EMT-TS Hybrid Simulation for Large Power Grids Considering IBR-Driven Dynamics

The escalating integration of inverter-based resources (IBRs) poses new challenges to power systems by introducing fast dynamics with higher frequencies, which may need to be simulated by an electromagnetic transient (EMT) program. As an alternative to conducting EMT simulations for the entire system, which is typically time consuming, hybrid simulation between EMT and phasor-domain transient stability (TS) can greatly reduce the computational burden while preserving the detailed fast dynamics in the EMT zone. This paper establishes an EMT-TS hybrid simulation platform using open-source tools, specifically ParaEMT, GridPACK, and HELICS, which are the EMT simulator, TS simulator, and interface framework, respectively. Case studies on the 240-bus Western Electricity Coordinating Council (WECC) system demonstrate that the developed ParaEMT-HELICS-GridPACK hybrid simulator can accurately capture both slow electromechanical and fast IBR-driven dynamics with a 2.4x speedup.

electromagnetic transient↗

Deep Learning-enhanced Block-Diagram Modeling of Solar Power Systems

Data-driven models of power system inverter-based resources are desired to run simulations faster than with detailed electromagnetic transient models, to hide proprietary design details, to support control system design applications, and to aggregate the effects of distributed energy resources. This paper applies a customized Hammerstein Wiener framework to train block diagram models from thousands of electromagnetic transient simulations or experimental test records. The block diagram models integrate with larger grid simulations as voltagecontrolled current sources or current-controlled voltage sources for several simulators. Guidelines for block architecture and training are presented. Three-phase balanced, three-phase unbalanced, and single-phase examples all achieve an acceptable root mean square error of no more than 0.05 per-unit.

Mcdermott, Thomas E. [Private consulting company]↗

Real-World 20-Hz IBR Subsynchronous Oscillations: Signatures and Mechanism Analysis

This article provides analyses of subsynchronous oscillations associated with solar photovoltaics (PVs) observed in real world. All have oscillation frequencies at approximately 20 Hz in voltage and current magnitudes. On the other hand, in phase voltage and current, the oscillations show very different signatures. Through constructing simplified linear models and conducting sensitivity analysis, we are able to associate dynamic phenomena with the underlying mechanism and speculate the possible causes of the 20-Hz oscillations. The analysis results have all been validated via simulation results from electromagnetic transient (EMT) test beds constructed in MATLAB/Simscape.

inverter-based resources↗

A Gravitational-wave Measurement of the Hubble Constant Following the Second Observing Run of Advanced LIGO and Virgo

This paper presents the gravitational-wave measurement of the Hubble constant (H(0)) using the detections from the first and second observing runs of the Advanced LIGO and Virgo detector network. The presence of the transient electromagnetic counterpart of the binary neutron star GW170817 led to the first standard-siren measurement of H(0). Here we additionally use binary black hole detections in conjunction with galaxy catalogs and report a joint measurement. Our updated measurement is H(0) = 69(+16,-8) km/s Mpc (68.3% of the highest density posterior interval with a flat-in-log prior) which is an improvement by a factor of 1.04 (about 4%) over the GW170817-only value of 6(+17,-8) km/s Mpc. A significant additional contribution currently comes from GW170814, a loud and well-localized detection from a part of the sky thoroughly covered by the Dark Energy Survey. With numerous detections anticipated over the upcoming years, an exhaustive understanding of other systematic effects are also going to become increasingly important. These results establish the path to cosmology using gravitational-wave observations with and without transient electromagnetic counterparts.

