Machine Learning for Automated Metadata Assignment in Buildings: Cooperative Research and Development (Final Report, CRADA Number CRD-18-00767)

RealTerm Energy and NREL have identified a shared vision to evaluate opportunities to facilitate the organization and assignment of metadata to building control system (BCS) data via industry-informed machine learning (ML). Manual metadata assignment is labor intensive and costly, slowing down any Energy Management and Information System (EMIS) deployment in the building space. This project aims to develop methodologies to accurately assign this metadata and significantly decrease the level of effort associated with deploying EMIS. The objective of this project is to identify/design methodologies to assign metadata to HVAC control points automatically. The identified methodologies will be programmed in analytics algorithms so they can ingest a list of points and produce a detailed tagging following the Haystack classification nomenclature. To validate the efficacy of each methodology, tagging results will be compared utilizing a list of points extracted from RealTerm's building database-as well as data extracted from the NREL campus via the Intelligent Campus program-enabling testing against large datasets with real world challenges. The developed methodologies may leverage building manager/operator input on a limited basis to add context to the classifying algorithms. The partnership aims to advance global efforts in areas related to the DOE missions through improving operational performance of commercial buildings. It is well documented that buildings fall out of commission after they are occupied, wasting significant energy and incurring associated costs simply due to poor operational performance. Emerging EMIS technologies that perform continuous commissioning help to address this issue, yet integration of these systems can be labor intensive both for the technology vendor and the building owner/operator. This project will enable more efficient and cost-effective analytics for buildings, enabling improvement in building operations at lower cost points.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Enhancing Performance Contracts with Monitoring-Based Commissioning (MBCx)

Integrating monitoring-based commissioning (MBCx) software tools into performance contracts is a timely topic given recent developments in MBCx software offerings and the growing number of MBCx deployments nationwide. Many commercial building owners have started to install MBCx software tools that tie in advanced metering infrastructure, building automation systems, and local weather data to enable ongoing commissioning and identify energy conservation measures. To support federal and commercial building owners in understanding, procuring, and implementing MBCx software tools, this report provides an overview of their capabilities, the MBCx process, and how MBCx can be integrated into - and benefit - each phase of a performance contract. This report is intended to spur increased use of MBCx in performance contracts, whether an agency has previously installed or is considering adding MBCx at the time of their project. Additionally, case studies illustrate successful experiences using MBCx within performance contracts at a university campus and across a large number of buildings managed by the General Services Administration.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A dataset of cyber-induced mechanical faults on buildings with network and buildings data

We have collected data of cyber-induced mechanical faults on buildings using a simulation platform. A DOE reference building model was used for running the simulation under a Rogue device attack and collected the network data as well as the physical buildings data to better understand the impacts of cyber attacks on the building and help identify the source of the mechanical fault with the network data. Alfalfa is the tool used for simulating the DOE reference buildings and acts as an interface to the model for querying the status and providing input externally. The Building Automation System (BAS) is the centralized controller providing control commands to other BACnet devices on the network based on the building status received from Alfalfa. The BACnet devices like damper will listen for the control commands from BAS on the BACnet network and implement it. The attacker is the malicious actor on the network creating disruptions by placing cyber-attacks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Putting Our Industry's Data to Work: A Case Study of Large-Scale Data Aggregation: Preprint

With increasing deployment of Advanced Metering Infrastructure (AMI), Building Automation System (BAS) controls, Internet of Things (IoT) network devices, and data-driven evaluation, measurement, and verification studies, the building sector is currently generating a staggering amount of energy-related data. In the right hands, these data sets can contribute to increased comfort and energy savings for building occupants and a more reliable electrical grid; however, due to a combination of factors, including significant privacy concerns, much of the data that are presently generated and stored are not used outside of basic operational applications. In the past year, our team has dedicated over 2,000 person-hours to accessing building energy data for a project funded by the U.S. Department of Energy (DOE) Building Technologies Office. We sought whole-building or end-use (e.g., lighting) timeseries data at the individual-building or equipment level where possible or aggregated information, such as timeseries averages and quartiles by building type (e.g., office, retail, hospital), where sharing individual building information was not an option. We are additionally working with IoT and BAS data sets to derive information important to the project. We have assembled an extensive data set that will enable the development of publicly available end-use load profiles to benefit the U.S. building and electricity industries. Here we present an overview of the data set that we have assembled to date, the motivators and approaches that got us here, and the lessons we learned through our efforts. We also discuss work underway that presents additional options for future data access.

