At least 55 records · Page 3

DC Circuit Breakers: A Technology Development Status Survey

DC circuit breakers (DCCBs) play a significant role in obtaining the reliability and stability of DC power systems. Selective and fast isolating of faults minimizes the power supply outages to end electricity users and protects the power converters implemented in the DC system. During the last decades, DCCBs have been deeply investigated in industry and academia. There has been impressive progress in terms of efficiency, response time, power-density, lifetime, and electrical operating ratings. Introducing wide bandgap (WBG) devices further has motivated researchers to propose more efficient and novel topologies. This paper provides a point of reference and a background review for DCCBs from novel aspects, fulfilling absent parts in the literature. The elaborated subjects include current commutation circuitry, DCCBs trip-curves developments, newly added functions to DCCBs, as well as marketing analysis. The advancements of DCCBs are surveyed and development needs are recognized. This paper aims to identify the future research needs of DCCBs for emerging DC power systems.

42 ENGINEERING↗

Evaluating the Incident Energy of Arcs in Photovoltaic DC Systems: Comparison Between Calculated and Experimental Data

Solar Photovoltaic (PV) systems have permeated the energy generation world at a very high rate, some of the safety codes and standards are still lagging in accurately assessing the hazards and risks associated with PV array arcing energies. Safety professionals and maintenance workers using NFPA 70E have utilized the Doan, Stokes & Oppenlander or Enrique models, meant to determine arc energies in DC power systems using the maximum power method. These methods may lead to an overestimate of energy available in PV systems during a fault. Since PV modules/arrays are non-linear, current limited DC devices, some of these calculation methods may not accurately predict fault energy. This paper will validate current arc energy models for PV systems by comparing experimental and calculated data. Additionally, this data will help modify the current NFPA 70E models related to smaller solar arrays. Understanding where the real safety threshold for DC arc flash in PV systems exists will help maintenance and safety professionals better prepare for a variety of work related activities. This paper will analyze real arc data taken for PV systems <1000VDC and <60amps and compare this to the calculated incident energy models, to include 70E. Thus, using these comparisons, it may be possible to reduce the safety hazard severity and thus relax the PPE requirements for installation and maintenance crews.

14 SOLAR ENERGY↗

Optimized Highly Efficient SSCB Using Organic Substrate Packaging for Electric Vehicle Applications

Solid State Circuit Breakers (SSCBs) are an attractive protection solution for their arcless current interruption and fast actuation speeds over mechanical breakers. This paper proposes a Bidirectional SSCB (BSSCB) with a thermally defined and digitally controlled current time profile for fault protection in EV and other low-voltage DC systems. The paper proposes an organic packaging approach utilizing flex circuitry to develop a reliable, cost-effective power module for BSSCBs. The paper studies transient heat transfer in the power modules using finite element analysis (FEA). An RC themal ladder network is extracted to define a fusing curve. To demonstrate and verify the design, a 1kV/50 A SiC MOSFET BSSCB prototype is fabricated and tested, having a power density of 60 W/cm3 and 4x reduction in form factor over presently researched breakers. Also, given are results for 750 V/150 A operation showing interruption in 2.4 μs.

organic power packaging↗

Review on Switching Device Fault, Protection, and Fault-Tolerant Topologies of Current Source Inverter

The fault modes, protection, and fault-tolerant topologies of voltage source inverters have been investigated for decades. However, issues and solutions related to the fault modes of current source inverters are less well understood. This paper summarizes some of the key topics relevant to a fault in current source inverters, including types of fault modes and their ramifications, post-fault protection methods, and fault- tolerant current source inverter topologies that have been presented in the literature.

42 ENGINEERING↗

Grid Forming Control of PMSG-based Wind Turbines under Fault Conditions

Grid-forming control is widely envisioned as core technology ensuring stable operation of future power systems with increasing deployment of converter-interfaced renewable generation. However, research on grid forming control of wind turbines, especially under faults, is still in its early stages. In this context, this paper augments dual-port grid-forming control for type IV wind turbines with auxiliary controls to enable reliable fault ride through capabilities. In particular, the proposed control does not require a dc chopper or mode switching to grid-following control. Instead, energy-balancing dual-port GFM control is augmented with active rotor speed damping control and threshold virtual impedance for current limiting during faults. Different operating conditions of wind turbines are considered in a detailed electromagnetic transient simulation study to validate the effectiveness of the proposed control.