B. P. Abbott↗

Control and Simulation of a Grid-Forming Inverter for Hybrid PV-Battery Plants in Power System Black Start

Power system restoration is an important part of system planning. Power utilities are required to maintain black start capable generators that can energize the transmission system and provide cranking power to non-blackstart capable generators. Traditionally, hydro and diesel units are used as black start capable generators. With the increased penetration of bulk size solar farms, inverter based generation can play an important role in faster and parallel black start thus ensuring system can be brought back into service without the conventional delays that can be expected with limited black start generators. Inverter-based photovoltaic (PV) power plants have advantages that are suitable for black start. This paper proposes the modeling, control, and simulation of a grid-forming inverter-based PV-battery power plant that can be used as a black start unit. The inverter control includes both primary and secondary control loops to imitate the control of a conventional synchronous machine. The proposed approach is verified using a test system modified from the IEEE 9-bus system in the time-domain electromagnetic transient simulation tool PSCAD. The simulation results shows voltage and frequency stability during a multi-step black-start and network energization process.

Nguyen, Quan H.↗

Mechanism Analysis of Wind Turbine Var Oscillations

Electromagnetic transient simulation of parallel connected 4-MW type-3 wind turbines based on original equipment manufacturer's real-code turbine model shows 1.2-Hz turbine-turbine oscillations in reactive power. This letter reveals why such oscillations occur in the individual var measurement, while being insignificant in the total var measurement, regardless of the varying grid impedance. We adopt two analysis approaches: open-loop single-input single-output analysis and network decomposition. The two approaches differ in their treatment of turbine-network interaction. The open-loop analysis shows that the turbine-turbine oscillation mode is due to an open-loop system pole being attracted to an open-loop system zero. Furthermore, we use network decomposition method to explain why this mode is observable in individual vars while not observable in the total var. The entire system of n -turbines can be viewed as n decoupled circuits. For the two-turbine case, the system has an aggregated mode and a turbine-turbine oscillation mode. Here, the aggregated mode is associated with a circuit associated with the total var, while the turbine-turbine oscillation mode is associated with the var difference and is insensitive to the grid parameters.

17 WIND ENERGY↗

Enhanced Large-Signal Stability Method for Grid-Forming Inverters During Current Limiting: Preprint

Grid-forming (GFM) inverters are a promising technology for the widespread integration of renewable energy sources in future power systems. As a key element of GFM inverter control, the primary controller governs the internal reference voltage and angle. During contingencies in the grid---such as faults, voltage drops, or frequency and phase jumps---an inverter can be forced into a current-limiting mode of operation modulating inverter dynamics, and, as a result, it is prone to losing synchronism with the grid. In this paper, we propose a novel GFM primary control method with an additional synchronization term that naturally activates during contingencies to improve the dynamic response. The method allows the inverter to remain synchronized with the grid, which improves the inverter's dynamic behavior both during and after current-limiting grid conditions and enhances grid support, including voltage support using full current capacity. The method is demonstrated for voltage, frequency, and phase jumps both in a single-machine-to-infinite-bus and a network-wide electromagnetic transient simulation of the IEEE 14-bus system with 5 GFM inverters. The simulations provide insights into the proposed synchronization method and confirm the high potential of the method, which robustly secures synchronism under severe contingencies.

current limiting↗

Adaptive Protection and Validated Models to Enable Deployment of High Penetrations of Solar PV (PV-MOD)

