Search NASA⌕ Search

SEARCH · Search NASA

Results for “electromagnetic transients”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 55 records · Page 3

Observation of Electromagnetic Transients in a Nb3Sn 4-layer Dipole Mirror Magnet

During testing of the Stress Managed Cosine-Theta dipole mirror magnet SMCTM1, magnet quenches were observed following large voltage spikes in the half-coil voltage taps which preceded normal quench initiation. Following some recent work at CERN measuring power current converter transients in relation to flux jumps, an additional differential current probe was added to the magnet instrumentation. Measurements of this probe, as well as the half coil voltage taps show a fast and substantial current change preceding the quench, hinting at coil motion. A simple model based on relative shift of the inner and outer layer coils was developed which suggests the magnitude of coil shift events is on the estimated relative coil shift from the magnet constraint conditions. The behavior is shown to be reversible and characteristic of stick-slip.

Krave, Steven [Fermilab] (ORCID:0000000217521457)↗

Electromagnetic Transient Modeling of Data Centers

This report serves as a user manual for the accompanying EMT model library developed by the National Laboratory of the Rockies (NLR) for various equipment in large data centers. The EMT model library enables detailed modeling of large data center loads for conducting grid stability studies. The EMT model library for data centers include detailed models of a 5.5 kW power supply unit (PSU), a 2.5 uninterruptible power supply (UPS), a 260 MW gas turbine-generator, a 500 kW motor load, and a 33 kW IT rack. These components represent all major equipment in data centers that need to be modeled for performing grid stability studies for data centers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Electromagnetic Transient and Three-Phase Phasor Co-Simulation Platform for Studying Distribution System Transients with High Pentration of DERs

Inverter vendors usually have electro-magnetic transient (EMT) models of distributed energy resources (DERs) for validation purposes and these types of models are usually black-boxed considering intellectual property (IP) protection. Limited by small simulation time step for the entire power system network, studying the system-level responses of DERs in EMT simulators is more time-consuming as the network size increases. Meanwhile, vendors usually do not have inverter models that can be used in three-phase phasor-domain simulators. This paper proposes a platform that can dynamically co-simulate the EMT inverter models and three-phase phasor-domain distribution networks considering high penetration of inverter-based DERs. This platform is very useful for evaluating the impacts of vendor-provided black-box DER model on distribution system dynamics. The co-simulation platform is validated against the full EMT model using a simple two-inverter test system and tested using IEEE 34-node test feeder.

Liu, Yuan↗

Computational Math Problems for a Clean Energy Future

Cutting edge computational mathematics are ubiquitous in renewable energy research. Problems in resilient and reliable electric grid operations, infrastructure planning, wind farm yaw control, and more demand sophisticated and scalable computational tools that enable the transition of renewable energy technologies from proof of concept to deployment into our energy system. The mission of the Computational Science Center at NREL is to lead the lab's efforts to solve energy challenges using high-performance computing (HPC), computational science, applied mathematics, scientific data management, visualization, and informatics. In this poster, we provide a short overview of three areas of computational mathematics research at NREL: wind power scenario generation for stochastic grid operations and infrastructure planning, improved rational function approximations for electromagnetic transients codes, and wind farm yaw control using a combination of the Alternating Direction Method of Multipliers (ADMM) and reinforcement learning (RL). Increasing penetrations of renewable energy into power grids motivate the investigation of new approaches to characterizing uncertainty for five-minute economic dispatch problems. Similarly, as the penetration of distributed energy resources on power grids increases, it becomes important to revisit our methods of modelling transient phenomena, i.e. electromagnetic transients programs. Finally, the combination of ADMM and RL for wind farm yaw control presented here can potentially increase the efficiency of the deployed distributed controllers by orders of magnitude.

ADMM↗

Understanding Line Losses and Transformer Losses in Rural Isolated Distribution Systems

Rural, isolated power systems in the mainland U.S. and in states like Alaska and Hawaii are powered by assets like diesel generators. These rural, isolated power systems also cannot operate at the higher band of medium voltage (like 69kV). They are primarily in the 12 to 14 kV range to keep the cost of the distribution investments lower. Because of this mid-band medium voltage range, the line losses and distribution transformers losses consume significant diesel consumption (almost 10 percent of the peak load). This work considers one such power system powering an isolated system and presents key findings online losses, and transformer losses. Understanding and documenting the impacts is critical for these communities operating their power systems and take actions to reduce expensive diesel consumption. In this paper, we will present one such typical grid and model it in electromagnetic transients (EMT) domain. We used the tower structure, under ground cabling installation to develop high fidelity models of lines. We also used high fidelity models of distribution transformers to present the no-load losses and full load loses. We will also present technical solutions available commercially off-the-shelf to reduce these losses and reduce diesel consumption. This work will be a primer for communities to understand the technical challenges and to understand the possible solution available to solve such challenges for rural, isolated power system operators.