Lyu, Xue↗

A Hot‐Swappable, Fault‐Tolerant, Modular Power Converter System for Solar Photovoltaic Plants

The performance metrics of the state-of-the-art commercial solar inverters, such as system cost, operation and maintenance (O&M) cost, service life, reliability, maintainability, and power density are much lower than the target metrics needed to achieve SunShot’s 2030 levelized cost of energy (LCOE) goals. To overcome the shortcomings of the existing solar inverters, this project proposed a novel Hot-Swappable, Fault-Tolerant, Modular Power Converter (HSFT-MPC) concept for solar photovoltaic (PV) plants and proved the concept through the design, fabrication, and laboratory test validation of a single-phase HSFT-MPC prototype. The HSFT-MPC has the following distinct advantages over the state-of-the-art: 1) elimination of harmonic/ electromagnetic interference (EMI) filter in the inverter stage due to the novel topology, 2) lower system cost and higher power density due to the modular design, elimination of harmonic/EMI filter, and lower cooling requirement, 3) higher efficiency due to lower switching frequencies, 4) higher reliability and longer (50 years) service life due to simpler cooling and fault tolerance capability, 5) easier installation, lower O&M cost, and improved maintainability due to the modular design and hot-swappable power electronic building blocks (PEBBs), and 6) improved manufacturability due to the modular design. This project developed a single-phase HSFT-MPC prototype with 25kW nominal output power, 2.4kV, 60Hz nominal AC output, lower than 5% AC output voltage total harmonic distortion, over 5 kW/L inverter power density, and 99.4% inverter peak efficiency, being tolerant to failure of single and multiple PEBBs, and capable of hot swapping of the failed PEBB(s). The HSFT-MPC enables uninterruptable operation of the solar PV plant when failure of single or multiple PEBBs or PV modules occurs. Compared with the existing solar inverters in the market, the HSFT-MPC is expected to reduce the inverter failure-caused downtime and energy losses of solar PV plants by more than 60% and 50%, respectively. Project findings have been presented at major conferences in the field and published in peer-reviewed papers, which added new knowledge to the field of power electronics for solar PV systems. A minicourse on Solar PV Systems was developed for outreach activities. The minicourse will help attract young individuals to the renewable energy profession which has a significant talent shortage. The HSFT-MPC is expected to overcome all of the shortcomings of the state-of-the-art solar inverters in terms of cost, efficiency, service life, reliability, maintainability, and manufacturability targets needed to achieve SunShot’s 2030 LCOE goals. Therefore, the proposed HSFT-MPC concept has the great potential to disrupt the current solar inverter market. This project created a pathway towards industry adoption of the HSFT-MPC to help achieve 50-year service life solar PV systems. Since the solar PV plants using the HSFT-MPC will feature with higher reliability, longer service life, and easier maintenance, they are particularly useful for the rural areas with underserved populations that demand reliable and affordable clean electricity. The outcomes of the project have the strong potential to address national needs in the field of renewable energy to reduce CO 2 emissions from the electricity sector, reduce imports of energy from foreign sources, and improve energy security, efficiency, and sustainability. Since electricity is used in almost all of society’s sectors, the outcomes of the project will benefit various sectors of society and economy.

14 SOLAR ENERGY↗

Mitigating commutation failures in HVDC systems with SFCL deployment

Commutation failures represent a prevalent issue encountered in line-commutated-converter high voltage direct current (LCC-HVDC) systems. As the widespread deployment of HVDC systems continues, the risk associated with commutation failures increases, posing a growing threat to power grids due to their potential to trigger severe consequences, including cascading failures and widespread blackouts. This research paper aims to address the significant issue of commutation failure within direct current (DC) systems through advocating for the use of resistive-type Superconducting Fault Current Limiters (R-SFCLs). To substantiate the efficacy of this proposed strategy, an array of simulations are executed using the PSCAD/EMTDC software. This comprehensive study investigates the performance characteristics of R-SFCLs configured with varying resistance values, scrutinizing their response under diverse fault resistance scenarios and distinct fault initiation times within the LCC-HVDC system. The outcomes of these simulations are that SFCLs confer significant advantages for mitigating commutation failures, surpassing traditional mitigation methods in terms of effectiveness. Consequently, SFCLs emerge as an optimal solution to prevent commutation failures in the HVDC systems.