building energy data↗

Emulation and detection of physical faults and cyber-attacks on building energy systems through real-time hardware-in-the-loop experiments

The increasing use of remote or mobile access, integrated wearable technologies, data exchange, and cloud-based data analytics in modern smart buildings is steering the building industry towards open communication technologies. The increased connectivity and accessibility could lead to more cyber-attacks in smart buildings. On the other hand, physical faults (e.g., HVAC -heating, ventilation, and air-conditioning faults) may have similar adverse impacts as those from the cyber-attacks on building energy systems, such as occupant discomfort, energy wastage, and equipment downtime. However, current physical behavior-based anomaly detection methods fail to differentiate between cyber-attacks and physical faults in building energy systems. Moreover, the challenge in collecting real-world threat data with ground truth has led researchers to rely on numerical models with user-defined assumptions, which may not accurately reflect real-world conditions due to the lack of in-situ experimental datasets. To address these challenges and gaps, this paper presents a flexible hardware-in-the-loop (HIL) testbed for generating cyber-attack and physical fault datasets and demonstrating threat detection algorithms in a real building automation system (BAS) environment. This testbed combines hardware (i.e., real BAS with local HVAC controllers and a physical network) with software (i.e., high-fidelity models to represent behaviors of building envelope and HVAC energy systems), enabling emulations of realistic threats. Five HIL experiments, including one baseline without any threats, two with physical faults, and two with cyber-attacks, were conducted to generate datasets containing detailed network traffic and system states. A joint classification framework, incorporating a network analyzer and a physical HVAC fault detector, was proposed to automatically detect cyber-physical abnormalities on BAS at both the network and the physical HVAC levels. The network analyzer comprises a conditional random fields (CRF) based command validator and a statistics-based detection strategy. The fault detector employs a weather and schedule-based pattern matching and feature-based principal component analysis (WPM-FPCA) method. Evaluation of the classification using four metrics from the multi-class confusion matrix revealed an average accuracy of 90.2%, recall of 89.7%, precision of 88.5% and F1-score of 89.2%. Finally, these results demonstrate that the proposed joint classification framework can effectively differentiate between specific types of cyber-attacks (e.g., device reinitialization attack, network Denial-of-Service attack) and physical faults (e.g., air handling unit operational fault, cooling coil valve stuck) in real time for improved building energy management.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Implementation and validation of optimal start control strategy for air conditioners and heat pumps

Commercial buildings are responsible for approximately 20 % of the total energy consumption and greenhouse gas emissions in the United States. Over 85 % of these buildings lack building automation systems, and many are small (<50,000 square feet), underserved, and use rooftop units (RTUs) for heating, ventilation, and air-conditioning needs. Because these buildings lack proper energy management systems, several operational deficiencies lead to excess energy consumption. Studies have shown that managing the RTUs’ heating and cooling set points, schedules, setbacks, and optimal start can result in a 20 % to 25 % reduction in electricity consumption in small commercial buildings. These buildings typically use fixed schedules to start the RTUs 60 to 120 min before occupancy begins, which results in excess energy consumption. This paper presents research that demonstrates and evaluates the performance of four optimal start methods, which utilize data-based modeling as a key element in facilitating adaptive control in response to time-varying inputs while requiring minimal sensor inputs. The evaluation found energy savings in two commercial buildings equipped with RTUs by periodically alternating four different optimal start models during the cooling and heating season. The resulting energy savings are positive for all models and range from 2 to 5 kWh/day/unit. The units on the east side of the building showed higher savings, while interior units showed greater variability in savings due to the differences in capacities and room sizes. Savings were considerably greater during the heating season compared to the cooling season. The performance of all four models on Mondays was poor; models suggested a shorter optimal start time, which resulted in relatively larger errors. Finally, the future work will look at using a different model for the days after weekends and holidays.

42 ENGINEERING↗

Critical Energy Infrastructure Cybersecurity: Enhanced Cyber Resilience for Federal Energy Systems

This presentation is an overview of FEMP Resilient and Secure Infrastructure and Facilities. An educational and interactive workshop centered on resilient and secure federal infrastructure and facilities, with a focus on inverter-based resources at Federal sites, building automation systems, and Federal supply chains. This workshop will illustrate an all-hazards scenario and discuss how Federal agencies can be positioned to resist these real-world scenarios.

97 MATHEMATICS AND COMPUTING↗

Overall chilled water system energy consumption modeling and optimization

The emergence of increasingly affordable variable-speed drive technology has changed the approach used to control chilled water systems equipped with these drives. The purpose of this research was to develop an integrated chilled water modeling technique that can determine the optimal system setpoints and estimate the energy saving potential of chiller system. The chiller system equipped with Variable Frequency Drives (VFDs) on cooling tower fans and condenser water pumps. To accomplish the objective, physical component models of the centrifugal chiller, cooling tower and condenser water pump were established with the goal of incorporating the system’s condenser water flow rate and cooling tower fan speeds as optimization variables. Furthermore, a cooling load prediction algorithm was developed using a multiple non-linear regression model to approximate the building’s cooling load subject to a range of environmental conditions. The inputs and outputs of the individual component models were linked to estimate how adjusting the cooling tower fan and condenser water pump speed would influence the system’s comprehensive performance. Here, the overall system model was then optimized using a generalized reduced gradient optimization algorithm to determine the potential energy savings through speed control with VFDs and to ascertain a control logic strategy for the building automation system to operate the heating and cooling system. A case-study was performed on a single chiller system at a museum and the model was calibrated according to logged data collected over four months. Results showed that for the system analyzed, the energy saving of optimizing the cooling tower fan system was found to be 12–15%, while the energy saving potential of optimizing the condenser water pump with the cooling tower fan was negligible. Additionally, comparing different cooling tower fan control strategies showed that a wet-bulb approach-based cooling tower control strategy was shown to have the highest correlation to the optimized fan speed with an R 2 of 0.924.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A semantics-driven framework to enable demand flexibility control applications in real buildings

Decarbonising and digitalising the energy sector requires scalable and interoperable Demand Flexibility (DF) applications. Semantic models are promising technologies for achieving these goals, but existing studies focused on DF applications exhibit limitations. These include dependence on bespoke ontologies, lack of computational methods to generate semantic models, ineffective temporal data management and absence of platforms that use these models to easily develop, configure and deploy controls in real buildings. This paper introduces a semantics-driven framework to enable DF control applications in real buildings. The framework supports the generation of semantic models that adhere to Brick and SAREF while using metadata from Building Information Models (BIM) and Building Automation Systems (BAS). The work also introduces a web platform that leverages these models and an actor and microservices architecture to streamline the development, configuration and deployment of DF controls. The paper demonstrates the framework through a case study, illustrating its ability to integrate diverse data sources, execute DF actuation in a real building, and promote modularity for easy reuse, extension, and customisation of applications. The paper also discusses the alignment between Brick and SAREF, the value of leveraging BIM data sources, and the framework's benefits over existing approaches, demonstrating a 75% reduction in effort for developing, configuring, and deploying building controls.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Field Demonstration of the Brick Ontology to Scale up the Deployment of ASHRAE Guideline 36 Control Sequences

Many commercial buildings have a vast network of sensors as part of their building automation systems (BAS) that allows opportunities for energy consumption and cost savings by deploying advanced control sequences. However, this resource is often underutilized since BAS are typically programmed with simple control sequences with limited potential to deliver on these opportunities. The recent availability of ASHRAE Guideline 36 (G36) with advanced HVAC control sequences supports control retrofits in existing buildings to unlock much of the savings potential. However, barriers such as the lack of standard naming convention of building assets and data points, proprietary equipment and BAS, and the inherent uniqueness of buildings and their systems prevent building stakeholders from adopting any “plug-and-play” implementation of G36. Instead, control vendors must often undertake the manual and labor-intensive point mapping process to identify a data stream’s functional and spatial relationship within the HVAC system along with other relevant contexts and map it to the new control sequences. The vendor must carry out the point mapping process in each individual building since the mapping is unlikely to port over to another building. Even for the same building, the point mapping process can occur multiple times if various control vendors implement different control retrofits and/or multiple control retrofits happen over the lifecycle of the building. Then, there is the likelihood that G36 control sequences are programmed uniquely to the building, preventing the same implementation from being reused in another. Therefore, this paper presents a field demonstration of how we leveraged the Brick ontology with BACnet, OpenBuildingControl’s Control Description Language (CDL), and open-source support tools to implement scalable and portable advanced building controls. These tools provide standardized semantic descriptions and relationships of the building’s assets and data points (Brick), standardized communication protocol to read from and write to the building’s BAS (BACnet), and standardized code implementations (CDL) of standardized advanced control strategies (G36). We implemented G36’s hot water supply temperature setpoint reset in a Berkeley, CA building for this field demonstration. This field demonstration aims to show how integrating these tools may streamline the deployment of advanced control sequences such as G36 in a consistent manner regardless of differences found across buildings.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Machine learning-enhanced MPC for demand flexibility in small commercial buildings: An experimental study

Small- and medium-sized commercial buildings (SMCBs) represent the majority of U.S. commercial building stock and a significant share of peak electricity demand, yet they often lack centralized building automation systems, representing a significant untapped resource for urban energy management. This infrastructure gap makes advanced control implementation challenging, limiting the potential for widespread demand flexibility. Model Predictive Control (MPC) has shown strong potential for load shifting, peak demand reduction, and cost savings, but its effectiveness is hindered by unmeasured disturbances such as internal heat gains. This paper presents a Hybrid MPC framework that integrates a physics-based gray-box building thermal model, identified using a lumped disturbance (LD) approach, with a machine learning (ML) model for forecasting unmeasured disturbances. The hybrid approach is designed for buildings with multiple individually controlled heat pump and thermostat pairs, common in SMCBs, and aims to optimize coordinated scheduling of multiple heat pumps under dynamic electricity pricing while respecting comfort constraints. The methodology is validated through both simulations of case study buildings and experimental studies at a highly-instrumented test facility. Simulation results show that the Hybrid MPC achieves substantial load shifting and peak demand reduction, approaching the performance of an ideal MPC with perfect disturbance knowledge, and outperforming a conventional MPC without disturbance forecasting. In experiments, the Hybrid MPC reduced daily HVAC energy costs by 8.7%, peak-price time load (load shifting) by 41.7%, and peak demand by 29.2% compared to baseline control, demonstrating comparable benefits to the 11.6% cost savings, 42.9% load shifting, and 23.2% peak reduction of the ideal MPC. These results demonstrate that the proposed hybrid modeling approach can significantly improve MPC performance in real-world SMCB applications without requiring additional disturbance measurements.

Demand Flexibility↗

BrickQA: Bridging the Semantic Gap in Building Operations with Dynamic Graph Exploration

While standardized ontologies like the Brick schema address data heterogeneity in Building Automation Systems (BAS), accessing this semantic data remains a challenge as domain experts often lack the expertise to formulate complex SPARQL queries. To bridge this gap, we present BrickQA, a Large Language Model (LLM)-based framework that translates natural language into executable SPARQL queries through structured query decomposition, dynamic schema exploration, and inline validation. BrickQA utilizes an iterative reasoning agent to actively navigate graph topology through dynamic exploration actions without requiring exhaustive context injection or model fine-tuning. This approach effectively mitigates hallucinations, particularly in large-scale building knowledge graphs. Empirical evaluation on BuildingQA, a standardized benchmark, demonstrates that BrickQA significantly outperforms ReAct baselines, delivering a 0.291–0.355 absolute F1 improvement while achieving 3 × –12.7 × higher token cost-efficiency. Beyond these metrics, the framework maintains structural fidelity across heterogeneous buildings and remains resilient to ambiguous queries without requiring site-specific fine-tuning. Furthermore, a case study on operational analytics validates the framework’s capability to handle temporal and aggregation constraints, effectively transforming abstract semantic models into actionable facility management insights.1

Ko, Yun-Dam↗

Data-driven building energy modeling with feature selection and active learning for data predictive control

Three gaps impede the development of cost-effective and accurate data-driven building energy modeling/models (DBEM) for energy forecasting and predictive control strategies. Gap 1: data bias is common in building operation data, but this topic is hardly studied in DBEM; Gap 2: high data dimensionality is common in DBEM, but a systematic and scalable methodology is lacking to solve the problem; Gap 3: the interactions between data bias and high dimensionality have not been systematically studied for DBEM and predictive control in buildings. In this work, to address the three gaps mentioned above, we develop a framework that integrates active learning and feature selection for DBEM used for whole building data predictive control (or DPC, which is a branch of model predictive control). The framework provides a systematic methodology and automatic workflow that starts with raw data from building automation systems to the establishment of data-driven energy models for DPC controllers. The developed strategies and framework are evaluated in a virtual testbed based on EnergyPlus and BCVTB. Improved performance and reduced computational complexity are observed from the DBEM built with the developed framework, as well as the DPC controller based on that DBEM, indicating the effectiveness of the developed framework.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Event-Based Energy Impact Tracking and Forecasting with Limited Measurements for Rooftop Units

Packaged air conditioning units and heat pumps, also known as rooftop units (RTUs), are responsible for almost 133 billion kWh of electricity usage annually on site for space cooling U.S. commercial buildings. In addition, the use of heat pumps is a trend we expect to accelerate as buildings transition from fossil fuel-based heating to electricity as a key step for decarbonizing the U.S. commercial buildings sector. However, the operation conditions and energy use of RTUs and heat pumps are usually not well monitored as they are not commonly integrated with building automation systems and lack exposed sensing and control points. To fill this gap, this paper proposes a framework for tracking and forecasting energy impacts resulting from degradation of performance and improved performance for unit servicing using limited data. The proposed framework makes use of a constrained dataset, specifically measurements of the outdoor air temperature and the power demand of individual RTUs, to track and forecast changes in energy use associated with changes in performance over various temporal horizons ranging from days to weeks. Following the detection of an RTU fault, performance degradation, or performance improvement, the framework employs a prediction model to assess the cumulative energy impact. We demonstrate the effectiveness of the method with field-collected data for servicing and degradation examples and compare the predicting accuracy of Gradient Boosting Decision Tree (GBDT) Regression models to Support Vector Regression and Linear Regression models. The results show that GBDT achieved the best accuracy for time-series validation datasets for the servicing and degradation cases, and the prediction model was able to track the cumulative energy impacts of events. The proposed framework can inform building owners of the cumulative change in energy usage of RTUs associated with performance degradation, performance improvement, or a fault.

packaged air conditioners, packaged heat pumps, ro↗

Skewering the silos: using Brick to enable portable analytics, modeling and controls in buildings