The availability and validation of various PV models in commercial tools differ, with some models not yet thoroughly validated for advanced inverter functionalities and reliable performance under weak system conditions. Many existing models do not fully incorporate new inverter control functions, which can affect system stability. The increasing deployment of solar PV and other inverter-based resources (IBRs), including distributed energy resources (DERs), is influencing the reliable operation of protection schemes in distribution systems and microgrids. Emerging adaptive protection schemes (APS) offer new opportunities for protecting these systems during varying configurations and DER operating conditions, though their demonstration and validation remain limited. Adaptive protection schemes face similar challenges, as they are typically designed for specific configurations. There is a growing need for tools and methodologies to streamline the deployment of adaptive protection for safe and reliable DER integration. The project main objective was to develop and validate high-fidelity generic models of solar PV facilities for stability, protection, EMT, and QSTS analyses. This objective was achieved, and these models can now be integrated into commercial software tools, enabling utilities, vendors, and developers to study high-penetration PV systems more confidently. The project also demonstrated advanced applications of these models, including the design and deployment of adaptive protection schemes in high-penetration field applications and microgrids, supporting grid safety and reliability. Several milestones were reached by the end of the project. A sophisticated inverter test plan was developed, and inverters representative of the North American marketplace were selected. EPRI and NREL tested various inverters, conforming to IEEE standards. Improvements were made to existing generic models of IBR units, IBR plants, and aggregated feeders for various analyses. The first generic electromagnetic transient (EMT) model for a solar PV plant was developed, conforming to IEEE Std 2800™-2022 and validated against laboratory measurements of a 2.2 MVA large-scale battery energy storage system (BESS) inverter. That model was then used to produce reference responses illustrating examples of validated and verified IBR plant models that pass or fail tests for technical minimum capability and performance as specified in the IEEE standard. The developed, tested, and validated generic models can be used for transmission planning, stability assessments, expansion planning, and evaluating potential future IBR interconnection requirements. They can also support interconnection screens and conformity assessments of IBR plants, including solar PV. The project significantly contributed to the ongoing standardization and model-based representation and verification of IBR responses. The project further addressed challenges of common distribution protection schemes with increasing deployment of DER by developing, validating, and demonstrating adaptive protection schemes (APS) that can improve the reliable and safe integration of DER into distribution systems. New APS were designed using improved DER models for three common distribution systems: a radial feeder, a meshed network, and a microgrid. Modeling and hardware-in-the-loop (HIL) testing of the APS were conducted, successfully showing their effectiveness and selectivity. Proof-of-concept field demonstration was achieved for two APS, i.e., one on a radial feeder and another one in a microgrid. Field demonstration could not be achieved for the APS on a meshed network, primarily due apprehension of one utility partner and also due to limited access to the protective algorithms in the network protectors. Guidelines developed from the lessons learned in the project lay out the general process followed in the design, installation, and commissioning of APS for various distribution systems. Distribution utility partners’ apprehension about field demonstration of the new APS were addressed—with varying success—by taking a stepped risk-management approach of modeling of a wide range of sensitivities first, performing in-depth proof-of-concept testing in the laboratory including HIL next, and finally deliberately implementing and commissioning the actual protection equipment and algorithms into parts of—or in parallel operation to—the three real distribution systems. Future work should include pilot projects that further show the acceptable performance of the developed APS before these schemes be rolled out more widely. Inclusion of both utility and original equipment manufacturers (OEMs) in future projects could increase chances of successful field demonstration. Despite challenges in achieving the field demonstration goal of the project for all three APS, the research significantly contributed to the innovation of adaptive protection solutions for scalable and reliable DER integration into distribution systems. This project significantly enhances the understanding of the impact of using appropriate inverter models on distribution and transmission (T&D) systems. By addressing the limitations of existing generic models, the project introduces high-fidelity models for stability, protection, electromagnetic transient (EMT), and quasi-static time series (QSTS) analyses. These models, integrated into commercial software tools, enable utilities, vendors, and developers to confidently study high-penetration PV systems. The project also demonstrates advanced applications, including adaptive protection schemes (APS) for distribution systems and microgrids, ensuring grid safety and reliability. The technical effectiveness and economic feasibility of the methods are evident through the development and validation of sophisticated inverter test plans and the selection of representative inverters. Testing by EPRI and NREL on retail, commercial, and utility-scale inverters, conforming to IEEE standards, underscores the robustness of the models. Improvements to existing generic models for various analyses further enhance their validity and applicability. The project also identifies gaps in common distribution protection schemes and designed new APS using improved DER models, demonstrating their effectiveness through modeling and hardware-in-the-loop (HIL) testing. The project’s benefits to the public are manifold. By advancing the standardization and model-based representation of IBR response, it supports transmission planning, stability assessments, and future IBR interconnection requirements. The generic models can facilitate better communication between transmission planners and developers, supporting expected IBR plant capability and performance. Additionally, the development of APS for radial feeders, meshed networks, and microgrids supports the integration of distributed energy resources (DERs) into distribution systems, enhancing grid reliability and safety. The project’s emphasis on thorough testing and simplicity in design ensures practical and scalable solutions for DER integration.