Commutation failure↗

Thoughts and Hypotheses on the Metrics and Needs for the Stability of Highly Inverter-Based Island Systems

As levels of wind, photovoltaics (PVs), and battery energy storage on power systems rise, it is useful to be able to quickly compare how much generation (instantaneous power and annual energy) comes from these inverter-based resources (IBRs). A commonly used metric is the percentage of inverter-based generation (% IBR) in a dispatch scenario (as a percentage of the total generation or total load), which can be useful for estimating when certain operational challenges arise (high rates of change of frequency, underdamped control interactions, low system strength, low fault current availability, and so on). Another similar and commonly used metric pioneered on the relatively large island of Ireland, system nonsynchronous penetration (SNSP), is similar to the % IBR and is subject to similar limitations. SNSP has the advantage of handling high-voltage dc in a defined way.

fault currents↗

Intelligent, grid-friendly, modular extreme fast charging system with solid-state DC protection

The development of electric vehicle (EV) charging infrastructure is crucial for the widespread adoption of electric transportation. However, implementing such infrastructure is a complex task that requires consideration of factors such as space limitations, adherence to industry standards, grid capacity, and other technical and policy issues. This project seeks to create a framework for the efficient design of compact medium voltage (MV) extreme fast charging (XFC) stations for EVs. The station design involves the use of a solid-state transformer (SST) that connects to the MV distribution network, delivering power to a shared DC bus. This innovative approach eliminates the need for a step-down transformer to provide low-voltage service by connecting directly to the MV distribution network. Eliminating the low-frequency transformer not only reduces the system footprint and losses but also eliminates inrush currents during grid black-start. Additionally, placing power electronics directly on the distribution system allows for high-bandwidth filtering and power factor correction. The inclusion of a shared DC bus enables multiple charging dispensers and DC storage/generation units to connect, forming a DC microgrid. This setup facilitates power sharing with minimal conversion stages. The project showcases a DC distribution network protected by intelligent solid-state (SS) DC circuit breakers (DCCB) capable of isolating the smallest section of the faulted circuit much faster than existing mechanical solutions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Studying the Impact of IBR Modeling on the Commonly Applied Transmission Line Protective Elements

It is a well-accepted fact that detailed inverter-based resource (IBR) models are needed for electromagnetic transient (EMT) studies, especially for protection studies and protection designs. However, it is not clear which modeling aspects should be included in the EMT model to accurately represent the IBR fault responses. Therefore, this paper addresses this gap by evaluating the impact of key modeling aspects (DC source, inverter model, power control, current/voltage control, and current limiting) on the response of protective relay elements both qualitatively and quantitatively. Both grid-following (GFL) and grid-forming (GFM) IBR models are comprehensively evaluated through a simplified real-world transmission network by varying the IBR modeling aspects, fault locations, and types. The insights and findings from this paper will benefit the power system protection community because this work provides modeling requirements and guidelines for IBR modeling so that correct IBR models will be used for protection scheme settings design.

grid-following inverter↗

FIDVR Capability of Hybrid Grid-Forming PV Power Plants During Feeder Restoration

Grid-forming inverters must optimally transfer power from dc-coupled photovoltaic arrays and batteries into an ac grid. Further, they must be able to restore single-phase induction motors (SPIMs) and withstand fault-induced delayed voltage-recovery (FIDVR) events. These resilience and reliability challenges are addressed here by: (i) engineering a controller to optimally operate dc-coupled hybrid resources; (ii) modeling residential air-conditioning compressors for restoration/FIDVR studies; and (iii) analyzing SPIM thermal-relay performance under limited inverter currents and designing an electronic protection for stalled SPIMs. Furthermore, these contributions are demonstrated via electromagnetic-transient simulations and can be helpful to understand recommendations by the North American Electric Reliability Corporation.

14 SOLAR ENERGY↗

Control Design and EMT Simulation Toward the Restoration of Faulted Wind-Dominant Grids

Present power engineers have been challenged to employ electromagnetic transient (EMT) simulations to study the restoration of wind-dominant grids. This paper addresses this hurdle by developing strategies to: (i) reliably control the dc-link voltage of grid-forming wind turbines with dc-coupled batteries, (ii) tune controllers to stably interconnect wind power plants into a grid under recovery, and (iii) autonomously make restoration decisions if transmission faults occur during restoration. These contributions are assessed via EMT simulations of wind-dominant versions of the WSCC 9-bus grid and a 22-bus power system. Furthermore, this paper is significant to address recommendations by the North American Electric Reliability Corporation.