Nearly all large commercial buildings have heating, ventilation and air conditioning (HVAC) systems, lighting systems, safety and other systems controlled by a computer—a dedicated server with a building energy management system (BMS). However, these BMSs are proprietary with each building’s assets (that is, fans, valves, pumps, and their setpoints) named and coded uniquely by the BMS vendor or engineer; building analytics and control algorithms are written specific to the assets and the building. Thus, any control updates or analytics to improve building performance—especially critical to reduce greenhouse emissions or improve load flexibility—are labor intensive and costly. The Brick schema was developed so the same analysis or control algorithms can work on a variety of buildings if each is digitally represented in a Brick data model. The goal of this project was to further the development of Brick to extend it beyond an academic project with demonstrated success in a small field study, to a practical choice for industrial and commercial stakeholders seeking to realize value from building data. To do this, we executed four objectives: (1) expand the Brick schema including its modeling capabilities and vocabulary, (2) develop tools for integrating Brick with existing digital technologies and representations in buildings, (3) develop an open-source analytics platform to facilitate use of Brick in delivering data value, and (4) demonstrate Brick-driven analytics and controls in real settings.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Building Re-tuning Simulator

The Building Re-tuning Simulator (BRS) is a Re-tuning focused modeling and building automation system simulation environment.

Fernandez, Nick↗

Market Barriers and Drivers for the Next Generation Fault Detection and Diagnostic Tools

Commercial buildings in the U.S. consume as much as 30% excess energy compared to buildings that operate fault free and efficiently. Fault detection and diagnostic (FDD) platforms help to continually identify operational inefficiencies and maintain low-carbon performance. However, the recommendations generated by FDD tools need to be implemented by technicians, resulting in delays or lost savings opportunities. Recent research advances showed fault AUTOcorrection integrating with commercial FDD offerings filled this gap. Seven innovative AUTOcorrection algorithms were integrated into two FDD platforms and deployed across four buildings. The enhanced tools successfully correct faults focusing on incorrectly programmed schedules, override not released, control hunting, rogue zone, and suboptimal setpoints. Although its technical efficacy has been proven in the field, fault AUTO-correction is still early in the deployment cycle and opportunities and barriers need to be understood to reach its full potential in market transformation. This paper broadly introduces the new technology that automatically corrects HVAC faults. The authors describe in detail technology potential, market barriers, and enablers for scalability based on field testing results and interviews with the FDD providers and facility managers. The interviewees agreed that AUTO-correction can reduce the extent to which savings are dependent upon human intervention, scale building operators’ ability to act on FDD findings (especially for facilities with small operation teams), and achieve significant savings. To enable scalable deployment, future efforts are needed to overcome the barriers such as cybersecurity and accountability concerns from building operators and standardization of control parameters used in building automation systems.

Pritoni, Marco↗

Engineering Computational Practices (Rev. 1)

This manual will attempt to motivate the use of an automated build system for the purposes of computational science and engineering. As part of this motivation, the surrounding computational practices of version control, documen tation, compute environment management, and regression testing will also be addressed as applied to the practice of computational engineering. Specifically, this manual intends to motivate the adoption of these traditional software engineering practices for use in research and production engineering simulation projects. This manual is not the first such effort in the greater scientific computing community. In fact, the authors relied heavily on the lesson plans of the Software Carpentry, established to teach computing skills to researchers in 1998. As the intention for this manual is to lay out fundamental practices of engineering computing, it will not attempt to fully teach the underlying concepts and will instead reference the well designed lesson plans of the Software Carpentry. Where possible, this manual will explain to general computing practices and concepts and limit discussion of specific software implementations to examples or vehicles for practice in concrete application. The specific software taught by the Software Carpentry curriculum is an excellent starting point to learn the core concepts of computational engi neering. However, the authors have found that applications to engineering simulation and analysis require translation of these software development concepts into the language and workflows of computational engineers. Adopting these computational tools may require engineers to re-imagine their workflows in some combination of traditional engineer ing and software concepts. It has also been necessary to extend existing software build systems for engineering practices beyond the simple wrap ping of engineering software execution. Where necessary, examples of specific software and their method of extension to engineering simulations will be given, with reference to the User Manual for recommended practical use. Where this manual relies on specific implementation examples, it should be understood that the practicing engineer may find that different software is more amenable to their specific work. It is always the overall collection of computational practices is more important than any specific software implementation. The ability to recognize which concepts are implemented by a software package will make a practicing engineer agile to changing project needs, computing resources, numeric solvers, programming languages, and even available funding.

42 ENGINEERING↗