Search NASA⌕ Search

SEARCH · Search NASA

Results for “Inverter Based Resources”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 55 records · Page 3

Reliable Protection for an Inverter-Based Resources Dominant Grid: Technology Development and Field Demonstration

The project aimed to address the challenges posed by the rapid growth of inverter-based resources (IBR) such as solar, wind, and battery storage, which have fundamentally changed fault behavior, system strength, and protection performance in bulk power systems. Traditional protection schemes, designed for synchronous generator-dominated grids, are inadequate under high IBR penetration. Overall, the project materially advances protection modeling and simulation capabilities needed to maintain reliable grid protection under high IBR penetration. The results build utility confidence in operating power systems safely and reliably across a wide range of generation mixes, supporting grid modernization goals.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Behavior of Single-Line-Ground Faults in Inverter-Based Resource Dominated Grids Explained

It has been observed by protection engineers that it is difficult for a protective relay to identify the faulted phase during a single-line-ground (SLG) fault in a power system with a high ingression of inverter-based resources (IBR) using currents (phase or sequence). Further studies using electromagnetic transient (EMT) simulation show that the initial operating conditions of the IBRs influence the response of phase currents during an SLG fault. In this letter, we conduct a quantitative analysis using sequence components. We find that the pre-fault condition determines the relative position of the current contributed by the grid versus that from the IBR, and further dictates which phase has the largest magnitude during an SLG condition. Finally, this finding is further verified by the EMT simulation results.

electromagnetic transient simulation↗

Probing Signal-Based Inertia and Frequency Response Estimation for Power Systems With High Levels of Inverter-Based Resources

Power system inertia is the inherent capability of a power system to resist changes in its frequency during disturbances. Real-time inertia estimation technology has become more important due to the low-inertia issues caused by the increasing integration levels of inverter-based resources (IBRs) from renewable energy; however, existing inertia estimation methods hardly consider multiple frequency response controls that act within the same time frame as conventional inertial response, thus making measured inertia values vary under different testing conditions. To resolve this issue, this paper proposes a novel real-time estimation method to simultaneously estimate a power system's inertia constant and frequency response droop constant using a well-designed probing signal. First, we formulate the inertia and frequency response model of a power system with IBRs. Second, through the integration and manipulation of the developed model, we propose a multivariate linear regression-based estimation method that is resilient to measurement noise. Third, we design a probing signal that can be injected by IBRs to incite the required transients for estimation. Finally, we validate the proposed estimation method through comprehensive power-hardware-in-the-loop experiments using inverter hardware and a realistic island power system model. The results demonstrate that the proposed method can accurately estimate the inertia and droop value of the power system with grid-following IBRs and grid-forming IBRs with virtual synchronous machine control.

frequency response↗

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a realtime digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBRonly scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Probing Signal-Based Inertia and Frequency Response Estimation for Power Systems with High Penetration of Inverter-Based Resources: Preprint

Power system inertia is the inherent capability of a power system to resist changes in its frequency during disturbances. Real-time inertia estimation technology has become more important due to the low-inertia issues caused by the increasing integration levels of inverter-based resources (IBRs) from renewable energy; however, existing inertia estimation methods hardly consider multiple frequency response controls that act within the same time frame as conventional inertial response, thus making measured inertia values vary under different testing conditions. To resolve this issue, this paper proposes a novel real-time estimation method to simultaneously estimate a power system's inertia constant and frequency response droop constant using a well-designed probing signal. First, we formulate the inertia and frequency response model of a power system with IBRs. Second, through the integration and manipulation of the developed model, we propose a multivariate linear regression- based estimation method that is resilient to measurement noise. Third, we design a probing signal that can be injected by IBRs to incite the required transients for estimation. Finally, we validate the proposed estimation method through comprehensive power- hardware-in-the-loop experiments using inverter hardware and a realistic island power system model. The results demonstrate that the proposed method can accurately estimate the inertia and droop value of the power system with grid-following IBRs and grid-forming IBRs with virtual synchronous machine control.

frequency response↗

Phasor-Domain Modeling of Inverter Based Resources Considering Unbalanced Grid Faults

A significant increase in inverter-based distributed energy resources (DERs) is expected in distribution systems of the near future. The latest phasor modeling approach of DERs with emerging control technologies can capture relevant dynamics in large-scale three-phase distribution systems with unbalanced construction. However, there is a lack of appropriate phasor models to deal with unbalanced fault scenarios. As such, this paper describes per-phase phasor modeling approach appropriate for unbalanced grid disturbance studies in distribution systems with high penetration of DERs. The overall modeling performance of representative DERs is simulated in phasor domain GridLAB-D environment and validated against controller hardware-in-the loop (CHIL) testing or electromagnetic transient (EMT) based switching model simulation in PSCAD with test cases including different unbalanced grid faults. The high accuracy retained from the simulation verifies the effectiveness of the proposed phasor modeling approach considering interactions between positive and negative sequence signals.

Chen, Zhe↗

Assessing Inverter-Based Resources Modeling Gaps in Commonly Used Short-Circuit Programs

Future bulk power systems are expected to operate with a high penetration of inverter-based resources (IBR). This is anticipated to fundamentally change the system’s short-circuit behaviors and demand a change in existing transmission line protection settings or schemes. Phasor-domain short circuit programs (e.g., ASPEN, CAPE, and CYME) remain the mainstream tools for developing protection settings. However, the system protection community has shared concerns about the accuracy of IBR models in short-circuit programs. This report compares the performance of existing generic IBR models in short-circuit programs with detailed electro-magnetic transient (EMT) models provided by several different IBR manufacturers in PSCAD, to quantify the short-circuit program’s IBR model accuracy, assess their ability to replicate individual IBR controls such as negative sequence current injections, and identify specific gaps in the existing generic phasor-domain IBR models that are currently available.

42 ENGINEERING↗

Evaluating Protection System Performance for a Real-World Weak Grid Area With High Inverter-Based Resources: Preprint

This paper evaluates an existing protection scheme implemented in a real-world weak grid area with a high penetration of inverter-based resources (IBRs). The study aims to assess the reliability and adequacy of protection schemes originally designed for traditional synchronous machine systems and determine whether they can continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with an IBR original equipment manufacturer black-box model is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. These findings provide utilities with valuable insights for improving their protection systems in high-IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Review of Technical Requirements for Inverter-Based Resources in Chile

This document compares the technical requirements in the grid code of Chile (NTSyCS) against the EirGrid (Ireland transmission system operator) and National Grid Electricity System Operator (NESO) grid codes and the Institute of Electrical and Electronics Engineers (IEEE) 2800-2022 standard for conventional inverter technology at the transmission and subtransmission levels in the process of being adopted by system operators in the U.S. The document is intended to be a guide and reference for future updates of the NTSyCS, considering the local system requirements and present improvements in inverter-based resource (IBR) technology. In light of the findings of the aforementioned comparative review, this document proposes and describes the requirements for conventional IBRs that could be incorporated and updated into the Chilean grid code. The document is structured around the main grid challenges posed by the transition to an IBR-dominated grid and conventional IBRs capabilities to help address them. This document does not provide guidance on how this specification should be implemented (e.g., through a mandate or market solution).

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impedance Scan of Inverter-Based Resources and Diesel Generator for Stability Analysis: Preprint

Impedance-based methods are widely used for power system stability analysis with inverter-based resources (IBRs), e.g., assessing dynamic interactions between the power grid and an IBR, control interactions between multiple IBRs, and the sub-synchronous oscillation and damping phenomenon. Since it is difficult to get a numerical model 100% matching with the hardware IBR, using the hardware inverter directly to obtain its output impedance has become a prominent approach nowadays. Therefore, this article presents the impedance scan using hardware IBRs, and also a hardware diesel generator as it still stays with the grid before the grid completely goes to renewable. The devices under test (DuTs) for the impedance scan includes two 3-..phi.., 480 V, 60 Hz commercial grid-forming IBRs (one of 250 kVA and another of 125 kVA rating) in series with ..delta..-Y transformers, one 3-..phi.., 480 V, 60 Hz commercial grid-following IBR (of 125 kVA rating), and a 3-..phi.., 480 V, 60 Hz commercial diesel generator (of 187.5 kVA rating). Using voltage signals perturbed with sub-, inter-, and higher harmonic components, and measuring the current response, the positive-sequence impedances are computed via an offline- based post-analysis. Moreover, best-fit transfer functions are estimated that closely resemble the measured data points of the positive-sequence impedances. Based on the observations from various outcomes of the hardware experiments, this article also provides some fundamental insights on the equivalent positive- sequence impedance of a combination of multiple hardware components by comparing the estimated and the empirically computed impedances. A comparative insight on the damping capability of the DuTs using the positive-sequence impedances of the hardware is also discussed.

grid following inverter↗

Unified Universal Control and Coordination of Inverter-Based Resources, and Validation for a PV + Battery Hybrid Plant