17 WIND ENERGY↗

SCR-based Medium Voltage DC Solid-State Circuit Breaker

This paper describes a medium voltage solid-state circuit breaker (SSCB) based on SCR technology, featuring short fault-interruption time and a minimal turn-off auxiliary circuit. The SSCB design incorporates a specialized SCR and a commutation circuit designed with an objective to reduce the required SCR hold-off/turn-off time, tq, which primarily determines the fault interruption duration. To validate the design, simulation analysis is presented, and a 1.5 kV 300 A SSCB prototype has been built and tested. The results confirm the effectiveness of the proposed design philosophy demonstrating the SSCB's ability to interrupt a 200 A load current in less than 50 μs. The proposed SCR-based SSCB has been developed for DC applications but is equally applicable to AC applications.

Kandula, Prasad [ORNL] (ORCID:0000000174017284)↗

Comprehensive AI-based System for Control, Sensor Estimation, and Fault Detection of Cascaded Multilevel Inverters

In this paper, an Artificial Intelligence-based (AI) system is proposed for an 11-level cascaded H-bridge multilevel inverter (MLI) with the aims of harmonic suppression and reliability enhancement. The system consists of three seamlessly integrated Neural Networks (NNs). First, a multilayer perceptron is used to generalize the optimal switching angles for selective harmonic elimination under non-equal DC voltages. Next, an autoencoder NN estimates the voltage sensor readings to address potential drifting. Finally, a perceptron NN detects inverter faults based solely on the output voltage of the MLI. Simulation scenarios were evaluated, and the results show that the proposed system provides a comprehensive solution for the robust operation of the MLI. The proposed solution is capable of minimizing the targeted harmonics orders with minimal impact on the fundamental voltage, even when the voltage sensor drifts. Furthermore, the inverter under fault conditions was successfully identified.

Rezende da Costa Reis Kimpara, Renata↗

A High-Speed High-Power-Density Non-Heavy Rare-Earth Permanent Magnet Traction Motor

There has been a global push for higher torque density and lower cost traction motors. The use of non-heavy rare-earth (non-HRE) permanent magnet materials in traction motors are being investigated for the sustainability, profitability and affordability of electric vehicles and to broaden their adoption. A 20,000-rpm permanent magnet traction motor using non-HRE magnet materials is proposed. A dual three-phase winding configuration driven by a segmented dual three-phase drive is proposed to reduce the current ripple, and as a result, the DC Link capacitor, as well as to ease the voltage constraint at high speed and eliminate any risk of uncontrolled regeneration. Furthermore, the dual winding configuration enables a fault tolerant design which is useful for reliability. The paper presents comprehensive electromagnetic, thermal and mechanical designs and analyses using an integrated approach. The results have shown that the design is robust against demagnetization and confirmed its thermal and mechanical viability.

47 OTHER INSTRUMENTATION↗

Power Electronics Based Self-Monitoring and Diagnosing for Photovoltaic Systems

Faults in photovoltaic (PV) systems can seriously affect the efficiency, energy yield, cost, safety, and reliability of PV plants. Condition monitoring of PV plants is, therefore, a very important approach to estimating the health condition of PV modules and power electronics in the system. However, additional hardware for PV system monitoring adds cost to the system's operation; delayed maintenance service also causes additional energy production loss. The Center for Power Electronics Systems (CPES) at the Virginia Polytechnic Institute and State University and Siemens Cooperate Research developed the online impedance measurement for a PV panel self-monitoring and diagnosing technology using the DC-DC converter connected to the panel. Small-signal impedances of a monocrystalline silicon PV panel were modeled and simulated to reflect fault conditions such as the short-circuit, hot-spot, and junction box faults. Modeling and simulation results were validated firstly using a test setup consisting of a solar simulator, a network analyzer, small-signal injectors, and a monocrystalline PV panel rated at 300 W.

14 SOLAR ENERGY↗

A Review on Protection Challenges on Transmission Lines Connected to Inverter Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses. Utilities, university researchers, research institutes, and relay manufacturers have performed studies to investigate different aspects of high IBR penetration. Almost all studies support 1) creating international and national standards to regulate the IBRs, 2) revising engineering tools to address shortcomings, and 3) adjusting the protective relay settings to resolve protection problems. This paper summarizes the studies and research conducted in recent years to quantify the impact of IBR penetration on transmission line protection and to identify potential solutions to improve the dependability and reliability of grid protection systems.

14 SOLAR ENERGY↗

A review on protection challenges of Transmission Lines connected to Inverter Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses.