At least 55 records · Page 3

Variable frequency response testbed to validate protective relays up to 20 kHz☆

Microgrids operate in islanding or utility grid mode. In islanding mode, distributed energy sources with power electronics inverters can generate fault currents over a wide range of frequencies. To gain a better understanding of the nature of these events, it is crucial to measure currents at frequencies of up to 20 kHz at transient states with protective relays. Protective relays at these frequency responses should be tested prior to being installed in microgrids. However, testing at high-frequency currents cannot be done with Relay Test Equipment (RTE) that generate signals up to 50th Harmonic for 60 Hz (3 kHz). In this study, a frequency response method and testbed for high-frequency currents of up to 20.16 kHz was developed and tested. The testbed utilized a RTE and High-Frequency Power Source/ Amplifier. Furthermore, frequency relay experiments were run at frequencies of up to 1 and 20.16 kHz at a current magnitude of 0.1 and 0.5 A, respectively. The events were collected, and the current magnitude and frequency were plotted at time and frequency domain, respectively. The study of current magnitude and frequencies of up to 20.16 kHz for two overcurrent relays was performed and validated the variable frequency testbed and methodology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Critical values of cyber parameters in a dynamic microgrid system

An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Gyrokinetic particle simulations of interactions between energetic particles and magnetic islands induced by neoclassical tearing modes

Interactions between energetic particles (EPs) and neoclassical tearing mode (NTM) islands in the DIII-D tokamak are studied using the global gyrokinetic toroidal code (GTC). GTC simulations find that the EP radial profile is partially flattened within the magnetic island regions and that there are stochastic regions in the particle phase space. Radial particle flux is induced mainly around the magnetic island regions and decreases with time to almost zero when the initial EP distribution achieves a new steady-state in the absence of EP sources. Stochastic regions of magnetic field lines induced by the superposition of multiple islands have weak effects on the particle flux when the width of stochastic regions is smaller than the EP drift orbit width. In conclusion, the perturbed parallel EP current induced by the magnetic islands has weak stabilizing effects on the linear growth rate of the NTM instability in this DIII-D experiment.

70 PLASMA PHYSICS AND FUSION TECHNOLOGY↗

Enhanced van der Waals epitaxy of germanium by out-of-plane dipole moment induced from transferred graphene on TiN/AlN multilayers

We report recent advances in 3D/2D heterostructures have opened up tremendous opportunities in building highly flexible and durable optoelectronic devices. However, the inherit lack of interfacial bonding and low surface energy of van der Waals surfaces limit the nucleation and growth of 3D materials. Enhancing wettability by providing a porous buffer is effective in growing compound semiconductors on graphene while van der Waals epitaxy of Ge remains challenging. Here, the nucleation of Ge has been significantly improved from an islanded mode to granular modes by using a TiN/AlN multilayered buffer prior to Ge/graphene integration. Highly textured Ge growth with dominating (111), (220), and (311) peaks are identified by x-ray diffraction. The microstructure of the buffer TiN/AlN demonstrates a polycrystalline quality with clean interfaces between each interlayer and the substrate. Kelvin probe force microscopy measurements along the lateral TiN/AlN interface identify a potential drop corresponding to the AlN phase. This contact potential difference between TiN and AlN is the key in generating the out-of-plane dipole moment that modifies the surface energy of the monolayer graphene, resulting in enhanced wettability of the Ge adatoms nucleated on top. Surface dipole induced nucleation of 3D semiconductor thin films on 2D materials via the proper design of buffer layer is fundamentally important to enhance the 3D/2D growth toward flexible optoelectronic applications.

