Investigation of Pore Size Effect On Spray Cooling Heat Transfer With Porous Tunnels
Previous studies have shown that spray cooling heat flux enhancement may be attained by using enhanced surface structures. However, most enhanced surface spray cooling studies have been limited to extended surfaces relative to the base surface. In this study, experiments were conducted to study the effects of pore size on spray cooling heat flux when using porous tunnels. The porous tunnels where placed sub-surface relative to the top of the heater block. Pores of varying size were machined in the top of the heater block leading into the sub-surface tunnels. Pore diameters varied between 0.25 mm and 1.0 mm. Each copper block had a projected cross-sectional area of 2.0 cm(sup 2). Measurements were also obtained on a heater block with a flat surface for baseline comparison purposes. A 2x2 nozzle array was used with PF-5060 as the working fluid. Thermal performance data was obtained under nominally degassed (chamber pressure of 41.4 kPa) conditions with a bulk fluid temperature of 20.5 "C. Results for both the study show that the highest critical heat flux (CHF) attained was 141 w/cm2 using pores 1.0 mm in diameter. This gave an enhancement of 75% relative to the flat surface case under nominally degassed conditions.