As renewable energy deployment grows, hybrid power plants (HPPs) combining photovoltaic (PV) and battery systems must evolve to offer both energy and grid stability services. These systems typically include a mix of grid-following (GFL) and grid-forming (GFM) inverters, presenting unique coordination and control challenges. This Department of Energy–funded project developed and validated a Unified Universal Control and Coordination (UUCC) framework for such PV + battery hybrid plants, enabling seamless and stable operation, including ultrafast black start, autonomous synchronization, and robust frequency and voltage regulation, under different grid conditions. The project significantly advanced the understanding of inverter-based resource (IBR) control by developing and validating three complementary system-level approaches for hybrid GFL/GFM operation: 1. A combined Virtual Resistance (VR)-based GFL and Virtual Oscillator Control (VOC)-based GFM method, where each inverter type is governed by a specialized control strategy. Together, these achieve stable, fast-response coordination, eliminating inrush current and enabling smooth black start and grid synchronization across a wide range of grid strengths. 2. A Deadbeat-based UUCC strategy, which uses discrete-time, switching-cycle-level control for both GFL and GFM inverters. This approach replaces traditional PI/PLL control with a control parameter-free, high-bandwidth framework that supports stable LVRT and instantaneous synchronization under all conditions. 3. A benchmark comparison with Siemens’ commercial GFM microgrid controller, which provided a fast baseline platform. The commercial approach decoupled v & f control was implemented on a commercial microgrid controller.The baseline commercial benchmark helped highlight superior transient response and black start performance offered by the deadbeat and VOC approaches. These technical contributions offer substantial improvements over conventional inverter control schemes, which often rely on slow phase-locked loop (PLL)-based synchronization, require careful control parameters tuning, and prone to unstable in weak grids with GFL inverters and in stiff grid with GFM inverters therefore challenging for hybrid GFL+GFM under all grid conditions. The deadbeat-based UUCC framework enables simpler, faster, and more robust operation of hybrid IBR systems using wide-bandgap (WBG) devices such as SiC power semiconductors. The rapid expansion of hybrid distributed energy resources (DERs), including residential and commercial PV-BESS installations such as Tesla Powerwall, PV with vehicle-to-grid (V2G) capability, and other integrated configurations, presents complex operational challenges for medium-voltage radial distribution feeders. These networks are subject to frequent disturbances such as faults, switching operations, rapid reclosing sequences, and feeder reconfigurations, all of which introduce dynamic stress on IBRs. In addition, planned feeder segmentation and deliberate islanding for resilience will require DERs that can autonomously perform blackstart, establish voltage and frequency references, and resynchronize with the main grid. The advanced deadbeat-based UUCC control and blackstart functionalities developed in this project directly address these requirements, enabling decentralized and autonomous operation of inverter-dominated DERs in distribution systems under a wide range of fault and reconfiguration scenarios. From a public benefit perspective, these innovations enable more reliable and cost-effective integration of renewable energy into distribution networks. The ability to autonomously black start and stabilize grids under varying grid conditions support accelerates recovery from outages and support decentralized resilient energy systems. By reducing system complexity and improving performance, this project lays critical groundwork for future inverter-dominated power grids that are clean, reliable, and accessible to all.

14 SOLAR ENERGY↗

Advanced Measurements for Resilient Integration of Inverter-Based Resources: PROGRESS MATRIX Final Report

As nearly every aspect of the electric power grid undergoes rapid change, measurement technologies that support grid operation and planning must evolve as well. The rapid large-scale deployment of inverter-based resources (IBRs) vital to achieving the nation’s clean energy goals has in some cases led to negative impacts on the reliability and security of the bulk power system (BPS). Advanced power system measurements, including synchronized phasor and waveform measurements, are key to making IBR integration secure and reliable. To this end, the Department of Energy (DOE) initiated the PROGRESS MATRIX project to develop advanced measurement capabilities and analytics that will accelerate adoption of IBRs while improving the reliability and resilience of the BPS. This report discusses the outcomes of the project, which was a joint effort between the Pacific Northwest National Laboratory (PNNL), Oak Ridge National Laboratory (ORNL), the National Renewable Energy Laboratory (NREL), and Lawrence Berkeley National Laboratory (LBNL). In the project’s first year, PNNL, NREL, and ORNL partnered with the Bonneville Power Administration (BPA), the Western Area Power Administration (WAPA), and Kauai Island Utility Cooperative (KIUC) to understand their existing measurement capabilities and the gaps limiting deployment of IBR-focused measurement systems and analytics. The other primary activity in the first year was deployment of GridSweep instruments, which provide unprecedented precision in waveform measurement while probing distribution systems. The instruments were deployed at Dominion Energy and the University of California, Riverside. In the project’s second year, the input from partner utilities and collected measurements were used to advance measurement capabilities. Twelve analytical methods spanning disturbance analysis, power plant evaluation, feeder evaluation, and modeling were developed. Two software tools were developed, one to analyze GridSweep measurements and another to automatically evaluate the control performance of power plants connected to the BPS. Testbeds at ORNL and NREL were augmented to better enable studies of IBR integration. The project culminated in demonstrations of these analytical methods, software tools, and testbeds, both in the field and in the laboratory. This report discusses these various accomplishments and documents the significant progress in developing advanced measurement capabilities to support the secure, reliable, and accelerated adoption of IBRs in the BPS.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Inertia Estimation Under High Penetration of Inverter-based Resources