36 MATERIALS SCIENCE↗

Modified Andronov-Hopf Oscillator-Based Grid-Forming Converter with Emulated Virtual Cable for Enhanced Power Sharing Performance

Nonlinear oscillator-based grid-forming converters offer superior dynamic and steady-state performance, making them an attractive solution for interconnecting renewable resources. This paper proposes a novel modified Andronov-Hopf oscillator to enhance the operating spectrum and facilitate the integration of renewable energy sources. An inner loop controller based on the Lyapunov energy function is implemented to achieve robust stability and performance, while a virtual cable emulation strategy enables seamless parallel operation. Comprehensive modeling and simulation studies validate the effectiveness of the proposed system, demonstrating its capabilities in addressing diverse operating scenarios, including grid faults, renewable energy fluctuations, and parallel operation. The proposed solution exhibits fast transient response, robust stability, and flexible operation, making it a valuable contribution to the field of renewable energy integration. The results of this study can be used to inform the design and implementation of next-generation grid-forming converters, enabling a more sustainable and reliable energy future. Additionally, the proposed system's ability to operate in both grid-connected and islanded modes makes it an ideal candidate for remote and off-grid renewable energy applications. The proposed solution's scalability and modularity also make it suitable for large-scale renewable energy integration. The proposed system is verified through MATLAB/Simulink and PLECS simulations, demonstrating its effectiveness in ensuring robust and efficient operation.

Andronov-Hopf Oscillator (AHO)↗

Demand Estimation of Net Metered Loads for Microgrid Restoration

Microgrids can experience frequency instability while operating in the islanded mode due to a significant demand generation imbalance. Presence of net metered (NM) loads can further complicate accurate demand forecasting. For these loads only the net demand, difference of load demand and generation, is available. This paper presents the various stages observed during microgrid restoration with high penetration of NM loads. Disaggregation of demand and generation from the net metered time series is shown to be essential for accurate demand forecasting in each of these stages. A disaggregation approach is proposed using correlation in the net metered data. Time series analysis is then used to forecast the demand in each stage of the microgrid restoration process. A case study using demand and generation time series data from residential loads, shows that the proposed approach is significantly more accurate for demand forecasting than using only the net-metered time series.

demand forecasting, Microgrid, power system restor↗

System Modeling and Robust Stability Region Analysis for Multi-inverters Based on VSG

As the number of inverter-interfaced distributed generators (IIDGs) increases, the decrease in the inertia of the microgrid affects the stability of microgrid voltage and current. The virtual synchronous generator (VSG) control method simulates the output characteristics of the synchronous machine to improve the inertia and damping of the microgrid. However, low-frequency oscillations can occur in systems with multi-VSGs connected in parallel, primarily when operating in island mode. Therefore, this article develops the small-signal state-space model for multi-inverters based on VSG and analyses the robust stability region (RSR) of the control parameters. Firstly, an extensible small-signal state-space model is established and simplified in the dq axis, which is a necessary preprocessing for the subsequent stability analysis. Secondly, the guardian map method based on bialternate product operation is constructed, and the RSR is established through translation mapping and rotation mapping. Therefore, the solution of RSR is transformed into the problem of identifying the Hurwitz matrix. Finally, the simulations and experiments verify that the calculated region can ensure stable operation during startup and meet the requirement to suppress low-frequency oscillations. In conclusion, the method of solving RSR proposed in this paper provides a basis for selecting controller parameters in practical engineering.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A General State Estimation Formulation for Three-Phase Unbalanced Power Systems

Almost all of the three-phase state estimation algorithms assume existence of a reference bus whose phase angles are perfectly balanced. This assumption is quite realistic for transmission systems, and also for most distribution systems that are connected to a strong transmission system where transmission side can modeled by a balanced reference bus. However, for distribution systems having high penetration of renewable sources or for microgrids operating in islanded mode, the assumption of a balanced reference bus will not be realistic. While there are recent publications focusing on this problem, formulation of the three-phase unbalanced state estimation problem with proper treatment of the reference bus remains unaddressed. In this paper, a new formulation will be described where an accurate state estimation solution can be obtained for any unbalanced threephase system irrespective of its operating conditions (balanced or highly unbalanced), configuration (isolated microgrid, connected to transmission system, etc.) and whether or not it contains any synchronous generators. Validation of the proposed formulation will be carried out via simulations.

