Search NASA⌕ Search

SEARCH · Search NASA

Results for “Microgrid Controller”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 577 records · Page 32

Demonstrating the Need for Adaptive Droop Control for Grid-Forming Inverters in Islanded and Grid-Connected Modes

This paper demonstrates the need of adaptive droop of grid-forming (GFM) inverters operating in different operation modes (grid-connected and islanded). A pure hardware microgrid comprising multiple grid-forming (GFM) inverters from different vendors, multiple grid-following inverters, and a diesel generator is used for the demonstration. The key findings are summarized as follows: Tighter droop slope should be used in the islanded mode, and looser droop slope should be used in the grid-connected mode to ensure stability. It is important to have adaptive droop control in GFM inverters to ensure stable and reliable microgrid operation.

14 SOLAR ENERGY↗

Sensors with Intelligent Measurement Platform and Low-cost Equipment (SIMPLE) for Monitoring and Control of Medium Voltage Distribution Systems with High Penetration of Intermittent Distributed Energy Resources

The primary focus of the SIMPLE project was to develop, commission, test and introduce intelligent voltage and current sensor platform with enhanced characteristics (accuracy, bandwidth and harmonic range) and high measurement granularity for medium voltage distribution system monitoring, protection and control. The enhancements incorporated existing (commercially available) sensors and made them suitable for applications such as voltage regulation, frequency support, fault detection and location, distribution system state estimation, power quality measurements and electrical distribution network topology processing. The development of the intelligent sensor platform was driven by the need for high-fidelity monitoring and control of medium voltage distribution feeder to enable higher penetration of renewable resources and microgrid operation.

14 SOLAR ENERGY↗

On Control Schemes for Grid-Forming Inverters

Grid-forming inverters can collaboratively regulate the voltage and frequency of a microgrid. These inverters are expected to be seen more in the future microgrid, undertaking the roles of the conventional power generators. Like conventional power generators, they must balance supply and demand, contribute to power-sharing between inverters and other power generators, and restore the voltage and frequency after any power changes. These technical challenges are typically achieved through different primary and secondary controllers. This article reviews some state-of-the-art primary and secondary control schemes for the emerging technology of grid-forming inverters. First, the typical control schemes for grid-following inverters are briefly presented for the continuity of the discussion on the roles of the grid-forming inverters in future power-grid, followed by two basic control schemes for the grid-forming inverters. Then, two decentralized power-sharing techniques, i.e., droop, and virtual inertia, are analyzed. The technical challenges for inverter synchronization and some control methods are discussed afterward. Finally, several secondary control methods for the voltage and frequency restoration in grid-forming inverters are reviewed.

Sadeque, Fahmid↗

Transient Stability Study of a Real-World Microgrid with 100% Renewables

This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.

black start↗

Transient Stability Study of a Real-World Microgrid with 100% Renewables

This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.

black start↗

Foundational Report Series: Advanced Distribution Management Systems for Grid Modernization, DMS Integration of Distributed Energy Resources and Microgrids

Deregulation of the electric utility industry, environmental concerns associated with traditional fossil fuel-based power plants, volatility of electric energy costs, Federal and State regulatory support of “green” energy, and rapid technological developments all support the growth of Distributed Energy Resources (DERs) in electric utility systems and ensure an important role for DERs in the smart grid and other aspects of modern utilities. DERs include distributed generation (DG) systems, such as renewables; controllable loads (also known as demand response); and energy storage systems. This report describes the role of aggregators of DERs in providing optimal services to distribution networks, through DER monitoring and control systems—collectively referred to as a Distributed Energy Resource Management System (DERMS)—and microgrids in various configurations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Security Architecture for Microgrid Integration

The purpose of this document is to present cyber security risk considerations and mitigations for community microgrids. The mitigations discussed herein specifically focus on cyber security technical requirements for the De-centralized Autonomous Community Controller (DAC) as part of the SECURE project’s technology development effort. These requirements also consider the associated security implementation challenges involved with the decentralized characteristics of microgrids where upstream communications to utility security management functions are lost. These security recommendations and technical requirements may be used by microgrid implementers and technology vendors to specify the security design of the microgrid systems and their components.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Interfaces for Inverter-Based Microgrid Experiments Including Transitions