Many types of renewable energy sources, especially solar and wind generation, are connected to the electric grid through power-electronic-based interfaces (inverters). These inverter-based resources (IBRs) are mechanically decoupled from the grid, which reduces system inertia and thus may compromise its stability and reliability. In this study, we examine the impact of high penetration of IBRs on the power grid’s inertia. To achieve this, we intentionally introduce disturbances into a simulation case study, such as a step load change, to observe and record the system’s frequency responses. This study offers a nuanced understanding of how the integration of IBRs affects grid stability, and it provides essential guidance for future grid management and resilience strategies.

Yadav, Ajay↗

A Sensitivity-driven Wide Area Protection (SWAP) Coordination Tool for High Penetration of Inverter-based Resources (IBR)

Traditionally, power system generation sources have been composed of synchronous generators, of which the fault current behavior is understood with minimal differences between generation size and types due to the physics of their construction. Present protection schemes and modeling methods are based upon these understood characteristics. Most renewable generation is composed of inverter-based resources (IBR), in which fault current is determined by switching control software and hardware limitations, each of which can vary between manufacturers and even between models of the same manufacturer. The resulting fault current is low in magnitude, low in negative-sequence current, unpredictable phase angles, and is a challenge to model. These characteristics also result in a challenge to traditional protection schemes and fault simulation software. To address several of these concerns, the project has the following goals: 1. Improve IBR models: Improve IBR models used in short circuit (SC) programs to accurately capture the response of IBRs at the bulk power system (BPS) level for fault and protection studies. 2. Develop automation tool: Develop an automation tool that allows engineers to identify protection coordination and sensitivity issues by performing SC and protection coordination studies in a high IBR-penetrated grid by applying variations to the IBR models, faults, contingencies, etc. 3. Develop schemes: Develop new protection mitigation solution schemes that complement the existing protection systems to ensure safe operation of the BPS with higher IBR penetration levels. The project team did not achieve this final goal, as the Department of Energy (DOE) stopped the project early due to changes in DOE funding priorities. The termination notice came at the beginning of the final project phase, while the team was identifying and beginning to investigate protection issues. It should be noted that the team discussed a 100% penetration scenario. However, this scenario would require the use of grid-forming IBR models that are not presently available. Since developing these models requires additional effort, the 100% penetration scenario was not pursued during this project. In the future, developing the methodology and models for the 100% scenario could benefit the industry.

14 SOLAR ENERGY↗

A Review on Protection Challenges of Transmission Lines Connected to Inverter-Based Resources

Utilities, university researchers, research institutes, and relay manufacturers have performed studies to investigate different aspects of high IBR penetration. Almost all studies support 1) creating international and national standards to regulate the IBRs, 2) revising engineering tools to address shortcomings, and 3) adjusting the protective relay settings to resolve protection problems. This paper summarizes the studies and research conducted in recent years to quantify the impact of IBR penetration on transmission line protection and to identify potential solutions to improve the dependability and reliability of grid protection systems.

14 SOLAR ENERGY↗

A Digital Twin for an Inverter-Based Resource Power Plant: Real-time data streaming unlocks situation awareness

Here, this study presents the development and successful implementation of a digital twin specifically designed for a grid-connected IBR power plant. By integrating a reduced-order model of the IBR system and dynamically updating the grid impedance with real-time data, the digital twin effectively captures and replicates the behavior of the physical system. Its accuracy and reliability are validated through critical test scenarios, including a three-phase fault and a line-tripping event. The results confirm that the digital twin closely emulates its physical counterpart, demonstrating its strong potential for real-time analysis, system monitoring, and predictive decision making in modern power systems.

Digital twins↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

This presentation starts with the details of IEEE 2800-2022 requirements of IBR for balanced and unbalanced faults. Then, it shows how to design a droop based GFM control to be IEEE 2800-2022 compliant. An performance evaluation is carried out to see if three OEM GFM inverters 2800-2022 compliant or not. And finally we show how IEEE 2800-2022 complaint and non-compliant GFM inverter will impact the transmission line protection elements, such as directional element and FID. Finally, recommendations are made if the GFM is not IEEE 2800-2022 compliant to disable the protection elements that rely on reliable and regulated negative sequence current.

24 POWER TRANSMISSION AND DISTRIBUTION↗