State Estimation, Distribution System, Unbalanced ↗

Investigating Oscillations in Bulb Turbine Plant During Islanded black start Operation

This paper investigates the frequency oscillatory behavior displayed by the bulb turbine-based run-of-river (ROR) hydropower system under islanded operation. These oscillations prevent higher loading of these generators (under islanded conditions) and hence reduce the black start capability of these generators. To investigate the problem, first, a transfer function model of the bulb-turbine system, sensitive to the effects of head variation, blade angle, and other non-linearities pertaining to turbine characteristics is derived. Next, by analyzing this transfer function model and through simulations, it is determined that system inertia along with other parameters could be responsible for these oscillations. Also, through simulations it is shown that the same ROR system’s behavior is different under islanded mode compared to grid-connected mode.

13 HYDRO ENERGY↗

Implementing Admittance Relaying for Microgrid Protection

An earlier study evaluated issues with microgrid protection. This highlighted the difficulties with microgrid protection, which include: 1. lack of fault current from inverter-interfaced generation, 2. varying fault current between grid-connected and islanded modes, 3. potential for normally-meshed operation and 4. unbalanced operation due to single-phase loads. It is worth noting that not all microgrid designs will include all these challenges. For example, microgrids could choose to omit meshed operation. Previous work identified differential protection based on the discrete S-transform for line protection and admittance protection for load protection as possible solutions . However, some severe limitations were identified. This included the potential for blinding of the discrete S-transform protection when fault contribution on either end of the line is similar, and loss of protection selectivity for admittance protection in the case of upstream line-ground faults. This report investigates admittance protection as a solution for line and load protection in greater detail by comparing analytical and simulated results. Section 2 describes the protection schemes analyzed and the behavior of inverter-interfaced microgrids under faults in more detail. Section 3 derives sequence networks for the fault cases considered. Section 4 presents a transient model constructed to validate the impedances calculated from the sequence networks. Section 5 compares the results from the sequence networks and transient model. Last, Section 6 presents the conclusions of this study in terms of the suitability of admittance relaying for protection of inverter-interfaced microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dynamic State Estimation for Radial Microgrid Protection

Dynamic state estimation (DSE) is a generalization of differential protection that offers a reduced likelihood of misoperation, particularly in the case of devices with nonlinear characteristics such as transformers which are being energized. It is also useful in cases where distance protection performs poorly, such as transmission lines with series compensation or mutually coupled transmission lines. DSE has been previously applied to microgrid branch protection. This study investigates the use of DSE for protection of radial portions of a microgrid or distribution system. This can be a challenge in microgrids or distribution systems with distributed generation on account of lack of fault current from inverter-interfaced generation, varying fault current between grid- connected and islanded modes, the potential for normally-meshed operation and unbalanced operation due to single-phase loads. Admittance relaying has been investigated as a solution for protection of microgrids, though it has been observed to have issues with grounded-wye connected loads, and additional relaying is necessary to prevent misoperation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid Design Toolkit (MDT) User Guide. Software v1.3.

The Microgrid Design Toolkit (MDT) supports decision analysis for new ("greenfield") microgrid designs as well as microgrids with existing infrastructure. The current version of MDT includes two main capabilities. The first capability, the Microgrid Sizing Capability (MSC), is used to determine the size and composition of a new, grid connected microgrid in the early stages of the design process. MSC is focused on developing a microgrid that is economically viable when connected to the grid. The second capability is focused on designing a microgrid for operation in islanded mode. This second capability relies on two models: the Technology Management Optimization (TMO) model and Performance Reliability Model (PRM).