blackstart↗

Evaluation of a Reduced-Order Model for IBR Fault Response Representation via OEM Blackbox Models: Preprint

Driven by the need to capture the electromagnetic transients of transmission lines, inverter switching behavior, and detailed control systems, electromagnetic transient (EMT) studies have become increasingly important in industry, such as IBR interconnection study and fault study. However, original equipment manufacturer (OEM) inverter models typically include extensive parameters and proprietary settings that are unavailable to protection engineers. This paper introduces a data-driven, reduced-order model (ROM) developed as a PSCAD library component for use in EMT-based fault studies. The ROM replicates key OEM model behaviors without requiring detailed knowledge of control design or parameterization. The accompanying Python automation scripts streamline data generation, parameter fitting, and validation. The ROM's performance is demonstrated through comparison with both IEEE 2800-compliant and non-compliant OEM models in a real-world power system. Relay responses show nearly identical results, while simulation runtime is reduced by an average of 32.8\%, highlighting the ROM's practicality for protection engineers.

14 SOLAR ENERGY↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids: Preprint

Increased deployment of Distributed Energy Resources (DERs) and microgrids are significantly changing the operation of distribution grid. Increasing penetration of power electronics based DERs also raise several operational problems such as protection coordination issues, voltage raise, recloser synchronization, stability, and frequency control. Legacy systems are designed for unidirectional power flow. Bidirectional power flows, and varying short circuit levels are some of the major challenges in implementing these legacy protection schemes for future power grid with high penetration of power electronics based DERs. Inverter based DER’s can contribute to a maximum of 2 p.u. fault current. Interconnection standards might require even lower fault current contribution. If these protection related challenges are not addressed, it will result in limiting the penetration of DERs in distribution feeders. In this paper, the feasibility of high frequency signature generated by transients is evaluated to identify and locate faults in a distribution system. The paper will discuss the need for an accurate line modeling approach to accurately capture the high frequency signatures. These high frequency signatures are naturally occurring electromagnetic transients for events such as switching events in the network, faults events, etc. This is different than that implemented in transmission systems as the proposed approach utilizes advanced signal processing techniques to retrieve valuable information from the high frequency signatures generated during faults and does not just rely on time delay measurements between reflections of the high frequency signals. In the full paper, information of a modified IEEE distribution feeder test system to accurately model the high frequency signatures will be provided. The distribution lines will be modeled using universal line modeling (ULM) technique in an electromagnetic transients program (EMTP) modeling platform. Different test cases will be simulated and these test cases will include different fault types, multiple fault locations, capacitor bank switching, etc. The feeder system modeled for these simulations will also include power electronics based DERs. Additionally, experimental results demonstrating the high frequency signatures generated due to a transient event in a medium voltage (13.8 kV) distribution line will also be presented in the full paper. Furthermore, the analysis combined with simulation and experimental results in the full paper will help demonstrate the feasibility and efficacy of the proposed protection scheme. The developed protection scheme will not just help solve problems generated by bidirectional current flow, varying short-circuit current capacity, but also help in proliferation of DERs in distribution systems.

41 EE - Solar Energy Technologies Office (EE-4S)↗

EMT-TS Hybrid Simulation for Large Power Grids Considering IBR-Driven Dynamics

The escalating integration of inverter-based resources (IBRs) poses new challenges to power systems by introducing fast dynamics with higher frequencies, which may need to be simulated by an electromagnetic transient (EMT) program. As an alternative to conducting EMT simulations for the entire system, which is typically time consuming, hybrid simulation between EMT and phasor-domain transient stability (TS) can greatly reduce the computational burden while preserving the detailed fast dynamics in the EMT zone. This paper establishes an EMT-TS hybrid simulation platform using open-source tools, specifically ParaEMT, GridPACK, and HELICS, which are the EMT simulator, TS simulator, and interface framework, respectively. Case studies on the 240-bus Western Electricity Coordinating Council (WECC) system demonstrate that the developed ParaEMT-HELICS-GridPACK hybrid simulator can accurately capture both slow electromechanical and fast IBR-driven dynamics with a 2.4x speedup.

electromagnetic transient↗

Deep Learning-enhanced Block-Diagram Modeling of Solar Power Systems

Data-driven models of power system inverter-based resources are desired to run simulations faster than with detailed electromagnetic transient models, to hide proprietary design details, to support control system design applications, and to aggregate the effects of distributed energy resources. This paper applies a customized Hammerstein Wiener framework to train block diagram models from thousands of electromagnetic transient simulations or experimental test records. The block diagram models integrate with larger grid simulations as voltagecontrolled current sources or current-controlled voltage sources for several simulators. Guidelines for block architecture and training are presented. Three-phase balanced, three-phase unbalanced, and single-phase examples all achieve an acceptable root mean square error of no more than 0.05 per-unit.