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents two PHIL interfaces for such microgrids and the preliminary experimental results.

experiments↗

A Fast Dynamic Internal Predictive Power Scheduling Approach for Power Management in Microgrids: Preprint

This paper presents a Dynamic Internal Predictive Power Scheduling (DIPPS) approach for optimizing power management in microgrids, particularly focusing on external power exchanges among diverse prosumers. DIPPS utilizes a dynamic objective function with a time-varying binary parameter to control the timing of power transfers to the external grid, facilitated by efficient usage of energy storage for surplus renewable power. The microgrid power scheduling problem is modeled as a mixed-integer nonlinear programming (MINLP-PS) and subsequently transformed into a mixed-integer linear programming (MILPPS) optimization through McCormick's relaxation to reduce computational complexity. A predictive window window with 6 data points is solved at an average of 0.92s, a 97.6% improvement over the 38.27s required for the MINLP-PS formulation, implying the numerical feasibility of the DIPPS approach for real-time implementation. Finally, the approach is validated against a static objective using real-world load data across three case studies with different time-varying parameters, demonstrating the ability of DIPPS to optimize power exchanges and efficiently utilize distributed resources while shifting the external power transfers to specified time durations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantitative Metrics for Grid Resilience Evaluation and Optimization

Power system resilience has become a critical topic in recent years because of the increasing trend of extreme events and the growing integration of intermittent renewable energy sources. To enhance grid resilience against high-impact, low-frequency events, two questions should be answered: how to quantify the resilience of a given grid and how to incorporate the quantification into power system planning, operation, and restoration. Here this paper develops a new set of quantitative metrics with clear physical interpretation to comprehensively evaluate power system resilience. Using microgrids as an example, an event-based corrective scheduling (ECS) model and an online model predictive control (OMPC) model are developed to integrate the proposed quantitative resilience metrics into power system optimization models for resilience enhancement. The ECS model employs extreme event data to investigate the optimal restoration solution and to help microgrid operators prepare to respond to similar events. The OMPC model provides online decision-making support for operators to handle ongoing outages in the most resilient fashion. The effectiveness and superiority of the proposed quantitative resilience metrics and the resilience enhancement models are demonstrated through simulations and comparative studies on an IEEE test feeder and a real distribution feeder in Southern California.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A tool for assessing demand side management and operating strategies for isolated microgrids

Globally, power system operators are exploring ways to leverage the capabilities of smart meters to implement fine-grained demand side management (DSM). Here this paper presents a new simulation tool to evaluate operating strategies for smart-meter-enabled (SME) islanded microgrids being advanced for sustainable rural electrification in emerging economies. Based on MATLAB/Simulink, the tool's component-level models of small microgrids can be easily configured. Alternative rule-based operating strategies are implemented with controllable supply and storage components as well as other components driven by external factors (e.g., weather and time of day). To account for the wide range of possible operating conditions in real-world applications, statistical metrics can be evaluated using Monte Carlo (MC) methods based on user-defined, time-dependent probability distributions for demands, supplies, and environmental variables. Features of the tool are demonstrated with case studies for a representative microgrid in rural Rwanda.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Simulation and power quality analysis of a Loose-Coupled bipolar DC microgrid in an office building

With distributed generation and battery storage technologies thriving in microgrids, the use of direct current (DC) microgrids in the building sector offers multiple advantages in energy efficiency and power quality compared with alternating current (AC) systems. This study developed a new concept of a loose-coupled bipolar DC building power system. In this work, the concept was used to design a real-world office building in Shenzhen, China. A power system model was developed to study the stability and control of the DC power system and to verify DC power quality. The design and modeling of the DC power control system is discussed in detail. The study developed a few common fault scenarios in DC building microgrids that were simulated in the MATLAB-Simulink environment to validate the design of a loose-coupled bipolar DC system. The results indicate that the proposed loose-coupled bipolar DC system schema, when implemented with proper control algorithms, can achieve good fault-tolerant performance with reliable power quality, even during disruptive system events.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Power Quality Improvement Utilizing Photovoltaic Generation Connected to a Weak Grid