42 ENGINEERING↗

Management of Risk and Uncertainty Through Optimized Co-Operation of Transmission Systems and Microgrids With Responsive Loads (Final Report)

The evolution of the power system to the reliable, efficient and sustainable system of the future will involve development of both demand- and supply-side technology and operations. Ambitious national and state-level goals around the decarbonization of electricity relies on the integration of very high levels of renewable resources, most of which are variable and intermittent. The use of demand response is an ideal approach to counterbalance the intermittency of renewable generation and brings the consumer into the spotlight. Though individual consumers are interconnected at the low-voltage distribution system, these resources are typically modeled as variables at the transmission network level. Demand-side participation cannot be leveraged effectively without explicitly including the distribution system dynamics in the optimization-based wholesale market operations. This project grew from a vision for co-optimized interaction of distribution systems, or microgrids, with the high-voltage transmission system. In this framework, microgrids encompass consumers, distributed renewables and storage. The energy management system of the lower voltage system (distribution or microgrid) can also sell (buy) excess (necessary) energy from the transmission system. Until recently, very little research had been conducted on the co-optimization of these two systems due to computational limitations. However, advances in computational capabilities, and the judicious use of decomposition methods and innovative approximation methods for high-dimension dynamic programming made this goal a viable objective for this project, leading to a fundamental shift in the ability to integrate and fully utilize demand-side resources. To this end, the modeling framework developed introduces a novel co-optimization framework, to include the operations of both the transmission and distribution systems (or microgrids) in operational decision making. This framework was used to analyze renewable and distributed generation along with responsive demand and to compare the capability of co-optimized systems to perform with higher levels of variable renewables. An ideal microgrid is defined as an electric entity capable of operating in both interconnected (with the high-voltage grid) and islanded mode. As such, the microgrid should incorporate generating units (traditional units and intermittent) and if needed, exchange power with the high-voltage grid. The interplay between the microgrid and high-voltage grid motivated the development of the co-optimization approach to ensure efficient performance of the interconnected network. Results show that the use of a bi-level optimization approach is an appropriate structure, capable of co-optimizing a transmission system with multiple distribution systems and microgrids. While increasing the number of connected systems provides increasing flexibility for renewables integration this can also the economic benefits to the low-voltage subsystems with each additional system connected. Comparison of a traditional single-level decision structure with the co-optimization approach illustrates a reduction in overall system cost under co-optimization, while specific cost allocations to transmission and distribution systems are changed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Non-catalytic pyrolysis of associated gas to zero CO 2 hydrogen and high value carbon black

The overall objective of this work is to perform a pre-Front End Engineering Design (pre-FEED) study of the conversion of associated gas produced at an active oil pad of a Bakken oil field producer, to high value carbon black and hydrogen using the Microwave Plasma Pyrolysis of Associated Gas (MPP-AG) process developed by H Quest Vanguard, Inc (HQV). The University of North Dakota’s Center for Process Engineering Research (CPER) collaborated with HQV to complete a design and techno-economic analysis for the MPP-AG deployed at an active Bakken well site flaring an average of 54,000 standard cubic feet per day of AG. The proposed design consists of: • A Microwave Pyrolysis Unit (MPU) which consists of H Quest’s proprietary MPP technology • A patent-pending Gas Conditioning Unit (GCU) designed by the University of North Dakota to condition intermittent and variable flow gas prior to pyrolysis. • An auxiliary unit running on the associated gas to power the GCU and MPU in an “island mode” configuration.