14 SOLAR ENERGY↗

A Time-Domain Protection Approach for AC Transmission Systems With Grid-Forming Resources

Ac transmission protection must reliably detect, classify, and locate short-circuit faults from voltage and current measurements. At present, these functionalities, which have been classically engineered using phasors approaches, are being challenged by the dynamic behavior and fault-current limits of converter-based generation. This paper tackles these challenges by engineering a time-domain protection approach that leverages the classical Bergeron model in a new manner. Low- and high-impedance faults are detected and classified by ascertaining how well line voltage and current measurements match the Bergeron equations. Faults are located by posing a novel one-variable optimization problem, whereas voltage and current waveforms at the fault location are estimated by unveiling rigorous relationships. The proposed elements are secure against external faults, measurement errors, and variation of line parameters and sampling time. Furthermore, these advances are tested via electromagnetic transient simulations and are significant to satisfy IEEE and North American Electric Reliability Corporation requirements.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Review of the Generic Grid-Forming Model Used by the System Operator in Chile

The objective in this project is to verify the applicability of using generic electro-magnetic transient domain models of GFM technology through a wide range of tests and system conditions proposed by subject matter experts of GFM technology through a wide range of tests and system conditions proposed by subject matter experts. For this study, we used the generic GFM electro-magnetic transient model available in the EMTP (Electromagnetic Transient Program) software library, and we assessed the model’s various GFM capabilities through 12 tests. In this report, we compare the performance of the model with that of an original equipment manufacturer (OEM) GFM model. We also share the key insights and lessons learned from this work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids

Increasing penetration levels of inverter based distributed energy resources (DERs) impact the legacy distribution system protection. Inverter based DERs provide approximately 1.2-2 pu fault current. In systems with high penetration of inverter based DERs, it is difficult for over-current based protection schemes to differentiate between normal loading conditions and a fault. Directional, distance, and adaptive forms of protection schemes are also affected by low fault currents. This paper analyzes fault generated traveling wave (TW) based high-frequency signatures in the distribution system. In order to simulate such signatures, frequency-dependent distributed parameter line modeling approach is used in this research work to represent distribution lines and underground cables. Modified IEEE 13-bus medium voltage test system is modeled in electromagnetic transient simulation tool and multiple transient scenarios are simulated in this test system. The results are analyzed to understand the high-frequency signatures that can be used to detect and locate faults under high penetration of DERs.

41 EE - Solar Energy Technologies Office (EE-4S)↗

High-Frequency Signature-Based Fault Detection for Future MV Distribution Grids

Increasing penetration levels of inverter based distributed energy resources (DERs) impact the legacy distribution system protection. Inverter based DERs provide approximately 1.2-2 pu fault current. In systems with high penetration of inverter based DERs, it is difficult for over-current based protection schemes to differentiate between normal loading conditions and a fault. Directional, distance, and adaptive forms of protection schemes are also affected by low fault currents. This paper analyzes fault generated traveling wave (TW) based high-frequency signatures in the distribution system. In order to simulate such signatures, frequency-dependent distributed parameter line modeling approach is used in this research work to represent distribution lines and underground cables. Modified IEEE 13-bus medium voltage test system is modeled in electromagnetic transient simulation tool and multiple transient scenarios are simulated in this test system. The results are analyzed to understand the high-frequency signatures that can be used to detect and locate faults under high penetration of DERs.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Stabilizing Inverter-Based Transmission Systems: Power Hardware-in-the-Loop Experiments with a Megawatt-Scale Grid-Forming Inverter