Microgrid research and development in the past decades have been one of the most popular topics. Similarly, the photovoltaic generation has been surging among renewable generation in the past few years, thanks to the availability, affordability, technology maturity of the PV panels and the PV inverter in the general market. Unfortunately, quite often, the PV installations are connected to weak grids and may have been considered as the culprit of poor power quality affecting other loads in particular sensitive loads connected to the same point of common coupling (PCC). This paper is intended to demystify the renewable generation, and turns the negative perception into positive revelation of the superiority of PV generation to the power quality improvement in a microgrid system. The main objective of this work is to develop a control method for the PV inverter so that the power quality at the PCC will be improved under various disturbances. The method is to control the reactive current based on utilizing the grid current to counteract the negative impact of the disturbances. The proposed control method is verified in PSIM platform. Promising results have been obtained.

14 SOLAR ENERGY↗

Development of a Hydrogen Energy System as a Grid Frequency Management Tool

The Hawai‘i Natural Energy Institute (HNEI) is conducting research to assess the technical potential of using an electrolyzer-based hydrogen (H2) production and storage system as a grid demand response tool using battery data from a 200 MW grid to show the kind of response required. The hydrogen produced by the electrolyzer is used for transportation. A 65 kg/day hydrogen energy system (HES) consisting of a PEM electrolyzer, 35 bar buffer tank, 450 bar compressor, and associated chiller systems was purchased and installed at the Hawaii Natural Energy Laboratory Hawaii Authority (NELHA) to demonstrate long-term durability of the electrolyzer under cyclic operation required for frequency regulation on an island grid system. The excess hydrogen was stored for use by three fuel-cell buses to be operated at Hawai‘i Volcanoes National Park (HAVO) and by the County of Hawai‘i Mass Transit Agency (MTA). This paper describes the site selection and equipment commissioning, plus a comprehensive test plan that was developed to characterize the performance and durability of the electrolyzer under dynamic load conditions. The controls were modified for the operating envelope and dynamic limits of the electrolyzer. While the data showed these modifications significantly improved the system response time, it is not fast enough to match a BESS response time for grid frequency management. The electrolyzer can only be used for slower acting changes (1 to 0.5 Hz). A potential solution is to design an electrolyzer/BESS hybrid system and develop a modeling program to find the optimum mix of battery and electrolyzer to provide the maximum grid regulation services at minimum cost.

08 HYDROGEN↗

Investigation on Tuning Power–Frequency Droop for Improved Grid–Forming Inverter and Synchronous Generator Transient Load Sharing

Poor transient load sharing has been observed during the parallel operation of synchronous generators (SGs) and droop-controlled grid-forming (GFM) inverter-based resources (IBRs) in islanded microgrids. This can result in overcurrent protections, causing the inverters to trip, which leads to the collapse of voltage and frequency. In this article, small-signal analysis supported by electromagnetic transients (EMTs) simulation is performed on a detailed model of a microgrid containing IBRs and an SG to identify underdamped modes and their sensitivities to the power–frequency (P-F) droop parameter. Further EMT simulation of a more complex microgrid model with multiple GFM IBRs and SGs is performed to determine whether trends identified from the modal analysis extend to cases where the number of SGs in operation may vary. The objective is to investigate the effectiveness of tuning this parameter to reduce the likelihood of overcurrents in response to load and generation disturbances. The work uncovers both fast and slow modes of concern. Primarily, the findings show that increasing the P-F droop value improves the damping of the slower mode while degrading the damping of the faster mode, leading to an upper limit on the damping improvement of the GFM IBR output current. In EMT simulations of the more complex microgrid, the greatest damping improvement still exhibits significant maximum overshoot. Furthermore, the optimal value of the P-F droop parameter is sensitive to the number of SGs in operation. The conclusion is that tuning the P-F droop parameter is not an effective means to avoid the overcurrent tripping of GFM IBRs during response to large load or generation disturbances when operating in parallel to SGs in islanded microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