03 NATURAL GAS↗

Grid Resiliency using Hydro-based Microgrids During Wildfires

The primary objective of this project is to assess the techno-economic viability of hydropower resources with supplementary investments, including microgrid controllers, storage solutions, load banks, additional generation like diesel generators, communication links, and transmission infrastructure. The aim is to enable these systems to operate autonomously (in islanded mode) and ensure grid resiliency during and after wildfire events. The project seeks to establish a comprehensive framework for setting up hydropower-based microgrids, from risk estimation to final investment decisions. These microgrids can provide critical support during emergencies and offer additional grid stability and revenue opportunities during regular operations and other system contingencies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Investigation of Aerodynamic and Aerodynamic and Radiometric Land Surface Temperatures

The overall goal of the project was to reconcile the difference between T(sub s,r) and T(sub aero), while maintaining consistency within models and with theory and data. The project involved collaboration between researchers at Bucknell University, Boston University, University of mode Island, and the USDNARS Hydrology Laboratory. This report focuses on the work done at Bucknell, which used an analytical continuous-source flux model developed by Crago (1998), based on work by Brutsaert and Sugita (1996) to generate fluxes at all levels of the canopy. Named ALARM [Analytical Land- Atmosphere-Radiometer Model] by Suleiman and Crago (2002), the model assumes the foliage has an exponential vertical temperature profile. The same profile is felt by the within-canopy turbulence and 'seen" by a radiometer viewing the surface from any zenith view angle. ALARM converts radiometric surface temperatures taken from any view angle into a clearly-defined version of Taero called the equivalent isothermal surface temperature T(sub s,j), and then calculates the sensible heat flux H using Monin-Obukhov similarity theory. This allows remotely sensed Ts,r measurements to be used to produce high quality sensible and latent heat flux estimates, or to validate or update the surface temperature produced by SVATs in climate or mesoscale models.

Crago, Richard D.↗

Remote Hardware-in-the-Loop Approach for Microgrid Controller Evaluation: Preprint

Utilities have been installing microgrids due to the advancements in the distributed energy resources technologies. Microgrids also improve the resiliency of the system due to their capability to isolate themselves from the grid and run in islanded mode of operation. Microgrid controllers are management systems that can run the microgrids under varied operating condition and enable the smooth operation of microgrids under various system conditions. It is of high value to de-risk the installation of such controllers. Hardware-in-the-loop evaluation is used by controller developers and utilities to evaluate the controllers under stressful conditions to understand the performance and to understand the necessary improvements to the microgrid controller. In this research work, the team has leveraged the existing infrastructure of real-time simulation at the Energy Systems Integration Facility (ESIF) and the capability of the microgrid controller to control assets over the Internet Protocol (IP) to evaluate a university developed microgrid controller in an efficient and cost-effective manner. The full paper will provide the complete setup, the experimental use cases and the results. In this abstract, one use case will be expalined, and the results from the use case is provided.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Resilient, Rural, and Revolutionary: Salisbury Square's Direct-Current Affordable Microgrid Community: Preprint

The technology to interconnect buildings with a dedicated direct-current (DC) power distribution network is in place today; what is missing is a turnkey approach to designing a DC microgrid - and the business models allowing such systems to be deployed, owned, and operated at scale. To close this gap, the Salisbury Square Development Team, comprising clean-energy experts, has engineered a resilient community DC microgrid for an affordable housing community in Randolph, Vermont. Ten single-family, occupant-owned residences and 12 multifamily rental units will share locally generated and stored solar energy via a DC power distribution bus capable of operating during extended grid outages. With a DC power distribution network in place, each home will be equipped with high-efficiency DC lighting and appliances, operating alongside alternating current (AC) appliances, even during an islanded mode of operation. To obtain a comprehensive understanding of what is possible and achievable, the Team collaborated with the local utility, regulatory agencies, a national laboratory, energy-as-service providers, and vendors. The collaborators evaluated microgrid typologies, business models, and energy modeling, and analyzed electrification and resilience. Further, the Team applied the URBANoptTM (Urban Renewable Building and Neighborhood optimization, NREL 2022) software development kit (SDK) to Salisbury Square's single-family and multifamily buildings to validate workflows and identify needs for advanced capability. This paper addresses the barriers to entry, scalability, and impact on residents and system ownership. It also examines the analysis that informed the design and engineering of the DC microgrid and the opportunities to streamline the process.

DER↗