This article presents what the authors believe to be the first experimental verification of the ability of grid-forming (GFM) inverters to stabilize a transmission electric power system that is otherwise unstable. The experiments described here were performed using power hardware-in-the-loop (PHIL) simulation to connect a megawatt-scale battery inverter to a real-time electromagnetic transient (EMT) simulation of the near-future Maui power system. This allows the dynamic interactions between the inverter and the power system to be observed without putting the real power system at risk. The ability to use the actual inverter hardware removes the need to rely on a computer model approximation of the inverter's behavior.

electromagnetic transient simulations↗

Developing a PSCAD Model of the Reduced 240-Bus WECC Test System: Preprint

Fast-acting controls of inverter-based resources (IBR) introduce unprecedented dynamics to bulk power systems and island power grids, especially the high-frequency dynamics ranging from $>5$ Hz to hundreds of Hz. These oscillatory stability problems cannot be captured by the phasor domain simulations, e.g., in PSS/E, Powerworld and TSAT, due to insufficient modeling. Instead, they should be studied by electromagnetic transient (EMT) simulations by using proper EMT dynamic models. This paper develops and validates the PSCAD model of the reduced 240-bus Western Electricity Coordinating Council (WECC) test system. The PSCAD model will be released to the public, which can be used by both academia and power industry practitioners for studying the fast dynamic problems without any Critical Energy/Electric Infrastructure Information (CEII).

240-bus WECC test system↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

EMT and Phasor-Domain Co-simulation of a Low Frequency AC Transmission System for Offshore Wind Integration

This work investigates system level interactions of multi-terminal low frequency high-voltage alternating current (LF-HVac) system using back-to back converters and grid-level 60 Hz system. A co-simulation framework by integrating high- fidelity dynamic model of multi-terminal LF-HVac system in electromagnetic transient (EMT) simulation platform and phasor model of IEEE 39 bus system in transient-stability (phasor) program. The co-simulation framework for multi-terminal LF- HVac system with offshore wind integrated in a bulk power system is developed successfully and its steady state and dynamic operation is demonstrated and compared with EMT simulation. The co-simulation results show accurate representation of the dynamic responses with reduced computation burden and time compared to EMT platform.

low-frequency transmission, co-simulation, electro↗

Validation of Maui PSCAD Model: Motivation, Methodology, and Lessons Learned: Preprint

As power systems become increasingly dependent on inverter-based resources, the dominant physical and control interactions that determine system stability may no longer be accurately captured in positive sequence dynamic simulation tools; electromagnetic transient (EMT) simulations may be needed. This paper describes the process of creating and validating an EMT model of the entire Maui island transmission system in PSCAD software. The model is validated against the utility's PSSE model and against field data for an event that consisted of a single-phase fault followed by a generation trip. The methodology and lessons learned are summarized here.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Improving the Performance of Integrated Power-Hardware-in-the-Loop and Quasi-Static Time-Series Simulations

This paper introduces a novel multirate cosimulation architecture that overcomes previous challenges integrating faster real-time, microseconds-scale, power-hardware-in-the-loop (PHIL) with larger scale but slower, real-time, seconds-scale, quasi-static time-series (QSTS) simulation. Specifically, an intermediate reduced-equivalent electromagnetic transient (EMT) model duplicates the key power system topology to capture high-speed dynamics and converge hardware-power system interactions between QSTS updates. Exchanging multidimensional parameter vectors (loads, control status, etc.) between the QSTS and EMT models enables capturing the interactions of the rich, high-node-count (thousands of electrical nodes) QSTS model with the hardware. This architecture offers full spatial resolution from QSTS, including individual load dynamics, actual distribution management system controls, and nodal voltages. Simultaneously, the intermediate EMT model provides more detailed high-speed transients of key distributed energy resource hardware interactions. In addition, we use careful PHIL interface design and the exchange of complex power data, rather than current, to further improve performance. This cosimulation architecture is demonstrated by testing a simulated distribution system with an interconnected 500-kVA advanced photovoltaic (PV) inverter in PHIL. In conclusion, the architecture successfully captured PV local volt-volt ampere reactive (volt-VAR) control interactions with the larger network under time-varying electrical and weather conditions.