Mcdermott, Thomas E. [Private consulting company]↗

Real-World 20-Hz IBR Subsynchronous Oscillations: Signatures and Mechanism Analysis

This article provides analyses of subsynchronous oscillations associated with solar photovoltaics (PVs) observed in real world. All have oscillation frequencies at approximately 20 Hz in voltage and current magnitudes. On the other hand, in phase voltage and current, the oscillations show very different signatures. Through constructing simplified linear models and conducting sensitivity analysis, we are able to associate dynamic phenomena with the underlying mechanism and speculate the possible causes of the 20-Hz oscillations. The analysis results have all been validated via simulation results from electromagnetic transient (EMT) test beds constructed in MATLAB/Simscape.

inverter-based resources↗

Control and Simulation of a Grid-Forming Inverter for Hybrid PV-Battery Plants in Power System Black Start

Power system restoration is an important part of system planning. Power utilities are required to maintain black start capable generators that can energize the transmission system and provide cranking power to non-blackstart capable generators. Traditionally, hydro and diesel units are used as black start capable generators. With the increased penetration of bulk size solar farms, inverter based generation can play an important role in faster and parallel black start thus ensuring system can be brought back into service without the conventional delays that can be expected with limited black start generators. Inverter-based photovoltaic (PV) power plants have advantages that are suitable for black start. This paper proposes the modeling, control, and simulation of a grid-forming inverter-based PV-battery power plant that can be used as a black start unit. The inverter control includes both primary and secondary control loops to imitate the control of a conventional synchronous machine. The proposed approach is verified using a test system modified from the IEEE 9-bus system in the time-domain electromagnetic transient simulation tool PSCAD. The simulation results shows voltage and frequency stability during a multi-step black-start and network energization process.

Nguyen, Quan H.↗

Mechanism Analysis of Wind Turbine Var Oscillations

Electromagnetic transient simulation of parallel connected 4-MW type-3 wind turbines based on original equipment manufacturer's real-code turbine model shows 1.2-Hz turbine-turbine oscillations in reactive power. This letter reveals why such oscillations occur in the individual var measurement, while being insignificant in the total var measurement, regardless of the varying grid impedance. We adopt two analysis approaches: open-loop single-input single-output analysis and network decomposition. The two approaches differ in their treatment of turbine-network interaction. The open-loop analysis shows that the turbine-turbine oscillation mode is due to an open-loop system pole being attracted to an open-loop system zero. Furthermore, we use network decomposition method to explain why this mode is observable in individual vars while not observable in the total var. The entire system of n -turbines can be viewed as n decoupled circuits. For the two-turbine case, the system has an aggregated mode and a turbine-turbine oscillation mode. Here, the aggregated mode is associated with a circuit associated with the total var, while the turbine-turbine oscillation mode is associated with the var difference and is insensitive to the grid parameters.

17 WIND ENERGY↗

Enhanced Large-Signal Stability Method for Grid-Forming Inverters During Current Limiting: Preprint

Grid-forming (GFM) inverters are a promising technology for the widespread integration of renewable energy sources in future power systems. As a key element of GFM inverter control, the primary controller governs the internal reference voltage and angle. During contingencies in the grid---such as faults, voltage drops, or frequency and phase jumps---an inverter can be forced into a current-limiting mode of operation modulating inverter dynamics, and, as a result, it is prone to losing synchronism with the grid. In this paper, we propose a novel GFM primary control method with an additional synchronization term that naturally activates during contingencies to improve the dynamic response. The method allows the inverter to remain synchronized with the grid, which improves the inverter's dynamic behavior both during and after current-limiting grid conditions and enhances grid support, including voltage support using full current capacity. The method is demonstrated for voltage, frequency, and phase jumps both in a single-machine-to-infinite-bus and a network-wide electromagnetic transient simulation of the IEEE 14-bus system with 5 GFM inverters. The simulations provide insights into the proposed synchronization method and confirm the high potential of the method, which robustly secures synchronism under severe contingencies.

current limiting↗