Equipment Co-simulation

Conventional dual fuel heat pumps lack the intelligent control mechanisms to efficiently manage the switch between heat pump and furnace, leading to sub-optimal energy usage and, in some cases, increased operating costs. To resolve this gap, this study applies optimized control on hybrid heat pumps. With a focus on equipment control strategies, we compare the performances of five spacing heating equipment, including a conventional heat pump (HP), a conventional furnace, a dual fuel heat pump (DFHP) with conventional control, a dual fuel heat pump with smart control, and a novel seamlessly fuel flexible heat pump (SFFHP). While DFHP runs on either gas or electricity at any given moment, SFFHP concurrently consumes gas and electricity by continuously optimizing the proportion of each. In this research, a co-simulation framework is developed by integrating a building envelope model with a physics-based heat pump simulation model to analyze the benefits of grid-responsive controls of DFHP and SFFHP. The model-based optimal controls adjust the operation of the heat pump and gas furnace based on utility price signals and marginal grid emission to minimize utility cost and CO 2 emissions for multiple climate zones, different utility tariffs, and marginal grid emission scenarios. Case studies in Chicago and Los Angeles demonstrate that SFFHP and DFHP, with model-based optimal control, can deliver significant reductions in peak demand, utility cost, and CO 2 emission. In Chicago, SFFHP and smart controlled DFHP yield up to 64.7% and 61.7% utility cost reduction and up to 15.7% and 8.5% CO 2 emission reduction compared to the gas furnace. In Los Angeles, SFFHP and smart controlled DFHP achieve up to 43.6% and 40.1% utility cost reduction and up to 13.8% and 14.1% CO2 emission reduction compared to conventional heat pumps. In conclusion, by leveraging the fuel flexibility nature of dual fuel heat pumps, the model-based control optimization approach makes dual fuel heat pump an attractive option for demand response programs.

Control↗

Real time heat load calculation software based on EPICS for Fermilab PIP-II CM tests

Fermilab has a project to improve the proton beam energy which is called PIP-II (the 2nd Proton Improvement Plan). There is a superconducting linear accelerator, LINAC, to improve the proton beam power and the LINAC consists of 5 types of cryomodules (CM), 1 HWR CM, 2 SSR1 CM, 4 SSR2 CM, LB650 CM, and HB650 CM. The prototypes of these cryomodules are being tested at Fermilab’s CryoModule Test Facility (CMTF). Heat load measurements are an important part of the prototype CM testing. The CMTF cryogenic control system was developed based on the ACNET (Accelerator Control NETwork) for CM testing for other projects, but the PIP-II cryogenic control system will be implemented using the Experimental Physics and Industrial Control System (EPICS). As part of the prototype CM testing campaign an EPICS based control system has been implemented at CMTF. This EPICS cryogenic control system includes real time heat load calculation software utilizing the Fortran implementation of Hepak. This paper details the real time heat load calculation software developed for the prototype CM testing including the first results from the HB 650 CM.

Yoon, S. [Fermilab]↗

Real time heat load calculation software based on EPICS for Fermilab PIP-II CM tests

Fermilab has a project to improve the proton beam energy which is called PIP-II (the 2nd Proton Improvement Plan). There is a superconducting linear accelerator, LINAC, to improve the proton beam power and the LINAC consists of 5 types of cryomodules (CM), 1 HWR CM, 2 SSR1 CM, 4 SSR2 CM, LB650 CM, and HB650 CM. The prototypes of these cryomodules are being tested at Fermilab’s CryoModule Test Facility (CMTF). Heat load measurements are an important part of the prototype CM testing. The CMTF cryogenic control system was developed based on the ACNET (Accelerator Control NETwork) for CM testing for other projects, but the PIP-II cryogenic control system will be implemented using the Experimental Physics and Industrial Control System (EPICS). As part of the prototype CM testing campaign, an EPICS based control system has been implemented at CMTF. This EPICS cryogenic control system includes real-time heat load calculation software utilizing the Fortran implementation of Hepak. This paper details the real time heat load calculation software developed for the prototype CM testing including the first results from the HB650 CM.

Yoon, S. [Fermilab]↗

Novel PCM-based fin and tube heat exchanger system for building heating and cooling applications

In the United States, the building sector accounts for 40% of all energy use, and buildings are responsible for more than two-thirds of electricity consumption. Buildings remain the major driver of energy-related carbon emissions, and such emissions are projected to increase in the years ahead because of urbanization and population growth. To accomplish the low carbon energy goal in the building sector, phase change material (PCM)–based thermal energy storage (TES) is increasingly being adopted because it offers several advantages, such as reducing building peak load and energy consumption, enabling large scale deployment of renewables, and improving grid stability. The integration of TES with thermally anisotropic building envelopes (TABEs) is a promising solution because, TABE can redirect natural thermal energy from a building using hydronic loops to TES, and the stored energy can be used later for heating and cooling applications. In this study, we experimentally investigate the thermal performance of a novel fin-tube heat exchanger TES system designed for potential integration with a TABE. An experimental rig for a 5-gal PCM fin-tube heat exchanger system with water as the heat transfer medium is described which records temperatures at the heated and cooled boundaries of the system. Experimental observations provide insight into the role a TES system can play in offsetting a building’s heating and cooling demand and also offer a means to characterize the performance of PCMs for building applications. The scale and study presented in this work will help in the design of future thermal storage systems optimized for storage capacity while also accounting for overall system costs for building applications.

Tamraparni, Achutha↗